Why a soft starter trips equipment error with an external bypass

Motors and motor starters Published 7 min read

Short answer

The starter senses line voltage on its output terminals T1–T3 whenever control power is on. An external bypass contactor back-feeds those terminals with no ON command at terminal 3, so the diagnostics latch an equipment error as if an internal bypass contact had welded. Break the control supply at A1 through an NC auxiliary contact of the external bypass so the starter is dead whenever the bypass runs.

On this page
  1. What the starter is really checking on T1–T3
  2. Why an external bypass looks exactly like that fault row
  3. The documented fix: an NC auxiliary contact in the A1 feed
  4. Emergency-only bypasses: a disconnect works too
  5. When bypass runs end in an unbalance trip
  6. Do you need the external bypass at all
  7. Questions asked

A soft starter that latches its equipment error fault every time the motor runs through an external bypass contactor is almost never a failed starter. The unit watches its own output terminals T1–T3 for line voltage whenever control power is applied at A1 and A2. Close the external bypass and that voltage appears on T1–T3 while no ON command sits on terminal 3, so the diagnostic does what it is designed to do: it reads voltage with no command as a welded internal bypass contact or a shorted SCR, lights the device and failure LEDs, and closes the fault output. The documented fix needs one auxiliary contact: break the control supply at A1 through a normally closed contact of the external bypass contactor, so the starter is fully de-powered whenever the bypass runs.

What the starter is really checking on T1–T3 #

The voltage check on the output terminals is not a fault test; it is part of normal operation. The SIRIUS 3RW40 keeps following voltage on T1–T3 while control power is applied because it uses that measurement to time the closing of its integrated bypass contacts during the ramp. With control power on, there are only four combinations, and one of them is a fault:

Voltage at T1–T3 ON command at terminal 3 What the starter concludes
Absent Absent Ready, waiting for a start
Rising Present Normal ramp under SCR phase-angle control
Present Present Running through the integrated bypass contacts
Present Absent Equipment error latched: welded bypass contact or shorted SCR

The fault path latches. The red device and failure LEDs stay on and the group fault output at terminals 95, 96 and 98 closes its contact to report the failure to the control circuit. Because the logic is level-sensing, the fault comes straight back after a control-power cycle as long as the voltage-with-no-command condition is still present.

One caution: the same indication covers a genuine failure. If the equipment error latches with the external bypass open, the line side energized and no ON command given, the starter is reporting a real shorted power path, and the search should follow the shorted-path procedure rather than the wiring fix below. The guide to troubleshooting 3RW40 phase loss and shorted power paths walks that diagnosis step by step.

Why an external bypass looks exactly like that fault row #

The usual reason to fit an external bypass contactor is standby: start through the soft starter normally, and if the starter ever fails, close the external contactor to run the motor direct-on-line. The contactor parallels the starter, with the line side common and its outputs landing on the same motor terminals as T1, T2 and T3.

The moment it closes, line voltage reaches the motor terminals, and because T1–T3 are tied to those same points, line voltage arrives on the starter's outputs. The starter is still powered at A1, no ON command has been issued, and the fourth row of the table is satisfied exactly. The diagnostic cannot tell back-feed from a welded contact, so it latches the equipment error by design, not by defect. This is why cycling control voltage off and on never clears it while the bypass stays closed.

The documented fix: an NC auxiliary contact in the A1 feed #

The manufacturer's documented suggestion for this exact scheme is to switch off the control voltage supply on terminal A1 with a normally closed (NC) auxiliary contact of the separate external bypass contactor. With A1 dead, the control electronics are unpowered: nothing senses T1–T3, nothing can latch, nothing can ramp. The motor runs solely through the external contactor. The instant the bypass opens, the NC contact re-applies control voltage, the starter runs its start-up self-test and returns to ready.

  1. De-energize and lock out the panel, then test for absence of voltage on the line and load terminals before touching any wiring. NFPA 70E, Standard for Electrical Safety in the Workplace, 2024 edition, covers the de-energize, verification and PPE requirements; confirm what applies to your site with the authority having jurisdiction and the equipment documentation.
  2. Remove the control supply conductor from terminal A1.
  3. Route that conductor through an unused NC auxiliary contact on the external bypass contactor, then on to A1. Leave A2 on the control supply return as it is.
  4. Confirm the auxiliary contact's rated switching current covers the starter's control input draw, per the contactor's documentation.
  5. Re-energize and function-test: with the bypass open, the starter reaches ready and ramps the motor; close the bypass and verify control voltage at A1 falls to 0 V with no fault latched; open it again and verify the starter returns to ready.

One consequence to design for: with A1 interlocked, the starter's integrated electronic motor overload is out of the circuit for the whole bypass run, so whatever protects the motor through the external contactor must carry the protection duty on its own for that period.

If the unit arrives already latched, clear it before testing the new wiring: bypass open, no ON command, remove control power at A1 and re-apply. The page on diagnosing a soft starter fault or alarm before resetting it lists the checks worth running first, because a latch that survives a power cycle with the bypass open is a hardware problem, not a wiring one.

Emergency-only bypasses: a disconnect works too #

If the external contactor exists only for the day the starter fails, a lockable disconnect in the A1 feed is a valid substitute for the automatic interlock. The rule is identical, that the starter must not be powered while line voltage sits on its outputs, so the operating procedure keeps the disconnect open for the entire bypass run. Label the disconnect, note the requirement on the single-line diagram, and make the bypass-start step depend on it. The automatic NC contact is still the better answer wherever operators run through the bypass regularly, because it cannot be forgotten.

When bypass runs end in an unbalance trip #

After the interlock is in, the remaining field failure mode is an external motor protection relay tripping on current unbalance during bypass runs. The cause lives in the external path: with the starter's electronics unpowered, all the current flows through the contactor, and any pole that is not making up solidly (a pitted contact face, a loose lug, an incorrect termination) raises that phase's resistance and pulls its current down.

Measure all three line currents at the contactor load side with a true-RMS clamp; the page on measuring VFD and soft starter current with the right meter explains where average-responding clamps go wrong. Then compute the unbalance:

Unbalance (%) = (largest deviation from the average ÷ average) × 100

Worked example with illustrative inputs: IA = 48.6 A, IB = 47.9 A, IC = 44.1 A. Average = (48.6 A + 47.9 A + 44.1 A) ÷ 3 = 140.6 A ÷ 3 = 46.87 A. Largest deviation = 48.6 A − 46.87 A = 1.73 A. Unbalance = 1.73 A ÷ 46.87 A × 100 = 3.7%.

The limit is the unbalance trip setting documented for the relay in your panel, and 3.7% against a tighter setting trips exactly as designed. Fix the resistance asymmetry rather than the setting: re-torque the lugs to the documented torque, clean or replace the pitted pole, and if one pole shows a distinctly higher voltage drop under load than its neighbours, replace the contactor. If the current comes back balanced but above the motor's nameplate, that is a different problem, and the article on a motor running over nameplate amps after soft starter bypass follows that thread.

Do you need the external bypass at all #

Before wiring around the fault, question the scheme. This starter family already carries integrated bypass contacts and an electronic motor overload, which is why the manual notes a separate external bypass contactor is unnecessary in most installations: the internal contacts close automatically during the ramp, add no semiconductor losses in the run state, and the overload function keeps protecting the motor.

Keep a separate bypass where the design genuinely wants a hot-standby start path if the starter electronics fail, or where a special scheme cannot use the internal contacts, and wire the NC interlock in those cases. Everywhere else, deleting the external contactor deletes the failure mode.

Questions asked

Why does the equipment error fault come back after cycling control power?

The detection is level-sensing, not a one-shot trip. While the external bypass is closed, line voltage sits on the output terminals, so the moment control voltage returns at A1 the logic again sees voltage with no ON command and latches immediately. No amount of power cycling clears it while the bypass path is energized. The NC interlock on A1 removes the condition itself; with the bypass open, a control-power cycle then resets the unit normally.

Does an equipment error fault mean the starter is damaged?

Not necessarily. The same indication also covers a genuine failure, a welded internal bypass contact or a shorted SCR, so the test is to open the external bypass and cycle starts. If the fault never appears with the bypass open and no ON command given, the power section is healthy and the back-feed wiring was the cause. If it still latches with the bypass open, treat it as a hardware fault and test the power section before returning the starter to service.

What protects the motor while it runs through the external bypass contactor?

With A1 interlocked through the NC contact, the starter's integrated electronic overload is unpowered for the whole bypass run, so the overload relay in the external path carries the duty alone. Set its current and trip class against the motor nameplate before the first bypass run, and remember that a motor which has just soft-started carries heat into the run, so give the relay's thermal model time to reflect it.

Can the soft starter and the external bypass be closed at the same time?

No, and the interlock makes that impossible by construction. Running an SCR path in parallel with a contactor path splits current between two impedances that were never matched, and issuing an ON command while the bypass is closed violates the same detection logic from the other side. Design the scheme so exactly one path to the motor is closed at any moment: the starter only for the ramp and soft run, the contactor only while the starter is de-powered.

Keep reading

  • Troubleshooting

    Diagnosing a soft starter fault or alarm before resetting it

    Record the exact fault or alarm text, the values shown with it, and whether it appeared during start, run, or stop, before you reset, because a reset clears the diagnostic context. Then check the supply, the starter's documented ratings, the configured motor data, and the load: most trips trace to one of those four, not to a failed starter.

    Motors and motor starters

  • Troubleshooting

    Why neutral-side switching trips a smart DOL starter

    Move the direction changeover contactor to the line side so the starter feeds the selected winding directly, and leave the run capacitor between the CW and CCW terminals: in the tested 110 V, 2.6 A circuit that raised successful starts from about 1 in 20 to 19 in 20. Return-side switching lets capacitor charging current through the unselected winding distort the current the starter measures at closure, so its residual-current diagnostic reports a missing path.

    Motors and motor starters

  • How-to

    Setting a soft starter current limit without overheating the motor

    Set the soft starter current limit from the accelerating torque the load needs, not from the starter's duty figure. Estimate the limit as locked-rotor current times the square root of required torque over locked-rotor torque, check that current, dwell time and starts per hour against the starter's duty table, then verify every start with a measured peak current and acceleration time. At a 300% limit a typical design B motor develops only about a third of its full-load torque.