Current IntelPower LibraryShop main store

Explainer

Why a synchronous motor starts like an induction motor

Motors and motor starters Published 7 min read

Short answer

A synchronous motor starts as an induction machine because its amortisseur windings carry the acceleration torque until the DC field is applied. For a voltage dip study, model the start with the nameplate locked-rotor current — typically about 3.5 times full-load current rather than the 6 times an induction motor draws — and rerun the study if the real locked-rotor amps prove higher.

On this page
  1. Why does a synchronous motor start like an induction motor?
  2. How much starting current does a synchronous motor draw?
  3. How do you model the start in a voltage dip study?
  4. What voltage dip will the start actually cause on the bus?
  5. When does the induction-motor model stop being true?
  6. Does coupling the load after synchronization change the dip result?
  7. What belongs on your study inputs before you commit?
  8. Questions asked

If you are running a voltage dip study for a large synchronous motor start, treat the machine as an induction motor for the whole acceleration interval and feed the study its locked-rotor current. The reason is hardware, not convenience: a squirrel-cage-style damper winding embedded in the rotor carries the starting torque, so the machine draws an induction-motor-shaped inrush until DC excitation pulls it into step. The good news is that a synchronous machine usually draws less of it — on the order of 3.5 times full-load current against roughly 6 times for an induction motor — so an induction-motor model built on the nameplate locked-rotor current is slightly conservative. This article explains why the machine starts this way, what to model, a worked dip calculation and what changes once the field is applied.

Why does a synchronous motor start like an induction motor? #

Embedded in the rotor face, under each field pole, sits a squirrel-cage-style damper called an amortisseur winding, and that winding — not the field winding — produces the torque that accelerates the motor, so the machine behaves as an induction motor until it synchronizes.

The amortisseur winding is a set of bars sunk into the pole faces and shorted together at the ends. Energize the stator and those bars see a field rotating faster than the rotor, currents are induced in them, and they develop torque exactly the way the cage of an induction motor does. Manufacturers document this directly: the amortisseur winding gives the machine the starting and accelerating characteristics of a squirrel-cage motor, which is why the machine accelerates from standstill without any DC on the field.

The field winding plays no part in this interval. It is held disconnected from its exciter until the rotor is close to synchronous speed, so for the entire acceleration period the machine genuinely is an induction machine electrically, and it continues to behave as one until the excitation is applied and the rotor pulls into step.

How much starting current does a synchronous motor draw? #

Expect on the order of 3.5 times full-load current at the moment of energization, against roughly 6 times for an induction motor of similar rating, and treat both as rules of thumb until the nameplate locked-rotor current of your specific machine replaces them.

The difference has a structural reason. An induction motor has to establish its running flux through the same rotor bars that do the starting, so those bars must serve continuous duty and the rotor design cannot be tuned freely to cut inrush. A synchronous machine carries its running flux with the field winding instead, so the cage is sized only for starting, acceleration and damping, and the designer can aim for a lower inrush. For the other side of the comparison, see why an induction motor draws heavy current at starting.

Before trusting that multiple on any project, get the locked-rotor amps from the machine's own datasheet, because the nameplate figure overrides every rule of thumb. A guide to RLA, FLA and LRA motor current ratings explains how these nameplate figures relate to each other if the abbreviations are not part of your daily work.

How do you model the start in a voltage dip study? #

Model the machine as an induction motor for the whole acceleration interval, using its locked-rotor current as the inrush: the amortisseur winding supplies the torque, the DC field contributes nothing until pull-in, and a synchronous-machine dynamic model does not govern the dip.

In practice that means three inputs. First, the locked-rotor current from the nameplate or datasheet. Second, if that data is not yet issued, an assumed start current of 3.5 times full-load current, flagged explicitly as an assumption in the study record. Third, an induction-motor representation for the acceleration interval only — do not model field excitation during acceleration, because there is none.

Run the dip study against that induction-equivalent inrush. The real machine will be slightly easier on the supply than a conservative induction model of the same rating, which gives your results a built-in margin. When the manufacturer data arrives, check the assumed value against the actual locked-rotor current and rerun the study if the assumption was low. The hand method is the same one used for estimating voltage sag from motor inrush current, so nothing about the synchronous label changes the arithmetic.

What voltage dip will the start actually cause on the bus? #

With an example 250 A full-load nameplate, a 3.5-times start current of 875 A and a 4.16 kV bus behind 150 MVA of short-circuit capacity, the dip works out to about 4.2 percent; the same start modeled at 6 times would pull the bus down by 7.2 percent.

Worked example, with every input stated. A three-phase 4.16 kV switchgear bus with a short-circuit duty of 150 MVA. An example synchronous machine with a nameplate full-load current of 250 A and no published locked-rotor figure, so the start current is assumed at 3.5 multiplied by 250 A, giving 875 A.

  1. Source short-circuit current: 150,000,000 VA divided by (1.732 × 4160 V), that is 150,000,000 ÷ 7205, gives about 20,818 A.
  2. Dip as a fraction of bus voltage, I start divided by I source: 875 A ÷ 20,818 A = 0.042, so about 4.2 percent.
  3. Residual bus voltage: 4160 V × (1 − 0.042) ≈ 3985 V.
  4. Induction equivalent at 6 × 250 A = 1500 A: 1500 ÷ 20,818 = 0.072, so a 7.2 percent dip and a residual of about 3860 V.

This is the stiff-source quick estimate: it assumes the source impedance dominates and ignores motor contribution and X/R ratios, so treat the result as an estimate to check against your study method and the real locked-rotor data. The same arithmetic applied at another voltage level is worked through in the 11 kV bus motor starting dip calculation. And the dip percentage alone does not decide acceptance — what the rest of the bus can ride through does, which is covered in what decides acceptable voltage drop for MV motor starts.

When does the induction-motor model stop being true? #

At synchronization the roles swap: once the controller applies DC excitation near synchronous speed, the field winding carries the torque and the amortisseur cage drops back to damping duty, so the induction equivalent and its inrush no longer describe the machine.

During acceleration the field is isolated from its exciter, commonly shorted through a discharge resistor so the slip-frequency voltage induced in it cannot build to dangerous levels. As the rotor approaches synchronous speed, the controller applies excitation automatically, and the pull-in torque — developed jointly by the cage and the now-excited field — drags the rotor into step. From that instant the machine runs as a synchronous machine and the cage reverts to its steady-state job of damping oscillations.

For the dip study this fixes the window: the disturbance lasts from energization to pull-in, so your accelerating-time estimate sets its duration, while the induction-motor model sets its magnitude.

Does coupling the load after synchronization change the dip result? #

No: the dip study covers the starting inrush only, and a clutch coupling the load onto an already-synchronized machine is a running-current question — check it against the nameplate full-load amps, and if coupling pushes current past that, the motor is undersized.

The installation that raises the question — the machine starts unloaded and a clutch connects the load afterwards — puts the coupling event after the inrush window has closed, so it produces no dip event in the study. It is a sizing check instead: if the coupled load drives the running current above the nameplate full-load amps, the machine was never sized for the application, and no dip-study assumption changes that. Settle the coupled-load current against the full-load rating as a separate sizing matter and leave it out of the dip study.

What belongs on your study inputs before you commit? #

Before you commit the study you need the nameplate full-load current, the locked-rotor current, the machine kVA and the source impedance behind the starting bus; if the locked-rotor figure is missing, flag the 3.5-times figure as an assumption and rerun when the datasheet arrives.

Work through the inputs in this order:

  • Full-load current from the nameplate.
  • Locked-rotor current from the datasheet; if it is not published, record the 3.5-times assumption and the date you will replace it.
  • Machine kVA or horsepower, rated voltage and the expected accelerating time.
  • Source impedance or short-circuit duty behind the starting bus.
  • The ride-through criteria for everything else that shares that bus.

One caution for the site visit: before you open the motor terminal box or the starter to read nameplate or datasheet data, de-energize, lock out and verify absence of voltage — this is a study method, not a go-ahead for live work, and the local authority having jurisdiction and the machine documentation govern anything you do on the equipment.

Questions asked

Can a synchronous motor be started without amortisseur windings?

Yes, by ramping the supply frequency from zero with a variable frequency drive instead of applying line voltage across the line. The drive holds the voltage-to-frequency ratio near constant, so the machine never sees the across-the-line inrush spike. The drive and its protection then become part of the starting study, and the machine still follows the starting procedure its manufacturer documents.

What happens to the field winding during acceleration?

It stays out of service. At slip frequency the rotating stator field induces voltage in the field winding far above its DC rating, so during acceleration the controller keeps the field disconnected from its exciter, commonly shorted through a discharge resistor, and applies excitation automatically once the rotor is near synchronous speed. Follow the documented excitation sequence for your machine.

Does the lower starting multiple change the overload protection setting?

The stator protection still sees an induction-like current for the whole acceleration period, so it must let that current flow for the full accelerating time without tripping. Size and set it from the machine's locked-rotor current and the expected accelerating time, and confirm the trip class or relay curve against the machine documentation rather than against the synchronous or induction label alone.

Keep reading

  • Troubleshooting

    Why a single phase motor stalls on start at 200 V

    The motor stalls because 200 V at its terminals leaves about 69% of rated starting torque — torque varies with the square of voltage — and the primed pump needs more than that. Recover the margin by starting against a throttled discharge, cutting the 20 V feeder drop with a step-up/step-down transformer pair, or converting to a three-phase motor and a drive sized for single-phase input.

    Motors and motor starters

  • How-to

    Estimating voltage sag from motor inrush current

    Do not divide the motor's asymmetrical first-cycle peak by √2; screen the dip with RMS locked-rotor current as dip % = transformer Z% × I_start ÷ I_rated. On a 750 kVA, 480 V, 6% transformer, a 50 HP motor at 395 A locked-rotor dips the bus about 2.6%, to roughly 467 V — start it across the line.

    Motors and motor starters

  • Explainer

    Why an induction motor draws heavy current at starting

    An induction motor draws five to eight times full-load current at starting because at standstill, with slip at 1, the rotor load resistance term R2'(1-s)/s is zero and only winding leakage impedance limits the current. The motor behaves as a transformer with a shorted secondary until slip falls near rated speed, and only starting methods that change voltage or frequency reduce it.

    Motors and motor starters