Why a VOM reads 400V on a 220V VFD output

Variable frequency drives Published 7 min read By Current Intel engineering team

Short answer

A general-purpose VOM cannot read a PWM drive output: it averages a pulse train whose pulses sit at DC-bus height, so it can indicate near 400 V where the real fundamental is far lower. On this 220 V-fed drive the bus holds about 311 V and the motor fundamental stays well below that. Treat the reading as an artifact, enter the 220 V delta motor data, and expect the unloaded motor to run near 1500 RPM at 50 Hz.

On this page
  1. Why the VOM shows 400 V on a PWM output
  2. The 311 V ceiling behind a single-phase input
  3. What to check when the motor turns slowly
  4. Enter the delta figures, not the 380 V star values
  5. Decisions for the two symptoms
  6. Questions asked

The near-400 V reading is the meter, not the drive. A general-purpose VOM on its AC volts range responds to the PWM switching pulses on a drive output, not to the line-frequency fundamental underneath them, so it can display far more voltage than the motor ever sees. This drive, fed from 220 V single phase, holds a DC bus capped near the supply peak and cannot synthesize a 400 V motor supply at any frequency. The slow rotation is a separate, ordinary commissioning problem: on a 220/380 V motor bridged in delta for its low-voltage rating, the usual culprits are the entered motor data and the terminal-box bridges. Work the checks below in order and both symptoms resolve.

Why the VOM shows 400 V on a PWM output #

A VFD builds its three-phase output by switching the DC bus voltage into the motor lines thousands of times a second. The waveform between U, V and W is a pulse train at bus height; the motor's inductance responds to the average of that train, the line-frequency fundamental, while the meter responds to the pulses themselves. Two quantities are being confused here: what the meter displays and what the motor actually uses.

An analog VOM, and many inexpensive digital meters, measure the rectified average of the waveform and multiply it by 1.11, the form factor of a pure sine wave. On a pulse train that conversion is meaningless, and the displayed number can land almost anywhere, including near 400 V. A plain true-RMS meter does better but still reports the total RMS of everything in the waveform, switching content included, which sits above the fundamental the motor responds to; only a meter with a low-pass filter or a drive measurement mode estimates the fundamental. Reflected pulses on the motor cable can also push the instantaneous terminal voltage above the bus level for microseconds at each switching edge, which is another way a slow-responding meter climbs high.

Treat the number as an indication, not a measurement: what a VOM shows between output terminals is not the motor voltage. The output terminals are live whenever the drive has supply, even with no run command, so use leads rated for the point and keep hands clear, and prefer the drive's own displayed output voltage and frequency, or an instrument and mode intended for drive outputs. The instrument-choice logic in Measuring VFD and soft starter current with the right meter carries over to the voltage side.

The 311 V ceiling behind a single-phase input #

Inputs, all from this installation: a 220 V RMS, 50 Hz single-phase supply on the line and neutral terminals, and a MICROMASTER 420, order number 6SE6420-2UC17-5AA1, whose nameplate input reads 200-240 V, 1/3 AC, +10/-10 percent tolerance, 47-63 Hz, with a 0.75 kW constant-torque output rating and 150 percent overload for 60 s. The 1/3 AC marking is what permits single-phase input on this rating, and the supply sits inside the nameplate band.

The rule: the input rectifier charges the DC bus to the peak of the supply sine, and peak equals RMS times the square root of two, 1.414. The inverter can only switch between the bus rails, so no output pulse exceeds the bus, and the fundamental it builds is a fraction of the bus: about 0.61 times the bus at the top of the drive's linear modulation range, and at most about 0.78 times the bus driven fully into overmodulation. This is the same ceiling behind why a VFD cannot make 415 V output from 240 V input.

The arithmetic: 1.414 × 220 V ≈ 311 V on the bus. Fundamental ceiling: 0.61 × 311 V ≈ 190 V with headroom left for voltage control, and 0.78 × 311 V ≈ 243 V only if the drive runs fully into overmodulation.

Result: from this supply, the fundamental line-to-line output stays below about 243 V at any speed, and near 190 V in normal voltage control. The expected 127 V figure mixes two quantities: 127 V line-to-neutral is what a star source would deliver alongside the supply's line-to-line value, and this three-wire output has no neutral — the delta-connected motor is fed line-to-line directly.

Decision: any indication above 311 V cannot be motor voltage, because it exceeds even the pulse height; a reading near 400 V is the meter's sine conversion misfiring on bus-height pulses. Reject it, re-measure with a drive-suitable instrument, and note that the motor's delta rating is inside what this bus supports, so no higher supply is needed to run this motor correctly.

What to check when the motor turns slowly #

The motor ran with nothing coupled to it and later turned under control, so this is a commissioning and measurement problem, not a mechanical one. Run these checks in order, and stop adjusting the frequency setpoint until one of them changes the picture.

  1. Compare the commanded frequency with the actual frequency the drive displays. A 50 Hz setpoint is a request; ramps, limits or a second active reference can leave the applied frequency far lower. If the displayed actual frequency reaches 50 Hz and the shaft still turns slowly, go to check 4.
  2. Confirm which source actually commands the drive. Identify the active run-command source and the active frequency-reference source in the control settings; a potentiometer or terminal signal has no effect while a different reference is selected.
  3. De-energize the drive, lock it out, wait the bus discharge time the manual specifies, and verify absence of voltage at the motor terminals before touching anything. Then check the winding bridges in the terminal box against the nameplate diagram: for the low-voltage rating this motor must sit in delta, and the bridge patterns are easy to misread — What star and delta jumper bars mean on a motor terminal box shows both arrangements side by side.
  4. Check the motor data entered in the commissioning set. It must carry the delta figures for the low-voltage rating: rated voltage 220 V, rated current for delta, rated frequency 50 Hz, rated speed 1450 RPM. The 1450 RPM figure identifies a four-pole winding, 1500 RPM synchronous, and it is a rated-load number, not a setpoint.
  5. Check the limits: the minimum and maximum frequency settings and the acceleration and deceleration ramps. A drive held to a low maximum frequency turns slowly no matter what the keypad asks, and an overlong ramp looks exactly like a slow motor during a quick test. Watch the output current too, because a drive sitting at its current limit folds the applied frequency back.
  6. Re-test unloaded at 50 Hz and read the displayed actual frequency as it ramps. Unloaded, the shaft should settle within a fraction of a percent of 1500 RPM. If it does, the drive and motor are consistent, and any remaining slowness belongs to the driven machine.

Enter the delta figures, not the 380 V star values #

Two mistakes produce the same symptom, and they need different fixes.

If the commissioning data carries the 380 V star figures — the star voltage and the star current — while the motor sits bridged in delta, the flux reference and current model are wrong from the first ramp: the drive regulates toward a voltage it cannot produce, and its current limit is a factor of 1.73 smaller than the delta connection needs.

If the terminal box is bridged star instead, each winding sees the line voltage divided by 1.73, about 127 V against a winding rated at the delta voltage, and torque falls with the square of applied voltage, to roughly a third of rated. The motor then reaches speed unloaded but drags hard at anything more.

The fix is the same either way: enter the delta voltage and the delta current, which is 1.73 times the star current on the same nameplate. Then re-test at rated frequency. Do not use 63 Hz to mask slow rotation — above the rated frequency the drive cannot raise voltage in step with frequency, so flux and available torque both fall.

Decisions for the two symptoms #

Voltage reading: discard the VOM number. From this feed the bus sits near 311 V and the fundamental output stays below about 243 V even fully overmodulated, so the near-400 V indication is an instrument artifact. Trust the drive's display, or measure with an instrument and mode built for drive outputs.

Slow rotation: enter the delta figures for the low-voltage rating, confirm the delta bridges with the drive de-energized and absence of voltage verified, clear the frequency limits, and re-test unloaded at rated frequency, expecting the shaft within slip of 1500 RPM. If the motor still misbehaves with correct data, bridges and limits, read the drive's fault history and follow the commissioning sequence in its own manual before changing anything else.

Questions asked

Can a true RMS meter read the voltage on a VFD output?

It reads the total RMS of everything in the waveform, switching pulses included, so the displayed number usually sits well above the fundamental the motor responds to. A meter gets close to the fundamental only when it offers a low-pass filter or a drive measurement mode. For routine checks on a drive like this, the output voltage and frequency shown on the drive itself are the practical reference.

Does this drive really accept a single-phase supply?

Yes, on this rating. The nameplate of order number 6SE6420-2UC17-5AA1 reads 200-240 V, 1/3 AC, +10/-10 percent tolerance, 47-63 Hz, and the 1/3 AC marking is what permits a single-phase feed on the line and neutral terminals. Follow the connection diagram in the installation instructions, and treat a supply sagging toward the bottom of the band as a suspect whenever performance disappoints.

Why is the star current on the nameplate smaller than the delta current?

The winding current limit is the same physical limit either way. In star, two windings sit in series across the higher voltage, so the line current that matches rated winding current is 1.73 times smaller than the delta value at 220 V. If a nameplate lists 2 A at 380 V star, enter about 3.5 A for the delta connection, because 2 A multiplied by 1.73 gives 3.46 A.

What does the 1450 RPM nameplate figure tell you?

At 50 Hz, a 1450 RPM rating identifies a four-pole motor whose synchronous speed is 1500 RPM, from 120 times 50 divided by 4. The 1450 figure is rated speed under rated load, not a target: unloaded, the same motor settles within a fraction of a percent of 1500 RPM, so expect roughly that on a no-load test.

What meter rating suits measurements at the drive power terminals?

Use a meter and leads rated for the measurement category of the point being measured. At the input and output terminals of a 230 V-class drive in a fixed installation, a 600 V CAT III instrument with undamaged leads is the usual class. Select the voltage function before connecting, and never connect an instrument set for resistance to a circuit that may be live.

Keep reading

  • Troubleshooting

    Why a VFD shows low output voltage and the motor has no torque

    The drive was following a V/f curve set far below the motor's rating: 38.6 V at 50 Hz instead of the 240 V a 220 V delta winding needs, about 16 percent of the required 4.8 V/Hz, which leaves roughly 3 percent of rated torque. Set base frequency and base voltage to the nameplate, then ring out and relink the six leads for low-voltage delta.

    Variable frequency drives

  • Explainer

    Why a capacitor-run motor needs a special VFD

    A standard three-phase VFD will not run a single-phase capacitor motor usefully: the fixed run capacitor's reactance rises as output frequency falls, so the auxiliary winding loses its phase-shifted current and low-speed torque collapses. Use a drive documented for PSC or shaded-pole motors, or change to a three-phase motor.

    Variable frequency drives

  • Explainer

    Why a VFD on a 400 V supply cannot feed a 480 V motor

    No: a VFD's maximum output voltage is set by its DC bus, which comes from rectifying the input supply. On a 400 V line that bus sits near 566 V, so the highest clean output is about 400 V. Retyping the motor data as 480 V/60 Hz does not raise it and does not change the kilowatts the load demands.

    Variable frequency drives