Why IEEE 1584 arcing current can exceed the bolted fault current

Electrical safety and codes Published 6 min read By Current Intel engineering team

Short answer

The IEEE 1584 arcing-current equations are curve fits, and for some inputs they print an arcing current above the bolted fault current. The arc adds impedance, so the bolted current stays the ceiling: enter it in the energy calculation, and keep the raw output as a flagged anomaly in the study record.

On this page
  1. Can the current in an arc really exceed the bolted fault current?
  2. Why does an IEEE 1584 calculator return more than the bolted current?
  3. How do you show the number is physically impossible?
  4. What arcing current do you enter in the arc flash study?
  5. What goes in the study report and on the label?
  6. Does a second calculator printing the same number confirm it?
  7. Questions asked

An arcing current of 24.88 kA calculated from a 20 kA bolted fault is not a physical current. It is a known anomaly of the empirical equations in IEEE 1584, and the bolted value stays the ceiling. The arc inserts its own voltage drop into the fault loop, so the current through an arc is always lower than the current the same path carries with the fault bolted. When a calculator prints the opposite, trust the available fault current you started with. What follows is the input set behind this result, the circuit math that rules the inflated output out, and the exact values to enter in the study, the report and the label.

Can the current in an arc really exceed the bolted fault current? #

It cannot: a bolted fault is a zero-impedance connection that sets the maximum current the source can deliver through that path, and every arc adds a voltage drop that only pulls the current below that maximum. Think of the arc as a resistive element in series with the fault path. Its voltage drop grows with the gap and depends on the electrode arrangement, and the loop current must fall as a result.

That is also why the bolted figure, never an arcing figure, is the basis for interrupting duty and for the available-fault-current documentation on the equipment, a choice covered in which bolted fault current to use for breaker duty and arc flash.

Why does an IEEE 1584 calculator return more than the bolted current? #

Because the arcing-current equations are log-linear curve fits to arc-test data, and for some combinations of voltage, gap and current the fitted surface drifts above the bolted value: a documented anomaly, not new physics.

IEEE 1584-2018, the IEEE Guide for Performing Arc-Flash Hazard Calculations, gives the empirical method for estimating incident energy and the arc flash boundary on three-phase AC systems from 208 V to 15 kV at 50 or 60 Hz, with bolted fault currents between 700 A and 106 kA. The equations descend from the 2002 edition, the fit this anomaly was first written up against. A fit reproduces the tests where the data is dense and interpolates smoothly everywhere else; nothing in the mathematics forces the result under the bolted current at every corner. This input set even sits inside the guide's stated ranges, which is why the fit, not the input, is at fault. A tool that evaluates the equations without clamping at the physical ceiling prints the overshoot faithfully.

The input set behind this question:

Input Value
System voltage 900 V, three-phase
Supply grounded
Equipment MCC
Conductor gap 32 mm
Working distance 457 mm
Bolted fault current 20 kA
Calculator arcing current 24.88 kA

For this set the output sits 4.88 kA above the input: the ratio is 24.88 ÷ 20 = 1.244, so the calculator reads 124.4% of the bolted current, a 24.4% overshoot. Working distance plays no part, since only voltage, bolted current, gap and electrode configuration feed the arcing-current equation, so changing it will not pull the output back under the ceiling.

How do you show the number is physically impossible? #

Replace the fit with the circuit: the bolted data puts the loop impedance at 0.026 Ω and the phase voltage at 519.6 V, and any arc voltage above zero then forces the arcing current below the bolted value. The loop impedance follows from the bolted fault current directly:

Z = 900 V ÷ (1.732 × 20 000 A) = 0.026 Ω

In the simplified arc model, the loop treated as source reactance in series with an arc resistance, the current ratio is Iarc ÷ Ibf = √(1 − (Varc ÷ Vph)²), with Vph = 900 V ÷ 1.732 = 519.6 V. The arc's voltage drop subtracts from the voltage available to drive current, so the current must fall; the relation needs no fitting constants.

Put an illustrative 100 V arc across the 32 mm gap into the model: √(1 − (100 ÷ 519.6)²) = √(1 − 0.037) = 0.981, so the arc carries 0.981 × Ibf ≈ 19.6 kA, below the bolted value as physics requires. Now run the calculator's ratio backwards: 1.244² = 1.548, so (Varc ÷ Vph)² = 1 − 1.548 = −0.55. A negative square has no real solution: no arc voltage, small or large, produces 24.88 kA through this loop. The output belongs to the fitted equation, not to the circuit.

What arcing current do you enter in the arc flash study? #

Cap it: run the energy calculation at the bolted value of 20 kA in place of the equation output, and run the reduced-arcing-current case at 17 kA, taking the higher energy of the two runs.

IEEE 1584 requires both runs, energy at the calculated arcing current and at 85% of it, because the current a real arc settles at varies; the reason software reports the reduced case is covered in why arc flash software reports 85% of the arcing current. With the ceiling applied, the companion run is 0.85 × the capped value. The cap is not bookkeeping: with an inverse-time device upstream, feeding the inflated figure moves the operating point down the time-current curve into a shorter modelled clearing time, and the study then understates the energy, an error that works against the person opening the panel.

The decision for each case:

  • Output at or below the bolted current: use the calculated arcing current and its reduced companion; nothing to flag.
  • Output above the bolted current: the available current stays the bolted figure; enter that figure as the arcing current, run the companion at 0.85 of it, and flag the raw output in the record.
  • Either way, the raw output never becomes the available fault current: not for equipment duty, not on any label.

What goes in the study report and on the label? #

Both figures go in the calculation record, the bolted current as the available current and the raw output marked as an equation anomaly, while the label and the equipment schedule carry only the study's final values. IEEE 1584.1-2022, the IEEE guide for specifying the scope and deliverable requirements of an arc-flash hazard calculation study in accordance with IEEE 1584, expects the report to state the calculation method and its inputs; the anomaly note belongs beside those inputs, with both numbers and the cap you applied.

NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, requires the arc flash risk assessment, and the label carries the incident energy, boundary and PPE information derived from the final values; confirm the study method and the label format with the authority having jurisdiction and the equipment documentation. The note costs one line and answers the question the next engineer asks when the software file and the label disagree.

Does a second calculator printing the same number confirm it? #

No, because two tools printing 24.88 kA from identical inputs ran the same fitted equations twice: that is repeatability, not evidence that an arc can draw more current than the source supplies. Agreement between implementations validates nothing but the implementations; the check that counts is the circuit bound, which rejects the output for every arc voltage.

Look for whether the tool offers a clamp at the bolted current and whether its report marks the substitution; where the software documents no handling, apply the cap by hand and note it. A future edition may move the anomaly's boundaries, but the physical bound will not move.

Questions asked

Does the anomaly depend on which IEEE 1584 edition the software runs?

The handling does not. The 2018 edition re-fit the equations to a larger test set and added electrode configurations, but a fit is still a fit, so the physical ceiling applies to any edition's output. Whatever version the report cites, an arcing current printed above the corresponding bolted current is capped at the bolted value and flagged in the record.

Does one anomalous bus invalidate the whole arc flash study?

No. The overshoot affects only the buses whose equation output crosses their own bolted current. Sort the study's arcing-current column against its bolted-current column, cap and re-run the two energy cases wherever the first exceeds the second, and leave every other bus as calculated. Document which buses were capped, with the before-and-after values.

Why doesn't changing the working distance change the result?

Working distance is not an input to the arcing-current fit; it enters the energy calculation, where incident energy falls roughly with the square of the distance. At the case's 457 mm the energy differs from any other distance you might enter, but the printed arcing current is identical, because the overshoot comes from the voltage, gap and bolted current alone.

How do I check a calculator for this before I trust it?

Run the boundary cases: the largest bolted current and widest gap the tool accepts at each voltage class, and watch whether any arcing current prints above its bolted input. A tool that clamps at the physical ceiling says so in its report; one that prints the raw fit needs the manual cap. Keep the test inputs with the study files.

Keep reading

  • Explainer

    Why voltage barely changes NFPA 70E incident energy

    Incident energy is set by arcing current and clearing time, not the nominal voltage: an arc drops roughly 80–200 V of its own, so at 480 V it draws well under bolted-fault current and the clearing device sits in a slower part of its curve. The simplified equations in earlier NFPA 70E editions were stated valid 16–50 kA; below 16 kA use IEEE 1584-2018, stated for 500 A to 106 kA at 208–600 V.

    Electrical safety and codes

  • Explainer

    Handling generator fault-current decay in arc flash studies

    IEEE 1584-2018 calculates incident energy from a bolted RMS symmetrical current and models no decrement, so a decaying generator contribution cannot be entered directly. Split the event into intervals, recalculate the arcing current in each, and verify breaker pickup at the steady-state arcing current before using any result below the fixed-current value.

    Electrical safety and codes

  • Explainer

    IEEE 1584-2018 fault current range limits above 600 V

    Above the 600 V band edge the IEEE 1584-2018 model was verified only to 65 kA of bolted fault current, so a 690 V bus at 70 kA sits outside the documented range by 5 kA. Run the range check, keep the IEEE result as a labeled out-of-range sensitivity case, cross-check the Ralph Lee method, and use the higher incident energy for PPE until an engineer signs the method decision.

    Electrical safety and codes