Current IntelPower LibraryShop main store

Explainer

Why arc flash software reports 85% of the arcing current

Electrical safety and codes Published 7 min read By Current Intel engineering team

Short answer

The 11.18 kA on your report is not a different arcing-current equation: it is the reduced arcing-current case IEEE 1584 requires, your 13.15 kA hand value multiplied by the standard's reduction factor and rounded. The software calculates incident energy at both currents and reports whichever case is higher, because the upstream fuse clears more slowly at the lower current.

On this page
  1. Why does arc flash software report a lower arcing current than my hand calculation?
  2. What is the reduced arcing-current case in IEEE 1584?
  3. Why can a smaller arcing current give a higher incident energy?
  4. How do I work the reduced case by hand for a 400 V board?
  5. How do I confirm which case the study reported?
  6. Is the reduced current still 85% under the 2018 edition?
  7. Why does my transformer's secondary bolted-fault current look low?
  8. Which case goes in the report and on the label?
  9. Questions asked

Your hand calculation is right, and the software is not using a different arcing-current equation. The 11.18 kA on its report is the reduced arcing-current case that IEEE 1584 requires: your 13.15 kA hand value multiplied by the standard's reduction factor and rounded. Study software computes incident energy twice, once at the full arcing current and once at the reduced one, then reports whichever case gives the higher energy. On a 400 V board fed from a transformer protected only on the primary side, the lower current stretches the fuse's clearing time, and that is the case that wins. Below is the arithmetic, the clause behind it, and how to confirm the case in your own report.

Why does arc flash software report a lower arcing current than my hand calculation? #

Because it is showing the reduced arcing-current case: the software takes your hand-calculated current, applies the standard's 85% reduction, and displays the reduced value whenever that lower current produces the governing incident energy.

The arcing-current equation you solved is one step of the procedure, not the whole procedure. IEEE 1584 adds a second evaluation at a lower current because measured arcs scatter below the equation's prediction, and the protective device responds to the current that actually flows. The program runs both evaluations and prints the current that belongs to the worse result. Your full current is still in the study — it is the other case, one line away in the report or the study file. Nothing in your equation work needs fixing; what was missing is the second case.

What is the reduced arcing-current case in IEEE 1584? #

It is a second evaluation at a lower arcing current: IEEE 1584-2002 set the reduced value at 85% of the calculated current for systems under 1 kV, and the incident energy is computed again with the clearing time that lower current produces.

IEEE 1584, the IEEE Guide for Performing Arc-Flash Hazard Calculations, standardizes how you get from bolted-fault current to arcing current, incident energy and the arc flash boundary for three-phase arcs. Its arcing-current equations are regression fits to test arcs, and individual arcs wander below the fit, so the guide covers that scatter by making you evaluate the reduced current and keep the higher energy of the two runs. The 2018 edition keeps the two-case check but derives the reduction from a calculated arcing-current variation factor instead of a fixed number. Both editions remain in service, so a study's basis has to state which one it runs.

Why can a smaller arcing current give a higher incident energy? #

Because clearing time moves faster than current on a fuse's time-current curve: a 15% drop in arcing current can multiply the clearing time several times over, and incident energy grows with current and time together.

Illustration only, not fuse data: if the upstream fuse clears the full current in 0.1 s and the reduced current in 0.5 s, the time term grows fivefold while the current term shrinks by well under a fifth, so the reduced case ends up carrying roughly four times the energy. The real times come from the fuse's published time-current curve, read once at each case current.

The arrangement in this study is the worst case for that effect. With no secondary main, a secondary arc is cleared by the primary fuse through the transformer, and the arc's reflected current lands on the steep part of that fuse's curve, right where the two cases separate the most. The same clearing-time dominance is why control panel incident energy is set by upstream clearing time rather than by the panel itself. The clearing time itself is its own problem, covered in what clearing time applies to a transformer secondary arc.

How do I work the reduced case by hand for a 400 V board? #

Two lines of arithmetic settle it: the reduced current is 0.85 × 13.15 kA = 11.1775 kA, which rounds to the 11.18 kA on the report, and the cases then stand or fall on their own clearing times.

Take a hypothetical study with the same shape as the one that raised the question — an example, not a recommendation. A 2000 kVA, 13 kV/400 V transformer has only an 80E high-voltage fuse on its primary and no secondary main. The main board's secondary bolted fault is 29.67 kA. The equipment is enclosed, the arc is in a box, the gap is 32 mm at 0.4 kV with k = −0.097, and the hand calculation gives the full arcing current used above.

Case Arcing current Clearing time read at Governs when
Full 13.15 kA the full current its energy is the higher one
Reduced 0.85 × full = 11.18 kA the reduced current its energy is the higher one

Read the fuse's published clearing time at each of the two currents — they will differ, and the reduced case takes the longer one. Compute the incident energy for each case with its own current and its own time, as the guide's procedure lays out, and compare the two. In this study the reduced case wins, which is why its current is the one on display.

How do I confirm which case the study reported? #

Divide the displayed arcing current by your hand value at the same node: a quotient equal to the reduction factor identifies the reduced case, and the report's own case marker confirms it.

  1. Check the arcing-current line for a footnote, asterisk or case label. Study programs commonly tag the reduced case right there, and the tag is your confirmation that the comparison ran.
  2. Compare the two clearing times in the report or study file. The reduced case must show the longer time; identical times mean the device curve was not re-read at the lower current.
  3. Match the model's inputs to the hand calculation — same gap, same enclosed or open configuration, same voltage base. A gap mismatch changes the current and spoils the ratio test.
  4. Check the project's frequency and voltage settings, since the bolted-fault input that feeds both cases comes from that model.

Is the reduced current still 85% under the 2018 edition? #

No: the 2018 edition keeps the reduced case but derives its size from a calculated arcing-current variation factor, so the reduction now moves with the gap and the electrode configuration.

The variation-factor equations sit in Section 4.5 of IEEE 1584-2018. The two-case evaluation itself is unchanged — energy at the full current with its clearing time, energy at the reduced current with its own, keep the larger. That gives you a quick diagnostic: a reduction that is exactly the old fixed fraction at every node is the 2002 method's signature, while a 2018 run shows a reduction fitted to its own gap and configuration. In most study packages the edition is a project-level arc-flash setting, so open the project's calculation options and read which edition is active before comparing hand and software numbers. Where the 2018 model's voltage and current limits sit is covered in IEEE 1584-2018 fault current range limits above 600 V.

Why does my transformer's secondary bolted-fault current look low? #

A quick nameplate check will tell you: for this example, the transformer alone would deliver about 32.8 kA into a bolted secondary fault, so a reported 29.67 kA means the model carries impedance beyond the transformer.

The arithmetic: full-load current is 2000 kVA ÷ (√3 × 0.4 kV) = 2887 A, and the transformer-limited bolted fault is that current divided by the impedance written as a fraction, 2887 A ÷ 0.088 = 32.8 kA. The shortfall below that number comes from the source impedance behind a finite primary fault level and from any cable between the transformer and the board, so a modest gap is expected; a large one points to a wrongly entered impedance or tap. Trace it, because the bolted current feeds both arcing-current cases — but it does not change the reduced-case explanation: the displayed value is still the reduction applied to whatever full current the model computes. The derivation behind this check is spelled out in calculating transformer interrupting current from impedance.

Which case goes in the report and on the label? #

The higher incident energy goes in the report, whichever current produced it — here the reduced case — so the reduced run's energy, clearing time and boundary are the published values.

  • Full-current case: keep the run in the study file. It governs, and gets published, when the clearing device gives both currents nearly the same clearing time — typically a breaker's instantaneous element — and its energy comes out higher.
  • Reduced case: expect it to govern behind a fuse on the steep part of its curve, as with primary-only transformer protection. When it wins, publish its energy, which was computed with the longer clearing time.
  • Both cases: run them at every node the study calculates, keep both in the file, publish one.

NFPA 70E, the 2024 edition of the Standard for Electrical Safety in the Workplace, covers worker protection and requires the arc flash risk assessment whose PPE selection hangs on the posted incident energy. Confirm the study basis and the posted values with the authority having jurisdiction and the equipment documentation.

Questions asked

Does the reduced case also set the arc flash boundary?

Yes. The boundary is the distance at which the governing incident energy falls to the boundary threshold, so it comes from the same winning case as the posted energy. When the reduced case governs, expect a larger boundary as well as a higher energy, because both grow from the longer clearing time.

Does the reduced case matter as much behind a breaker as behind a fuse?

Usually not. A breaker's instantaneous element clears in roughly the same few cycles whether the arc current is full or reduced, so the full-current case governs. The reduced case wins where clearing time is sensitive to current, which means fuses on the steep part of their time-current curves.

What do I do when both cases give nearly the same incident energy?

Report the higher one and keep both runs in the study file. When the difference is a few percent, the choice does not change the PPE decision, but the record should still show the comparison was made, because a revised fuse curve or a changed source can move the result next time.

Does the arc flash label need the arcing current?

No. Under NFPA 70E, 2024 edition, the Standard for Electrical Safety in the Workplace, the label carries the nominal voltage, the arc flash boundary and the incident energy at the working distance or the PPE category. The arcing current and the case that governed stay in the study file behind the label.

Keep reading

  • Explainer

    Why voltage barely changes NFPA 70E incident energy

    Incident energy is set by arcing current and clearing time, not the nominal voltage: an arc drops roughly 80–200 V of its own, so at 480 V it draws well under bolted-fault current and the clearing device sits in a slower part of its curve. The simplified equations in earlier NFPA 70E editions were stated valid 16–50 kA; below 16 kA use IEEE 1584-2018, stated for 500 A to 106 kA at 208–600 V.

    Electrical safety and codes

  • Explainer

    Handling generator fault-current decay in arc flash studies

    IEEE 1584-2018 calculates incident energy from a bolted RMS symmetrical current and models no decrement, so a decaying generator contribution cannot be entered directly. Split the event into intervals, recalculate the arcing current in each, and verify breaker pickup at the steady-state arcing current before using any result below the fixed-current value.

    Electrical safety and codes

  • Explainer

    Should ground fault clearing time set arc flash incident energy

    No. IEEE 1584-2018 bases the incident energy on the three-phase arcing fault, and the clearing time comes from the phase overcurrent device at the arcing current, so the ground fault element never sets the label value. It still earns its place in the protection study, and outdoor open-air equipment under the NESC keeps its line-to-ground basis.

    Electrical safety and codes