Comparison
Why induced voltage defeats simple phase loss protection
Short answer
A spinning motor regenerates roughly half its normal voltage onto an open phase, so a phase loss relay that watches voltage alone can hold the contactor in while the motor single-phases. Set the relay's dropout above your measured back-feed voltage — or drop voltage sensing for per-phase current, unbalance or phase-angle detection, which the back-feed cannot fool.

On this page
- Where the voltage on an open lead comes from
- Setting the dropout threshold on a 230 V motor that back-feeds 110 V
- Comparing the four detection methods
- What current sensing sees that voltage cannot
- Phase-angle and sequence checks
- Prove it on your machine before you trust it
- The decision, case by case
- Questions asked
Judge a phase loss by current or by phase angle, not by voltage presence alone. When one line opens on a running three-phase motor, the machine keeps spinning and its own windings regenerate voltage onto the dead lead, commonly near half the healthy phase voltage. That is high enough to hold in a voltage-sensing relay whose dropout sits under the induced reading, so the contactor stays closed and the motor single-phases until the windings cook. This article explains where that induced voltage comes from, works the dropout-threshold arithmetic for a motor whose open lead back-fed about half of nominal, compares the four detection methods, and ends with the decision for each case: set the threshold above a measured back-feed when you can prove it, and use current-based detection when you cannot.
Where the voltage on an open lead comes from #
When a fuse blows or a lug burns open on one line while the motor runs, the two healthy lines keep energizing the stator. The rotor still carries flux, the three windings are magnetically coupled to each other, and the machine now behaves partly like a generator feeding its own disconnected terminal. Because the windings are symmetrical, that terminal settles near the midpoint between the two live phases: roughly half the normal voltage to neutral, not zero.
On the installation behind this article, the open lead still read 110 V to neutral and 190 V between lines on a supply that sits at 230 V to neutral when healthy — 48% of nominal — with the contactor closed and the motor turning. Treat those as reported readings from one motor at one load, not a guaranteed fault signature: load, speed and whether the windings are star or delta connected all move the number, which is why the threshold has to come off your machine rather than off this page.
A relay-per-phase presence circuit fails here in a specific way. Three sensing coils, one per line, with contacts in series in the contactor's seal-in path, protect only if at least one coil drops out when a line opens. If every dropout threshold sits below the induced voltage, all three coils stay picked up, the seal-in holds, and nothing in the voltage domain ever sees the fault. Voltage-based monitors have other blind spots in the same family: why phase loss monitors miss single-phasing on an open delta is the same failure wearing a different supply topology. Note too that the fault shows up in both reference systems at once — the general arithmetic connecting them is worked through in this phase-to-neutral versus phase-to-phase voltage compatibility guide.
Setting the dropout threshold on a 230 V motor that back-feeds 110 V #
- Nominal supply: 230 V line-to-neutral, 400 V line-to-line, three phase — from the supply single-line diagram and the motor connection data.
- Measured open-phase voltage with the motor spinning: 110 V to neutral and 190 V between lines — the reported reading from the installation above; measure your own before setting anything.
- Relay: adjustable phase-failure relay sensing line-to-neutral, dropping out on undervoltage, contact wired in the contactor seal-in path.
The rule in words: the dropout threshold must sit above the back-feed the open lead actually shows, so the relay drops out during the fault, and below the lowest voltage the supply sits at during an ordinary sag, so it does not nuisance-trip. The window on this motor runs from the back-feed fraction up to full nominal, and a setting near the middle of the window, about 65% of nominal, keeps margin on both sides.
The arithmetic:
- Back-feed fraction: 110 V ÷ 230 V = 0.48. Line-to-line: 190 V ÷ 400 V = 0.48.
- Threshold, line-to-neutral: 230 V × 0.65 = 149.5 V, set as a 150 V dropout.
- Threshold, line-to-line: 400 V × 0.65 = 260 V.
Result: with the phase open, the measured reading sits far below the 150 V setting, so the coil de-energizes and the contactor opens; healthy, the line sits at nominal, and the setting is 35% below that, so the relay rides through any sag shallower than 35%. Decision: if your own open-phase measurement stays under the setting you computed this way, adopt it and prove it with the test near the end of this article; if the back-feed on your motor comes back above your candidate threshold, no voltage setting can separate fault from healthy on that machine — go to per-phase current or unbalance detection.
Comparing the four detection methods #
| Method | What it measures | Can the back-feed defeat it? | Needs a neutral | Where it fits |
|---|---|---|---|---|
| Per-line voltage relay, line-to-neutral | Voltage from each line to neutral | Yes, whenever the induced voltage sits above its dropout setting | Yes | Grounded systems with a neutral brought to the starter |
| Line-to-line voltage relay | Voltage between line pairs | Yes — an open pair still shows about half the line voltage | No | Delta motors and ungrounded systems, threshold permitting |
| Phase-angle and sequence monitor | Order and 120° spacing of the three voltages | Only if tuned carelessly; it judges the pattern, not the magnitude | No | Starters that also need reverse-phase blocking |
| Per-phase current sensing | Current in each motor lead | No — an open lead carries no current however high its voltage sits | No | Any motor; the same inputs feed overload and unbalance functions |
The two voltage rows are the cheap, simple answer, and their whole logic rests on the fault producing a voltage the relay can separate from healthy. The back-feed attacks exactly that assumption, so treat both as acceptable only after a measurement on your machine.
The current rows measure what the motor is doing rather than what the supply shows, which is why they form the default recommendation: an open lead reads as no current regardless of the voltage sitting on it. The angle row is voltage-based but pattern-based rather than magnitude-based, and it lives or dies by a timing window derived from your supply frequency.
What current sensing sees that voltage cannot #
An open lead carries no current no matter what voltage the motor induces on it, so sensing each motor lead answers the only question that matters: is current flowing in all three lines. Under single-phasing, current in the open lead falls to nothing while the two live leads carry elevated current, and the unbalance between them dwarfs anything a healthy motor produces. NEMA MG-1, the motors and generators standard, puts the voltage-unbalance derating point at 1% and treats current unbalance above 10% the same way — check the edition your machine is built to for the exact curves. A running single-phase fault is past both limits the instant it occurs, which is what makes unbalance sensing fast where a thermal element is slow.
The trap is relying on the thermal overload alone. An overload relay set by the method in setting overload relays from motor nameplate full-load current protects against sustained heating, and a motor that was running light before the fault may never draw enough on its two live lines to reach trip. It can run that way long enough to bake one phase of the rotor circuit. A dedicated phase-supervision or negative-sequence function trips on the asymmetry itself, not on the heating it eventually causes; what current-only motor protection can and cannot detect maps which functions catch which fault, and why a VFD trips a motor phase loss fault and what to measure covers the same fault from the drive's output side.
Phase-angle and sequence checks #
In a healthy supply the three line voltages sit 120 electrical degrees apart in a fixed order, so a lost phase shows up as a missing or displaced crossing even though the magnitude on the open lead stays near half of normal. Sensing needs isolation per line — linearized optocouplers, isolated voltage transducers or small sensing transformers — and a timing window derived from the supply frequency and your edge convention.
Derive that window from the measured period, not from a memorized figure. At 60 Hz the period is 1 ÷ 60 Hz = 16.67 ms, and corresponding crossings of adjacent phases sit a third of a cycle apart: 16.67 ms ÷ 3 = 5.56 ms. At 50 Hz it is 20 ms ÷ 3 = 6.67 ms. If the design timestamps every crossing of every line, consecutive crossings arrive twice as often: 16.67 ms ÷ 6 = 2.78 ms at 60 Hz, and 20 ms ÷ 6 = 3.33 ms at 50 Hz. The 2.8 ms figure that circulates with this kind of circuit matches only the 60 Hz, count-every-edge convention; carry it to a 50 Hz supply and the real spacing is 3.33 ms, a 20% error big enough to swallow a tight window. Write the frequency and the edge convention next to the thresholds in the design notes.
Prove it on your machine before you trust it #
Wire the relay and set the thresholds with the panel dead: de-energize the feeder, lock it out and test for absence of voltage before touching a lug, and run any step that must happen live under your plant's energized-work rules with the correct protective equipment.
The measurement that settles the whole method is the open-phase back-feed, and the only way to get it is to open one line while the motor spins. Keep the test brief and observed: start the motor normally, open one supply-side line through an arrangement made beforehand (a test switch or a single fuse, never a control wire that leaves the contactor state ambiguous), record the open lead's voltage to neutral and between lines, confirm the relay drops out and the contactor opens, then close the line promptly, because a single-phased motor is overheating every second it runs. Repeat for each of the three lines. Then restore the phase and verify the contactor does not pull itself back in on the returning or induced voltage — that unexpected-restart behavior is precisely what the machinery safety standard is written against.
For the standards background: IEC 60204-1:2016, the safety standard for the electrical equipment of machines, requires that a supply disturbance, including the loss of a phase, must not create a hazardous condition or an unexpected restart, and it expects protective measures where phase failure can produce one. Confirm the applicable clauses and any local amendments with the authority having jurisdiction and the machine's documentation before you sign off the design.
The decision, case by case #
- Neutral at the starter and a measured back-feed below your planned threshold: a line-to-neutral phase-failure relay with the dropout set mid-window — the worked example's placement — proven by the open-phase test.
- Delta-connected motor or no neutral: line-to-line sensing with the same mid-window arithmetic against your measured line-to-line back-feed, or go straight to current sensing.
- Back-feed too close to the healthy voltage to leave a clean window, or no chance to measure it: per-phase current or current-unbalance/negative-sequence detection. This is the default whenever the voltage method cannot be proven on the machine it must protect.
- A motor that runs lightly loaded: do not count on the thermal overload alone; add phase supervision whichever method you choose.
- A drive in the motor circuit: let the drive's phase-loss function do the work and coordinate the upstream protection with its trip.
Questions asked
Why did my motor keep running after a line fuse blew even though I had phase loss protection?
Check the relay's dropout threshold against the voltage on the open lead. A spinning motor feeds voltage back onto the open line through its own windings, and that lead can sit near half the healthy phase voltage. If the relay only drops out below that reading, all three sensing elements stay energized and nothing trips. Measure the back-feed on your motor during a controlled open-phase test, set the threshold above it, or move to current-based detection.
How do I protect a delta-connected motor when there is no neutral?
Sense line-to-line voltage or line current. A line-to-line phase-failure relay works if its dropout threshold sits above the voltage the open pair still shows while the motor spins, so run the open-phase test and record that reading before choosing the setting. If the induced voltage sits too close to the healthy voltage for a clean window, per-phase current sensing or a current-unbalance function is the reliable route, and neither one needs a neutral.
Why didn't my overload relay trip while the motor was single-phasing?
An overload relay models heat, not phase symmetry. After one line opens, torque drops, and if the motor was running below full load the current in the two live lines can settle under the overload setting, so the thermal element never reaches its trip point while the rotor runs hot. NEMA MG-1 treats current unbalance above 10% as requiring derating, and a single-phased motor sits far past that. Add a dedicated phase-loss or unbalance function.
What time interval should a phase-angle monitor expect between zero crossings?
Derive it from the supply frequency and your edge convention. Corresponding crossings of adjacent phases sit 120 degrees apart, which is 5.56 ms at 60 Hz and 6.67 ms on a 50 Hz supply. Counting every crossing of every line halves those intervals, giving 2.78 and 3.33 ms. State both the frequency and the convention in your design notes so the window is never tuned to the wrong supply.


