Why a VFD trips a motor phase loss fault and what to measure

Variable frequency drives Published 8 min read By Current Intel engineering team

Short answer

Measure all three motor phase currents under load before you reset a VFD motor phase loss fault. Imbalance between the readings, not a continuity check with the circuit dead, is what finds the loose joint, open conductor or failed winding behind the trip; the worked example shows the arithmetic.

On this page
  1. What the phase loss fault actually watches
  2. Why the circuit reads fine de-energized and trips under load
  3. Worked example: 10.0, 10.0 and 7.0 A at the drive output
  4. The measurement sequence
  5. What each result decides
  6. Resetting and the alarm-disable question
  7. Questions asked

A motor phase loss fault means the drive has measured one of the three conductors feeding the motor carrying much less current than the others, or none, and has stopped the motor to keep it from single-phasing. Before you reset, measure all three phase currents with the machine running at the speed and load where the trip happened. A high-resistance joint, a broken strand or a failing contactor pole can read perfectly with the circuit de-energized and still starve one phase under load, because the imbalance only exists when load current flows through the resistance. This article works the circuit from the drive output terminals to the winding, gives the arithmetic that judges the readings, and keeps the fault separate from its two neighbors: a supply-side missing phase fault and a ground fault, which is insulation failure rather than phase continuity.

What the phase loss fault actually watches #

A drive measures its own output current to control the motor, and the phase-loss function compares those measurements. On the drive behind the original case, an Emotron VFX, the manufacturer documents the function under the name Motor Lost and describes it as detecting a fault in the motor circuit: the motor, the motor cable, a thermal relay in that circuit, or an output filter where one is fitted. Other makers sell the same protection as output phase loss or phase failure monitoring. Whatever the keypad calls it, the scope is the same: everything between the output terminals and the windings sits inside the detection path, so the fault list includes the cable, every termination, every series device and the motor itself.

The trip is a symptom, not a location. The drive knows the three currents are unequal; it cannot know whether the extra resistance sits in a cable gland, a contactor pole or a winding turn. Locating it is your measurement job.

Two neighboring faults are easy to confuse with this one. A missing phase fault raised by a drive fed from a single-phase supply is input-phase detection on the supply side, a different function covered in why a drive shows a missing phase fault on single-phase supply. A ground fault is current leaking to earth through failing insulation, not unequal phase currents; the case where that trip appears while insulation tests read good is covered in VFD ground fault at start with good megger readings.

Why the circuit reads fine de-energized and trips under load #

Ohm's law is the reason a dead circuit hides a live fault. The voltage dropped by a resistive joint equals the current through it times the joint's resistance, so a continuity meter pushing milliamps sees millivolts and reports the conductor as sound. Under motor load the same joint drops real volts, steals current from its phase, and heats on every pass of current. The resistance is not fixed either: it rises with oxidation and loose clamping pressure, and it changes with temperature, vibration and cable movement. That is why these faults are intermittent, and why a trip that follows machine warm-up or cable flex points directly at a joint rather than a conductor.

A fully open phase is the limit case: the motor tries to run on two phases, torque collapses, and the windings that still carry current overheat quickly. The partial case, a joint that is merely resistive, is what produces an imbalance the drive can measure and trip on while the motor still turns. Both damage the motor; the drive stops to prevent exactly that heat, which is why resetting it without finding the resistance buys nothing.

Worked example: 10.0, 10.0 and 7.0 A at the drive output #

The original case gave no motor size, so take a typical one: a motor at the trip condition, with a true-RMS clamp reading 10.0 A, 10.0 A and 7.0 A on the three output conductors under steady load. These are example readings for the calculation; the drive's own trip margin comes from its manual, not from this example.

The rule is the deviation-from-average method, the same one used for voltage unbalance in NEMA MG 1: average the three readings, take the reading farthest from that average, divide by the average and multiply by 100.

  • Average = (10.0 + 10.0 + 7.0) ÷ 3 = 27.0 ÷ 3 = 9.0 A
  • Largest deviation = |7.0 − 9.0| = 2.0 A
  • Imbalance = 2.0 ÷ 9.0 × 100 = 22.2 percent

The result is 22.2 percent current imbalance, concentrated in the conductor reading 7.0 A. The decision: a spread of 22.2 percent under steady load is not meter scatter or normal motor behavior — treat the low leg as carrying extra resistance and find the joint, series device or winding behind it before resetting. The trip margin of the phase-loss function itself is documented per drive model in the drive manual; whatever that margin is, real and repeatable imbalance of this size is a circuit fault to be found, not a reset to be pressed.

Prefer currents over voltages for this comparison. A drive output is a pulse-width-modulated waveform, not a sine wave: an average-responding meter under-reads it, two meters can disagree on the same terminals, and the voltage numbers depend on the instrument. A true-RMS clamp reads the actual waveform shape and gives usable RMS current, and the drive's own display values are usable too.

The measurement sequence #

This list opens panels and the motor terminal box. NFPA 70E, 2024 edition, covers work on or near energized electrical equipment and requires de-energizing, locking out and verifying the absence of voltage before anything is opened; any measurement taken with the equipment running is energized work done inside the arc-flash boundary and PPE your own study assigns. Confirm the details with your authority having jurisdiction and the equipment documentation — and note that the drive manual states a wait time for its DC bus to discharge after the supply is switched off, because dangerous voltage persists inside the drive.

  1. Before any reset, pull the drive's fault history and record the fault name, timestamp, speed reference and load at each occurrence. A fault that returns at one operating point behaves differently from one that follows cable movement.
  2. Use the drive display first for the three phase currents; if the keypad shows a single current value rather than one per phase, clamp each output conductor with a true-RMS clamp and apply the calculation above.
  3. De-energize, lock out, verify the absence of voltage at the drive output and the motor terminals, and wait the bus-discharge interval the manual states.
  4. Inspect every termination in the three paths: drive output terminals, intermediate junctions or terminal strips, the thermal relay if the circuit has one, contactor poles and the motor terminal box. Look for discoloration, corrosion, broken strands and loose hardware; remake the suspect joint and tighten to the torque the documentation specifies.
  5. Continuity-test every series device phase by phase: each fuse, the thermal relay poles, the contactor poles. Replace an opened fuse only with the same type and rating, and find the reason it opened — fuses rarely open without a cause.
  6. Disconnect the motor cable at both ends and continuity-test each conductor end to end, so the drive's electronics stay out of the meter path and the cable is judged alone.
  7. At the motor terminals with the cable leads separated, measure winding resistance phase to phase and compare the three readings. A material difference points inside the motor — winding, internal joint or terminal links — not in the cable.
  8. Reassemble and run the machine at the speed and load of the original trip, then re-measure the three currents. The repair is proven when the spread between the readings collapses to nearly nothing and holds through the operating point that used to trip.

What each result decides #

What the measurements show What it points to Decision
One phase reads near zero under load Open conductor, opened fuse, failed contactor pole or open winding Isolate the affected path and continuity-test it piece by piece until the break shows
A third phase reads low under load while continuity passed dead A high-resistance joint at a termination Remake that joint and re-measure under load before calling the repair done
Winding resistances differ materially phase to phase Winding fault or a bad internal connection Repair or replace the motor; the cable and terminations are not the culprit
Currents read balanced but the fault returns A joint that changes with heat or vibration, or wrong motor data in the drive Reproduce the exact trip condition, compare the fault-history timestamps, and verify the motor data the drive uses

Resetting and the alarm-disable question #

A reset that succeeds once proves the joint reconnected, not that it is sound. Repeated resets of a resistive connection keep heating it until the conductor finally parts; the failure where a motor T-lead burns open ahead of any ground fault is that end state, described in when a motor T-lead burns open before the ground fault. Disabling the phase-loss function, which the drive settings allow where the monitoring is not required, removes only the messenger: a motor that is genuinely single-phasing still overheats with the alarm off. Leave the function enabled, keep a correctly set overload relay over the motor as the second layer, and fix the circuit. The protection exists because the damage it prevents is real and fast.

Questions asked

Does a motor phase loss fault mean the supply side has a problem?

Not usually. Drives watch the input and the motor circuit with separate functions: a supply-side phase loss normally raises its own input or supply fault, while a motor phase loss fault points at the conductors, terminations, contactor poles, fuses or windings between the drive and the motor. Severe supply imbalance can still show up as current imbalance at the motor, so if the three output readings balance, log the three input currents next.

Can I trust the current value shown on the drive keypad?

For spotting that something is wrong, yes: the drive measures its own output current to control the motor, and that value belongs in the fault history. But many keypads show one current value rather than one per phase, so the keypad cannot tell you which leg is low. Use the display to confirm the fault, then clamp each output conductor separately for the three-way comparison.

Why does the fault only appear at some speeds or loads?

Two reasons. The imbalance the function detects grows with current, so at light load a resistive joint produces a smaller difference and may stay under the trip margin. And contact resistance itself moves with temperature and vibration, so a joint can open only when the cable flexes or the panel is warm. Reproduce the speed, load and cable position of the original trip before calling the repair finished.

What motor data should I verify in the drive after fixing the circuit?

Check that the motor data entered in the drive matches the nameplate on the motor: at least the rated current, voltage, frequency and speed. If the rated current is entered far from the real value, the protection functions judge their measurements against a wrong reference and can trip a healthy motor or miss a failing one. Correct the data against the motor's documentation before retesting.

Keep reading

  • Troubleshooting

    VFD output phase loss fault: tracing the broken phase

    An output phase loss fault means the drive's current monitor sees one of the three phases at its U, V and W terminals drawing no current or far less than the others, so the break is almost always between the drive and the motor windings: the cable, a termination, output fusing, a contactor pole or the winding itself. Lock out, compare the three line-to-line resistances at both ends, and the readings name the broken phase.

    Variable frequency drives

  • Troubleshooting

    VFD ground fault at start with good megger readings

    A drive that trips ground fault only when the move command is applied, while cable and motor megger in the hundreds of megohms, has an intermittent leakage path inside the motor terminal box that a DC test cannot reproduce. De-energize, reterminate and reinsulate the leads, and dress them so the cover cannot pinch a phase against ground, and leave the ground-fault threshold and the fault itself armed.

    Variable frequency drives

  • Troubleshooting

    Finding a 113 V drop between a VFD and the motor terminals

    The drop is real, it lives in the path between the drive lugs and the terminal box, and it works out to about 0.36 Ω per phase — enough to dissipate roughly 11 kW per phase if it is resistance. Verify the reading with a drive-rated meter, then find it with an infrared scan under load and a micro-ohmmeter on every joint; the motor is downstream of both measurement points and is not the cause.