Explainer
When a motor T-lead burns open before the ground fault
Short answer
On a large motor, a T-lead can burn open in the middle of its run and erase over an inch of copper before any ground fault appears. A strand break arcs at every current peak, erodes copper progressively, and only flashes to a grounded surface at the end. That is why the megohmmeter reads fine and the 51G ground relay is the only function that trips.
On this page
When a large motor trips its ground relay and the insulation then tests clean, the megohmmeter cannot tell you which failure came first. On the reported case worked through here — a 13.2 kV, 3,500 hp vertical squirrel-cage motor that tripped its 51G element and was later found with an open B-phase lead — the evidence orders it conductor first. A strand-level break in the T-lead arced on every current cycle, eroded about 1.5 inches of copper at a spot with no joint, and only then flashed to the grounded stator surface about 4 inches away. Until that flash, the ground relay had nothing to see: a series arc in one phase carries load current, not ground current. The sections below give the mechanism, the ground-fault numbers behind the trip, and the checks that order this failure on your own machine.
The megohmmeter reading dates nothing #
After the trip, the reported checks found B phase open-circuited, A and C phase resistances balanced, insulation resistance above 1,000 megohms and a polarization index above 2, and the repair shop repeated every one of those results. Those numbers describe only the paths the test can still reach once the damage is finished. A series arc erases its own conductive route as it burns the conductor open, so a completed conductor failure can leave the insulation system testing like new, and an open lead can leave part of the winding unreachable from the line side, which hides damage as well as explains a clean reading.
A clean megger reading next to an open phase is therefore the signature of a finished series failure, not evidence about what came before it. Neither the insulation value nor the polarization index carries a date. The same puzzle shows up on drive-fed machines, and the drive-side version of it — a ground trip with insulation tests that pass — is covered in why a VFD can trip on ground fault while insulation tests pass.
How a T-lead burns open before any ground current flows #
A conductor-first failure starts with damaged strands, not failed insulation. The initiation can be vibration fatigue where ties and clamps restrain lead movement, handling damage during the 2005 rewind this machine went through, or a defect hidden inside the strand bundle. A damaged strand rarely separates cleanly: the broken ends sit close together, touch and part as the machine vibrates and the bars shift under load, and every make-break strikes a small series arc.
Each arc cycle does two things at once. It shifts current into the surviving strands, raising their current density and their local heating, and it concentrates arc energy on a pinpoint of copper at the arc roots — energy equal to arc voltage times current integrated over time, delivered at two attachment points instead of spread through the conductor. That is why inches of copper can disappear while the winding's bulk temperature never moves. Strands fail one after another until the bundle opens and the insulation around it burns through. Only then does the arc reach the nearest grounded steel, and only from that moment does any ground current exist for the ground relay to measure.
An insulation-first fault looks different. It flashes at a weak spot, the sensitive ground element trips within its operating time, and the burn is small. Copper erosion at a location with no joint, splice or insulation transition does not fit that picture, and phase-to-phase and turn faults were ruled out here by the balanced phase resistances and the absence of any other damage.
Working the numbers: a 13.2 kV motor grounded through 20 ohms #
This machine was grounded through a neutral resistor, which is what let a ground arc persist long enough to do this much damage, and what sets the current the ground element finally tripped on. The example uses the reported inputs; substitute your own machine's data before reusing the arithmetic.
- System voltage: 13.2 kV three-phase, phase-to-phase (machine nameplate data, as reported)
- Neutral grounding resistance: about 20 ohms (the plant's neutral grounding calculation, as reported)
- Ground protection: a 51G time-overcurrent element, 1 A pickup, time dial 2, fed from a 50:5 core-balance CT (relay settings, as reported)
Rule: in a resistance-grounded system the available ground-fault current is approximately the phase-to-ground voltage divided by the grounding resistance, because the resistor dominates the fault loop, and a relay's primary pickup is its secondary pickup times the CT ratio.
- Phase-to-ground voltage: 13,200 V ÷ 1.732 (the square root of 3) = 7,621 V
- Resistor-limited ground-fault current: 7,621 V ÷ 20 ohms = 381 A
- Ground element primary pickup: 1 A × (50 ÷ 5) = 10 A
Result: the worst-case ground current on this system is about 381 A. Treat that as a calculated estimate, not a measured event current: it assumes the full phase-to-ground voltage stands across the resistor and neglects arc and system impedance, so the actual current was if anything lower. Check the figures against the grounding resistor's nameplate and your one-line diagram; the same pickup math is what you apply when matching a zero-sequence CT to a large motor.
Decision: once the erosion finally flashed to the stator steel, the trip was certain — 381 A against a 10 A pickup leaves a margin of roughly 38 times, so no tuning was needed for the relay to notice. But during the erosion phase the ground element contributed nothing, because a series conductor break produces no ground current at any pickup. Sensitivity buys early tripping against insulation-first faults; against a conductor-first fault it buys nothing. On a machine grounded like this one, expect a ground-relay trip to mark the end of the copper loss, not its start.
Why the other five functions stayed silent #
| Function | Setting as reported | Primary pickup or basis |
|---|---|---|
| 51G ground time overcurrent | 1 A pickup, time dial 2, on a 50:5 core-balance CT | 10 A |
| 51 phase time overcurrent | 5 A pickup, time dial 2, on 200:5 CTs | 200 A |
| High-dropout instantaneous | 30 A secondary held for 0.1 s | 1,200 A |
| 50 phase instantaneous | 50 A secondary, no intentional delay | 2,000 A |
| 51BX B-phase alarm | 4.3 A pickup, time dial 1.5 | 172 A, alarm only |
| 46 current balance | 1.1 A pickup, 5% slope | magnitude imbalance only |
The table values are computed from the reported CT ratios; they are settings as reported, not verified calibration. While the break was arcing, the phase relays saw ordinary load current, because the arc sat in series with the phase. Once the flash to ground arrived, a resistor-limited fault of a few hundred amperes sits far below the high-dropout and instantaneous levels and gives the phase time-overcurrent elements only a modest multiple, while the ground element — tens of times above its own pickup — operates first and wins the race. The current-balance element compares phase magnitudes, which stayed nearly equal while the gap kept re-making contact, and the B-phase element is an alarm looking at the same near-equal magnitudes.
Only the ground element flagging is therefore consistent with the conductor-first order, not evidence that anything failed to operate. That is the general limit of current-only protection: it measures what flows in the conductors, and a series defect hides inside normal-looking current. Which functions a current signal can and cannot expose is laid out in what current-only motor protection can and cannot detect. After any event like this, verify the ground element by secondary injection against the manufacturer's curve; a flag proves operation, not calibration.
What the damage geometry tells you #
The shop findings, as reported: the open sat in the line-side B-phase T-lead a few feet inside the machine, in the endwinding area of this weather-protected outdoor unit, at a spot with no joint, splice or insulation transition; the lead was 2 AWG silicone-rubber-insulated; the missing conductor measured about 1.5 inches; an arc mark sat on the grounded stator surface about 4 inches away; and silicone insulation powder coated the adjacent lead and the bracket above, with that adjacent lead proving undamaged once cleaned. Each finding sorts into place under the conductor-first order: erosion at a joint-free location points to strand damage rather than a failed connection, and the mark on grounded steel shows where the arc finally found earth after the copper was already gone.
The temperature record neither proves nor refutes the order, because none of it measured the failure site. Space heaters held the winding 10 to 15 °C above ambient while the machine sat idle that winter, which argues against condensation as the initiator. The hottest of six slot RTDs had stayed under 200 °F at full load since the 2005 rewind, and the lead insulation is rated 150 °C by its manufacturer — three numbers that describe locations away from the endwinding spot where a strand defect concentrates heating. A mechanical tie sat within a few inches of the break; that makes it an inspection target on the next machine, not proof of fatigue at this one.
Water trails that radiated outward along a blade — centrifugal force, not gravity — show the motor was spinning when water got in, and bugs were present inside the enclosure. Both are containment defects that deserve fixes on their own. They do not order this failure: an insulation-first flash on a resistance-grounded system trips the sensitive ground element early and leaves little copper behind, which is the opposite of what the shop found. The verdict the geometry supports is conductor first, insulation failure last, flash to ground as the final act.
After the trip: the checks in order #
Open the circuit first: de-energize, lock out and verify absence of voltage before anyone opens a terminal box or works in an endwinding area. NFPA 70E, Standard for Electrical Safety in the Workplace, 2024 edition, covers the shock protection, arc-flash boundaries and voltage-verification steps that apply to this work; requirements differ by jurisdiction and edition, so confirm them with your authority having jurisdiction and the equipment documentation.
Then work in this order:
- Continuity before insulation. Measure dc resistance between each pair of phases at the line-side terminals. An open pair with clean insulation readings is a series conductor failure — go inspect the lead route before condemning the winding.
- Insulation, phase by phase. Interpret a high reading knowing an arc can erase its own conductive path, and test the winding in reachable sections rather than trusting one number for the whole machine.
- Lead route inspection. Examine restraints, ties, clamps and any splice or transition for strand-level discoloration, powder or displaced strands.
- Relay verification. Confirm the ground element's pickup and operating time by secondary injection against the manufacturer's curve.
- Upstream check. If insulation tests still show a ground path after the motor leads are disconnected, the fault is upstream of the machine; the voltage-reading method used for tracing it on a resistance-grounded bus is covered in locating a ground fault on a resistance-grounded 480 V system.
- Feed the findings back. The outputs worth acting on: lead support and handling practice at the rewind shop, vibration at the lead bundle, and enclosure sealing against weather and insects.
Questions asked
If the conductor was arcing open, why did the motor keep running?
A broken strand bundle rarely opens all at once. The gap touches and parts with vibration, passing near-normal current on every contact, so the machine keeps turning and the phase relays keep seeing load current. Single-phasing appears only when the gap finally stays open, and in the reported event the ground flash and the 51G trip arrived first.
Would a more sensitive current-balance setting catch the next one?
Probably not. A 46 element compares phase-current magnitudes, and a re-making gap passes close to normal load current, so even a tight slope sees almost no imbalance until the break stays open, by which time the ground element has already tripped. The practical detection happens during outages, with per-phase dc resistance readings tracked over time against a baseline.
Does the same conductor-first failure happen on 480 V motors?
The strand-arcing mechanism is the same at any voltage, but the slow-erosion window is widest on resistance-grounded medium-voltage machines, where the grounding resistor holds ground current to tens or hundreds of amperes and an arc to ground can persist. On a solidly grounded 480 V circuit the first ground flash draws far higher current and the branch protection clears it quickly, so erosion usually stops much earlier.
Can a motor lead fail at a spot that is not a joint?
Yes. Some cable manufacturers butt-weld conductor ends together mid-length, smooth the weld to full diameter and insulate over it as normal practice, so a continuous-looking lead can still contain a welded splice that is both a mechanical and a voltage stress point. The lead in the reported failure had no connection at the break, but on any replacement lead it is worth asking the supplier whether embedded welds exist.
What would an insulation-first failure have looked like instead?
An insulation breakdown on a machine grounded like this one would flash at the weak spot and trip the sensitive ground element within its operating time at roughly 38 times pickup, leaving a small burn at one insulation surface and little or no missing copper. Erosion measured in inches at a location with no joint points instead to a conductor defect that came first.
Did moisture or contamination inside the enclosure start the failure?
In the reported case the enclosure admitted bugs and water, and both deserve fixes on their own. They do not order the failure: space heaters held the winding about 10 to 15 degrees Celsius above ambient while the machine sat idle, and an insulation-first flash would have tripped the sensitive ground element long before inches of copper could erode.