Troubleshooting
Why two motors behind one overload relay trip or burn
Short answer
Set one overload relay per motor winding, sized from that winding's own nameplate full-load current. A shared relay set to the combined current lets a single winding run near twice its rating before tripping, and a shared relay set to one winding's rating trips on normal running current. NFPA 70 Article 430, Part III requires individual motor overload protection.
On this page
Two motors on one overload relay cannot both be protected, and the relay can be set wrong in two directions at once. Set it to the sum of the two nameplate currents and a single overloaded winding can run near twice its rated current before the relay asks for a trip; set it to one motor's rating and the normal combined current is twice the setting, so it trips on every run. NFPA 70, the National Electrical Code, 2023 edition, requires overload protection for each motor, sized from that motor's nameplate current. On a two-speed crane pair that means one overload per winding — four devices for the two motors — confirmed with your authority having jurisdiction for the edition in force where you work.
Why one relay fails in both directions #
A thermal or electronic overload responds to the current through it. With two motor windings behind one relay, that current is the sum, and the relay has no way to tell whether it is two healthy windings sharing the load or one winding in trouble while the other runs light. That ambiguity produces exactly the two symptoms you see:
- Set to the combined full-load current, the relay is blind to a single overloaded winding. One stalled or mechanically binding motor can draw roughly the whole combined setting on its own while the other draws little, so the combined reading sits in the relay's normal band. The winding overheats while the relay waits; that is how motors burn with no overload trip.
- Set to one motor's nameplate current, the relay sees twice its setting the moment both motors run normally, and it trips in ordinary operation — the nuisance trips on the crane.
Raising the setting to stop the trips removes the only protection either winding had. It treats the symptom and leaves both motors unprotected.
What the NEC requires #
Part III of Article 430 covers motor overload protection. Section 430.32 requires overload protection for each continuous-duty motor, and 430.6(A) fixes the basis: the motor's nameplate full-load current rating, not a calculated or assumed value. Two-speed motors make this a per-winding requirement: each speed winding is separately energized through its own contactor, so each winding needs overload protection sized from that winding's nameplate current.
Section 430.53 does allow several motors on a single branch-circuit short-circuit and ground-fault device, but only under its listed conditions, and even there every motor keeps its own overload per 430.32. A listed group-installation arrangement consolidates the short-circuit protection, never the thermal protection. There is no configuration in the code that lets one overload relay stand in for two motors.
The mechanics of applying nameplate current to the relay dial are the same as for any single motor, and our article on setting overload relays from motor nameplate full-load current walks through that procedure.
Worked example: the shared relay on two identical windings #
Take the crane's low-speed circuit as a hypothetical worked example: two identical three-phase windings on one reversing contactor, each with a nameplate full-load current of 2.4 A at 460 V.
Combined nameplate current: 2 × 2.4 A = 4.8 A.
- Shared relay set to the combined 4.8 A: in normal running the combined current equals 100% of the setting, so the relay never acts — correct only while both windings stay healthy. If one winding binds or stalls, it can draw up to 4.8 A on its own, twice its rating, before the total even reaches the trip point, and that winding's insulation cooks while the relay waits.
- Shared relay set to the single-winding 2.4 A: normal running delivers 4.8 A, 200% of the setting. That is deep inside the trip region of every standard overload curve, so the relay acts during ordinary running, not during a fault.
No setting between those two points protects either winding. The decision: fit one overload per winding — two set from the 2.4 A low-speed nameplate and two from the 3.7 A high-speed nameplate — and keep the shared contactor only as the switching means, with each overload in its own winding circuit.
Finding the real cause of the nuisance trips #
Once each winding has its own overload, a trip is real information. Work through it:
- De-energize the crane, lock out, and test for absence of voltage before you open any panel or motor terminal box; NFPA 70E, 2024 edition, governs the safe work practice, and your site procedure governs the sequence.
- Before any reset, record which relay tripped, which speed and direction was in use, the load condition, and whether the trip followed a start, a reversal, or a plugging stop.
- With the circuit restored under controlled conditions, measure each motor's current separately at each speed. A clamp reading on the shared feeder cannot show an imbalance between the two motors.
- Inspect contactors, overload wiring, motor leads and terminations for looseness and heat discoloration while the equipment is still isolated.
- Compare the measured current with each nameplate and with the relay settings now installed; a relay tripping below its documented trip current points to a wiring or setting error, not duty.
- If the currents match the nameplates and the trips continue, the trips are telling you the duty exceeds what the motors and starter were built for — see the next section.
Plugging duty and trip class #
The crane stops by plugging: the supply is reversed while the motor is still turning, so the windings absorb start-level current plus the reversal current, run after run. Both the winding and the overload element accumulate that heat, and a correctly set relay will trip when the cycle repeats faster than the motor's duty rating allows. The fix is the duty cycle or the stopping method, never a wider setting band. How trip class and the relay curve interact with repeated starts is covered in our article on overload relay trip classes and curves, and trips that only show up on start or reversal are worked through in our troubleshooting piece on intermittent instantaneous motor start trips.
If the trip follows the plugging stop rather than the run, check the reversing contactors' ability to break and make under speed, the mechanical brake release timing, and the motor manufacturer's stated plugging capability. A motor not rated for repeated plugging will overheat even with perfect overload protection, because an overload relay responds to current, not winding temperature.
The decision #
- One shared overload relay set to the combined current: rejected. It lets either winding run to roughly twice its rating before any trip.
- One shared relay set to one motor's rating: rejected. It trips on normal running and gets defeated in practice.
- Four individual overloads on the two-speed pair, each sized from its own winding's nameplate full-load current per NEC 430.32 and 430.6(A): the compliant arrangement.
- Trips that persist after the change are real overload events: trace the plugging duty, the brake, and the mechanical load, and correct the duty rather than the setting.
Questions asked
Can I size one relay at the combined current if the motors only run intermittently?
No. Reduced duty does not relax the protection requirement: each motor still needs an overload sized from its own nameplate current per Article 430. A shared relay set to the combined current lets one winding run to about twice its rating before the total reaches the trip point, and a shared relay set to one motor's rating carries twice its setting in normal running. Duty only changes how fast the damage accumulates.
What group protection is allowed under NEC 430.53?
Section 430.53 lets several motors share one branch-circuit short-circuit and ground-fault device when you follow its conditions, typically a listed combination controller rated for group installation, with the conductors and disconnect sized per its rules. The sharing stops at short-circuit protection: every motor keeps its own overload per 430.32, sized from its nameplate full-load current. Sharing the contactor and a single overload, as the crane's factory wiring does, is not one of those conditions.
What trip class should the crane overloads use?
Trip class is the relay's maximum trip time in seconds at a standard multiple of setting, for example Class 10 trips within 10 seconds at seven times setting. For plugging and frequent-reversal crane duty, pick the class from the relay manufacturer's curve against the motor's stated thermal capability, not from habit. A correctly sized relay that trips on repeated plugging is reporting real accumulated heating; widen the duty interval or change the stopping method instead.
Where should each overload's trip contact land?
Wire each relay's trip contact into the control circuit that feeds its own winding's contactor coil, so a trip drops only the affected motor and speed, and parallel another contact into the control-system input so the fault is reported. On a two-speed motor, both speed overloads must be able to break the drive command for whichever speed is selected, and the reversing circuit must not be able to re-energize a tripped winding until the relay is reset.