Current IntelPower LibraryShop main store

Explainer

Why mixed bases give the wrong generator fault current

Protection: breakers, fuses and SCCR Published 6 min read By Current Intel engineering team

Short answer

Pair each MVA base with a voltage measured the same way: 2.5 MVA per phase with 4.16 kV line-to-neutral, or 7.5 MVA three-phase with 7.205 kV line-to-line. Both give about 3.005 kA of initial symmetrical current for a 7.5 MVA generator with 0.20 pu subtransient reactance into a bolted three-phase fault at the terminals. Mixing 7.5 MVA with 4.16 kV line-to-neutral triples the result to 9.014 kA.

On this page
  1. One base system at a time
  2. Worked example: per-phase bases
  3. The same fault with three-phase bases
  4. Where 9.014 kA comes from
  5. Read the voltage definition first
  6. Reconciling a software result
  7. The decision
  8. Questions asked

A 7.5 MVA generator whose terminal voltage is stated as 4.16 kV line-to-neutral and whose subtransient reactance Xd″ is 0.20 pu delivers about 3.005 kA of initial symmetrical current into a bolted three-phase fault at its terminals. A hand calculation that returns 9.014 kA has not found a different machine: it has paired a power base that counts all three phases with a voltage base that counts one. Pair 2.5 MVA with the line-to-neutral value, or 7.5 MVA with 7.205 kV line-to-line, and both routes land on the same current. This article works both pairings, shows where 9.014 kA comes from, and gives the checks that catch the error in your own numbers and in a short-circuit tool's output.

One base system at a time #

A reactance quoted in pu only converts to ohms through a base impedance, and the base impedance is built from a paired choice of power and voltage:

Zbase (ohms) = (Vbase)² / Sbase

Written in kV and MVA the expression is kV²/MVA, and it looks identical for single-phase and three-phase quantities because the factor of three cancels: one phase's voltage squared over one phase's power equals line-to-line voltage squared over total three-phase power. That cancellation is exactly why the pairing is easy to miss. Base impedance has the same kV²/MVA shape either way, but base current does not: single-phase uses Sφ/Vφ, three-phase uses S3φ/(√3 × VLL). So the working rule is short: single-phase kVA goes with line-to-neutral voltage, three-phase kVA goes with line-to-line voltage, and nothing mixes.

The same discipline keeps transformer hand calculations straight — the walkthrough on calculating transformer secondary fault current in per-unit applies it on the secondary side of a transformer bank.

Worked example: per-phase bases #

Assume a bolted three-phase fault on the generator terminal bus, prefault terminal voltage at 1.00 pu, and only the subtransient reactance in the fault path. The result is the initial symmetrical RMS current, the first-cycle value.

  1. Split the rating per phase: Sφ = 7.5 MVA / 3 = 2.5 MVA.
  2. Take the voltage as stated: Vφ = the line-to-neutral value, 4.16 kV.
  3. Base impedance: Zbase = Vφ²/Sφ = 17.3056 / 2.5 = 6.9222 Ω.
  4. Reactance in ohms: Xd″ = 0.20 × 6.9222 Ω = 1.3844 Ω.
  5. Terminal fault current: I″ = Vφ/Xd″ = 4.16 kV / 1.3844 Ω = 3.005 kA.

Carry the intermediates unrounded: the exact chain 6.92224 Ω and 1.384448 Ω gives 3.0048 kA before the final rounding.

The same fault with three-phase bases #

Keeping the nameplate rating intact works too, as long as the voltage converts with it:

  1. Line-to-line base voltage: VLL = √3 × the line-to-neutral base = 7.205 kV — the line-to-neutral to line-to-line conversion shown step by step in calculating line-to-line voltage from line-to-neutral data.
  2. Base impedance: Zbase = VLL²/S3φ = 7.205² / 7.5 = 51.912 / 7.5 = 6.9216 Ω, which rounds to the same 6.922 Ω the per-phase route produced.
  3. Base current: Ibase = S3φ/(√3 × VLL) = 7500 kVA / (1.732 × 7.205 kV) = 7500 / 12.479 = 601 A. The page on calculating per-unit current with three-phase bases works through this same expression.
  4. Fault current: I″ = Ibase/Xd″ = 601 A / 0.20 = 3005 A — the terminal current the per-phase route found.

Two correct pairings, one answer. The base choice is bookkeeping; the machine has one fault current.

Where 9.014 kA comes from #

The wrong figure is the mixed pairing run to completion:

  • Base impedance from total MVA and phase voltage: Zbase = Vφ² / 7.5 MVA = 17.3056 / 7.5 = 2.3074 Ω.
  • Reactance in ohms: Xd″ = 0.20 × 2.3074 Ω = 0.4615 Ω.
  • Current: I = Vφ/Xd″ = the line-to-neutral base voltage / 0.4615 Ω = 9.014 kA.

The power base is three times the per-phase value, so the impedance base lands one third of what it should be, the ohms one third, and the current three times the hand value. Nothing about the machine changed between the calculations — only the bookkeeping.

Base pairing Power base Voltage base Base impedance Terminal fault current
Per phase, correct 2.5 MVA 4.16 kV line-to-neutral 6.922 Ω 3.005 kA
Three-phase, correct 7.5 MVA 7.205 kV line-to-line 6.922 Ω 3.005 kA
Mixed, wrong 7.5 MVA the line-to-neutral value as stated 2.307 Ω 9.014 kA

Read the voltage definition first #

The stated terminal voltage is also a common line-to-line class voltage, and many software voltage fields are labeled for line-to-line entry. If the machine data genuinely means that number line-to-line, then 2.307 Ω is not a mistake at all — it is the correct three-phase base — and the current becomes I″ = 7500 kVA / (√3 × the line-to-line reading × 0.20) = 7500 / 1.44107 = about 5.204 kA. Same ohms, different voltage definition, lower current. So the first diagnostic question is never which formula but what the voltage field actually holds: read the generator nameplate or datasheet, read the software field label, and enter the value the way that field defines it.

Reconciling a software result #

A short-circuit run of this exact case — synchronous machine model, 7500 kVA, Xd″ = 0.20 pu, fault placed on the terminal bus — returns 3.0047 kA, matching the hand value to the fourth digit. Any tool fed those inputs should land there.

Results that differ usually trace to the input screens, not to the base equations:

  • About 4 percent high, for example 3.124 kA: 3.124 against the hand value is a ratio of 1.0397, which is what a prefault driving voltage near 1.04 pu instead of 1.00 produces. Check the operating or prefault voltage setting first.
  • A generator marked as the swing or slack bus is only the network reference for load flow; the short-circuit solution still uses the machine's subtransient impedance, so the designation does not remove it from the fault path.
  • 20 entered where 0.20 belongs, a voltage field read line-to-neutral when it holds line-to-line, or cable and transformer impedance left between machine and fault bus — each moves the answer on its own.

Compare like with like: symmetrical RMS against symmetrical RMS, never against a peak or asymmetrical duty value. And keep the verification on paper and in the tool's input screens — confirming a short-circuit number never means re-energizing equipment to produce one.

The decision #

For the machine as stated — 7.5 MVA, the terminal voltage genuinely line-to-neutral at the value on the nameplate, Xd″ = 0.20 pu, bolted three-phase fault at the terminals, 1.00 pu prefault voltage — the initial symmetrical terminal fault current is 3.005 kA. Use it. A 9.014 kA result on the same data is a mixed-base bookkeeping error: fix the pairing, not the tool. A 5.204 kA result means the voltage was read as line-to-line: make the model match the machine datasheet, then keep whichever definition is true. A result about 4 percent above the hand value points to a prefault voltage slightly above 1.00 pu; confirm the setting.

Treat the hand figure as a first-cycle estimate for comparing fault duty and protective-device ratings. Converting it into breaker contact duty or relay settings follows IEEE Std C37.010-2016 or IEC 60909-0:2016, each of which applies its own prefault-voltage factor and decay treatment to the subtransient value. Take the rating, the reactance and the voltage definition from the generator documentation, and confirm duty requirements with the governing standard, the local authority having jurisdiction and the equipment documentation.

Questions asked

The datasheet gives subtransient reactance as 20 percent. What value goes into the calculation?

Divide by 100 first: 20 percent is 0.20 pu. Entering 20 where a pu value belongs makes the machine look a hundred times more reactive and understates the fault current by a factor of 100. It runs the other way too: a reactance written 0.20 pu is 20 percent, and a field that expects percent needs 20, not 0.20.

Does the terminal fault figure also apply to a fault downline of the generator, past a cable or transformer?

No. The 3.005 kA value assumes a bolted three-phase fault at the terminals with only the subtransient reactance in the path. For a fault downline, convert the cable or transformer impedance to ohms on the same base pair, add it to the machine's 1.384 ohms, and divide the phase voltage by the total. Every added ohm pulls the current below that terminal value.

Why does generator fault current fall after the first cycle while a utility contribution holds steady?

A utility source behaves as a fixed voltage behind a fixed impedance, so its contribution barely moves. A generator's internal flux collapses once the fault draws heavy current, and the contribution slides from the subtransient value set by Xd″, through a transient value set by Xd′, toward a much smaller steady value set by the synchronous reactance. Breaker-duty standards apply their own multiplying treatment to that decay; the hand figure in this article covers only the first cycle.

Keep reading

  • How-to

    Closed delta transformer fault current calculation

    Compute each delta branch from its own kVA and impedance, then take phasor differences at the line terminals: for a 150 kVA leg with two 100 kVA legs at 240 V and 3.3% Z each, the bolted three-phase terminal fault is highest at each end of the 150 kVA winding and lower at the junction of the two 100 kVA windings. Size secondary equipment on the higher terminal value.

    Protection: breakers, fuses and SCCR

  • How-to

    Calculating low-side fault current with source impedance

    For a 20 MVA, 8.2%, 161:13 kV transformer with an assumed 2500 MVA utility source, the source adds 0.008 pu to the transformer's 0.082 pu, and dividing the 888 A low-side base current by the 0.090 pu total gives about 9.87 kA. If the nameplate secondary is actually 13.8 kV, the answer is about 9.3 kA.

    Protection: breakers, fuses and SCCR

  • How-to

    How to calculate transformer secondary fault current in per-unit

    Yes — use one MVA base for the whole study, and the transformer rating is the convenient one: with 16.091 kA available at 230 kV and a 24 MVA, 8.8%Z, 230/13.2 kV transformer, the source impedance is 0.003744 pu, the total is 0.091744 pu, and the secondary fault current is about 11.44 kA at 13.2 kV. The infinite-bus figure, 11.93 kA, is the ceiling to rate against when the primary source is ignored or unknown.

    Protection: breakers, fuses and SCCR