Transformer taps scale the three line-to-line pairs by different ratios, so a rotary phase converter reading 3.77% unbalance at its terminals can deliver 5.15% at a 380 V secondary. Measure both sides with the same formula under the same load condition, tune the converter at its own terminals, and use the taps to set the average voltage only.

On this page
  1. Why the percentage moves across the transformer
  2. The one number to compute, and what it must not include
  3. What the plus and minus 5 percent taps can and cannot fix
  4. Measure both sides under the same condition
  5. From 239/246/248 V at the converter to 388/408/392 V at the secondary
  6. The decision, case by case
  7. Questions asked

Tune the converter where the converter is, and judge the supply where the machine is. The multi-tap step-up transformer between a rotary phase converter and its 380 V load does not scale the three line-to-line voltages by one common ratio. Each pair rises by the ratio of the windings it crosses, and an unequal set of inputs comes out reshaped, not merely magnified. In one recorded installation, a converter output sitting under four percent apart fed the machine more than five percent apart, past the balance its control was specified to tolerate. Measure both sides with one formula under one load condition, tune the converter at its own terminals, and use the taps to place the average voltage only.

Why the percentage moves across the transformer #

A rotary converter's output is two utility legs and one manufactured leg. The manufactured leg differs from the other two in both magnitude and phase angle, and the converter's own terminal-to-ground readings show the asymmetry, so the three line-to-line pairs arrive at the transformer unequal in size and spacing.

The transformer does not correct that. It transforms each winding by its turns ratio, and a tap moves that ratio in steps. How the pairs combine depends on the winding connection: in a wye winding, each line-to-line pair combines two phase windings, so one tap change shifts two pairs at once and leaves the third nearly alone; in a delta winding, each pair sits across its own winding. Either way the three pairs travel different paths, and unequal inputs leave as a differently shaped set. Because the percentage divides the spread by the lowest reading, reshaping the set moves the percentage even when every pair went up.

Two things follow. First, the effective step-up ratio is not one number — the worked example below shows the three pairs rising on three distinct ratios — so a tap setting that flatters one pair can widen the whole set. Second, taps change magnitude only. The converter's phase-angle error is not a magnitude, so no tap reaches it, and magnitude-only readings never show it directly, which is how a supply reads well balanced in volts and still misbehaves. The same winding ratios that reshape the voltage pairs reshape the leg currents, so leg amps on a phase converter step-up transformer read wrong pair by pair rather than by three-phase math.

The one number to compute, and what it must not include #

Compute one spread from the three line-to-line readings taken at one point under one load condition:

percent spread = (highest reading - lowest reading) / lowest reading × 100

Use line-to-line pairs only. On the converter side, the manufactured leg reads far higher to ground than the two utility legs; that is normal for a rotary converter, it is not a ground fault, and it contributes nothing to a balance number. On the transformer side, readings taken to the secondary common are a separate set on a different reference, so they go in their own column and never fold into the line-to-line spread. Terminal-level diagnosis works the same way: diagnosing a delta-connected transformer starts from its three line-to-line voltages, never from ground-referenced readings.

Watch the definition before you compare numbers. NEMA MG-1, the motors and generators standard, defines percent voltage unbalance as the largest departure from the average voltage divided by that average, which reads lower than the spread method on the same three readings; European practice additionally tracks a negative-sequence unbalance factor that sees the phase-angle side a magnitude spread never shows, and EPRI's voltage unbalance work lays out the comparison. Compute both sides one way, and hold the result only against a limit written for that same definition — the machine's documentation says which one it means. The spread itself is plain arithmetic on your own readings; the limit it must meet is the part that needs documentation behind it.

What the plus and minus 5 percent taps can and cannot fix #

Opening the transformer enclosure to move a tap lead is de-energized work: shut the converter down, lock out, and verify absence of voltage at every terminal before a lead moves. Measuring at live terminals is energized work — meter category, PPE and approach boundaries come from NFPA 70E, the electrical safe-work-practices standard, 2024 edition, and your authority having jurisdiction and the equipment documentation set the details for your site.

A tap is a turns-ratio step, and on a 380 V winding the plus and minus 5 percent positions move the output about 19 V per step: 380 × 0.05 = 19. That is the tool's entire reach, and its honest job is the average voltage. One reported secondary sat between 389 and 405 V against its nameplate target, and the documented taps are the right instrument for pulling that band onto target. They are the wrong instrument for balance. Taps rescale magnitudes, the converter's angle error passes the iron essentially unchanged, and once the average is on target, a secondary spread that still sits past the machine's limit is converter-side work — idler tuning, judged at the converter terminals where the effect you change is the effect you measure — not more tap hunting.

Measure both sides under the same condition #

Record both sides in one session, in this order:

  1. Converter running, machine disconnected: record all three converter line-to-line pairs.
  2. Transformer energized, machine still disconnected: record the three secondary pairs and write down the tap combination in place.
  3. Machine connected: record all three pairs at idle, during spindle acceleration, at speed, and during braking.

The two spreads only compare when both sides were read under the same condition, and the loaded sets decide acceptance, because every pair sits lower once the machine draws current — calculating voltage drop through step-up and step-down transformers puts a number on how far down to expect. Keep the tap combination attached to every set of readings: a measurement without its tap position cannot be reproduced, which is exactly how a working supply gets re-tuned into a fault one adjustment at a time.

From 239/246/248 V at the converter to 388/408/392 V at the secondary #

Inputs, from one recorded commissioning on a 15 hp rotary converter feeding a multi-tap step-up transformer set for 380 V, machine disconnected:

  • Converter output, line to line: 239 V, 246 V, 248 V
  • Transformer secondary, line to line: 388 V, 408 V, 392 V
  • Machine balance limit: 5 percent, the figure its documentation gave the installer
Measurement point Line-to-line readings Spread, (max - min) / min × 100 Rise per pair
Converter output 239 V, 246 V, 248 V 3.77% n/a
Transformer secondary 388 V, 408 V, 392 V 5.15% 1.62, 1.66, 1.58

Rule: percent spread = (highest reading - lowest reading) / lowest reading × 100, on the three line-to-line pairs at one point under one load condition.

Converter side: (248 - 239) / 239 × 100 = 9 / 239 × 100 = 3.77 percent.

Secondary side: (408 - 388) / 388 × 100 = 20 / 388 × 100 = 5.15 percent.

Rise per pair: 388 / 239 = 1.62, 408 / 246 = 1.66, 392 / 248 = 1.58.

Result: the transformer lifted the three pairs on three different ratios, so the spread grew 1.4 percentage points across it with nothing at the converter changed, and the pattern reshaped with it — the highest converter-side pair was the second-to-manufactured pair, the highest secondary pair was the first-to-manufactured pair, and the utility-to-utility pair stayed lowest on both sides.

Decision: the converter-side set passes the machine's 5 percent limit with margin; the machine-side set does not, which makes the secondary spread the acceptance number for this supply. That machine then ran repeated loaded spindle accelerations to top speed with regenerative stops at these readings and logged no drive fault — a recorded pass for that machine and that loading, not a clearance for the next installation. The sequence that follows: bring the converter-side spread down, set the taps for the secondary average, and re-measure all three pairs on both sides after each change.

The decision, case by case #

  • Converter-side spread over the machine's limit: fix it at the converter. Retune at the converter terminals until its own spread sits under the limit with margin, before any tap is touched.
  • Converter side in limits, secondary average off the machine's voltage band: set a documented tap combination for the average, expect all three pairs to move, and re-measure all three.
  • Secondary spread over the machine's limit while the converter side sits well under it: the tap combination is reshaping the output. Try the adjacent documented combination, and if no documented combination holds both the average and the spread, verify the winding and tap wiring against the transformer's own diagram before tuning anything further.
  • Machine faults with both sides inside limits: the fault is in the machine, not the supply. A CNC machine that trips instantly on a phase converter supply is worked from the machine's drive side, with the supply record in hand as the proof that the supply is not the suspect.

An acceptance record for a supply like this carries the tap combination, the three line-to-line pairs for each state, the load state for each set, and any drive error codes — enough for the next person to reproduce the reading instead of re-deriving it.

Questions asked

Do standards compute the unbalance percentage differently from the spread method?

Usually lower. NEMA MG-1 computes percent voltage unbalance as the largest departure from the average voltage divided by that average: the worked example's converter-side readings give about 2.2 percent that way against 3.77 percent by the spread method, and the secondary readings give about 3.0 percent against 5.15 percent. Neither number is wrong; a limit written for one definition is only valid against numbers computed the same way.

Do idle voltage readings predict how the supply behaves under load?

Only roughly. Every pair sits lower once the machine draws current, and one reported 460 V installation saw all three pairs drop about 20 volts with the spindle running. Record the three line-to-line pairs at idle, during spindle acceleration, at speed, and during braking, and use the loaded sets, not the idle sets, for the acceptance decision.

Is the generated leg's high voltage to ground a fault?

No. A rotary converter manufactures its third leg, so its voltage to ground is expected to differ from the two utility legs, 217 volts against 119.5 volts on the recorded installation. That asymmetry is normal, is not a ground fault, and contributes nothing to a balance number, which comes only from the three line-to-line pairs. Check a ground reading further only if it appears on a utility leg or shifts after the install has been working.

Which do I adjust first, the converter or the transformer taps?

The converter. Retune the idler and its capacitor banks until the spread at the converter terminals is as low as the design holds, then set a documented tap combination to bring the secondary average onto the machine's voltage band, then re-measure all three pairs on both sides. Taps only rescale magnitudes; if the secondary spread stays past the machine's limit while the converter side sits well under it, no tap setting will repair the balance.

Keep reading

  • Troubleshooting

    Why a static phase converter stops after a few minutes

    When a static phase converter starts a motor cleanly and the machine stops after about ten minutes, the opened device is downstream of the converter: thermal fuses in the accessory-transformer circuit or a thermal overload reacting to manufactured-leg imbalance. The potential relay only switches the start-capacitor branch and cannot open the motor path; label the manufactured leg, measure loaded line-to-line voltages and per-leg currents, and feed the accessory transformer from a branch that tolerates the imbalance.

    Motors and motor starters

  • Troubleshooting

    Why phase loss monitors miss single-phasing on an open delta

    A spinning three-phase motor acts as an induction generator and holds near-normal voltage on a lost phase, so a voltage-sensing phase loss monitor sees a healthy supply while winding current goes badly unbalanced. The fix is current-based phase-loss and unbalance protection in the starter; the voltage relay stays only for line-side conditions like phase reversal and total collapse.

    Motors and motor starters

  • Troubleshooting

    Why transformer inrush blows fuses on a running rotary phase converter

    Closing a transformer onto a running rotary phase converter draws magnetizing inrush that sags the generated phase, re-engages the start capacitors through the potential relay, and opens the phase fuse. Connect the transformer and leave it connected, then start the converter: the idler brings the transformer up with it and the inrush step never happens. Then verify the stepped-up voltage against the machine's band before running the load.

    Motors and motor starters