Troubleshooting
Why phase converter step-up transformer leg amps look wrong
Short answer
Neither reading points to a bad transformer; the 329 V is a floating-reference artifact: the secondary has no ground reference, so the meter reports whatever leakage sets. The 3.0 A to 3.5 A is unloaded exciting current made uneven by the converter's voltage unbalance. Restore identical taps on all three units, re-tag the secondary so (a) is the odd leg, and accept the bank on phase-to-phase volts and loaded amps.
On this page
Neither reading shows a bad transformer. With no motor on the bank, the 329 V from (a) to ground is a floating-reference artifact: the 480 V secondary has no ground reference, so the meter reports whatever leakage and its own input impedance settle on. The 3.0 A to 3.5 A on leg (1) is unloaded exciting current, made uneven by the voltage unbalance already sitting on the converter. The tap experiment is the strongest evidence of all — moving unit #1 one position changed only the lines sitting on that unit, which is how a healthy bank answers a deliberate ratio mismatch. Restore identical taps on all three units, re-tag the secondary so (a) carries the odd-leg tag, and accept the bank on phase-to-phase volts and loaded amps.
The phase-to-phase readings clear the bank #
Judge the bank on phase-to-phase volts, and compute the unbalance instead of eyeballing it. Percent unbalance is 100 × (largest deviation from the average) ÷ average — the same basis used when setting voltage imbalance limits on a phase monitor.
- Converter side: average = (235 + 243 + 235) ÷ 3 = 237.7 V; largest deviation = 243 − 237.7 = 5.3 V; unbalance = 100 × 5.3 ÷ 237.7 = 2.2%.
- Secondary side: average = (475 + 473 + 488) ÷ 3 = 478.7 V; largest deviation = 488 − 478.7 = 9.3 V; unbalance = 100 × 9.3 ÷ 478.7 = 1.9%.
| Side | Readings (V) | Average (V) | Largest deviation (V) | Unbalance |
|---|---|---|---|---|
| Converter output, 1-2 / 1-3 / 2-3 | 235 / 243 / 235 | 237.7 | 5.3 | 2.2% |
| Secondary, a-b / a-c / b-c | 475 / 473 / 488 | 478.7 | 9.3 | 1.9% |
Both sides sit near 2% — sound enough to keep testing. A shorted winding distorts phase-to-phase voltage far past this.
The pairs also map the legs. If both sides use the same connection with no phase shift (delta-delta is the usual arrangement for three single-phase 2:1 units), each primary pair doubles onto its secondary pair. The high primary pair 1-3 doubles to 486 V against the high secondary pair b-c at 488 V; the two 235 V pairs double to 470 V against a-b and a-c at 475 and 473 V. So converter legs 1 and 3 feed b and c, and the generated leg 2 feeds a. The ground-reading pattern confirms the same mapping in the next section. The tag calling (b) the wild leg is wrong: the odd leg on the secondary side is (a). Re-tag before anything is connected for rotation or tied to another source.
Why 329 V to ground is a floating artifact #
An ungrounded delta or an unreferenced wye gives a meter nothing solid to measure to, so it reads the potential that stray capacitance, leakage and its own input impedance agree on — the same trap behind why a blown fuse still reads 280 V to ground. On a floating system that reading can land anywhere, even above the phase-to-phase voltage, and it moves with load and with the meter. It says nothing about copper.
Rule out the grounded patterns first. A grounded wye would read about 277 V (the phase-to-phase voltage ÷ √3) on all three legs; a corner-grounded delta would read 0 V on one leg and full phase-to-phase voltage on the other two. Neither appears. Then check the geometry that did appear: (b) and (c) read 245 and 246 V, which sum to 491 V against the 488 V b-c pair — the reference sits near the midpoint of b and c. From that midpoint, clean geometry puts (a) at 0.866 × 488 ≈ 423 V. The meter's 329 V sits below that because its input impedance draws current through the leakage holding the reference. Prove it in a minute: re-measure with a second meter or a low-impedance range. A floating reading moves; a winding voltage does not.
The 240 V ground readings are real but describe system geometry, not the transformer. The 121 / 200 / 121 V pattern is a high-leg signature: half of 243 V is 121.5 V, and 0.866 × 240 V is about 208 V. Legs 1 and 3 are the hot legs of a center-tapped 120/240 V single-phase feed and leg 2 is the generated leg. That assumes the converter is fed from a 120/240 V service with the center tap grounded — confirm it at the converter's input terminals.
If this secondary is ever meant to be grounded, that is a one-time design decision — the same choice behind grounded or floating control power transformer secondaries in MCCs — not a repair for this reading. NFPA 70, the National Electrical Code, 2023 edition, covers grounding a separately derived system in 250.30; confirm the arrangement with the authority having jurisdiction.
What the leg currents are with no load connected #
These currents were taken with no motor on the bank — they are too small, and too disconnected from the 2:1 ratio, to be load current. The primary readings are exciting current plus its harmonics and any current circulating between units. That current is steeply nonlinear in voltage, so the unbalance computed above lands hardest on one leg, and three separate single-phase units never magnetize identically even on a perfect supply. Uneven no-load amps are the normal state of such a bank.
The secondary readings show no real load in play. A 2:1 step-up reflects 0.8–1.1 A of secondary load as 1.6–2.2 A on the primary, and the primary legs do not follow that pattern — leg 2 sits at 1.5 A. With a genuinely open secondary there is no path for line current at all, so if nothing is connected on the secondary side, expect the clamp near zero; readings around 1 A mean clamp pickup or a small load you have not accounted for. Either way they cannot judge a winding.
Connect the motor and the physics works for you: load current dominates each leg, the exciting-current differences shrink to a small fraction of the reading, and the legs come together. Expect the generated leg to sag under load — the behavior at the center of fixing a machine shutdown on a rotary phase converter third leg.
The tap change points away from a bad unit #
Lowering unit #1 by one tap position produced this:
| Line | Before (A) | After (A) |
|---|---|---|
| 1 | 3.0 | 3.5 |
| 2 | 1.5 | 1.5 |
| 3 | 2.0 | 1.9 |
| a | 1.1 | 0.7 |
| b | 1.0 | 0.3 |
| c | 0.8 | 0.7 |
The large moves all sit on lines 1, a and b — lines that unit #1 touches — while legs 2, 3 and c stayed within one clamp digit. Two ordinary mechanisms explain it:
- The changed unit now has a different turns ratio from its two siblings, and a ratio mismatch inside a closed delta or wye bank drives circulating current that redistributes the line currents at that unit.
- If the tap is on the primary winding, fewer turns raise volts per turn and core flux, and exciting current rises with flux. Check which winding the tap actually changes before crediting this one.
Current that tracks a tap setting is a bank responding to a deliberate mismatch — decide that #1 answered like a healthy unit and put its tap back. A shorted winding does not answer a tap change this way.
The test order that accepts the bank #
De-energize the converter and the secondary, apply lockout, and prove every terminal dead — phase-to-phase and phase-to-ground — with a meter rated for the voltage, before touching any tap or terminal.
- Record each unit's nameplate kVA, primary and secondary voltages, connection diagram and tap table. The diagram settles whether the primaries close in delta or tie to a floating star point — three units wye-connected on the 240 V side with the point left floating behave very differently under unbalanced exciting current than a closed delta, and that changes what the no-load amps should look like.
- Return unit #1 to its original tap, then set all three units to the same tap position. Every tap terminal must match across the bank.
- Trace conductors from converter to transformer to load, and tag the secondary so the leg fed from converter leg 2 carries the odd-leg tag — (a) on these readings.
- Energize unloaded and re-take phase-to-phase volts on both sides. Accept at 2% unbalance or less; above that, balance the converter before loading a motor.
- Connect the motor and repeat under load: phase-to-phase volts plus clamp amps on all six lines. A leg still far off its sisters at load points at the converter's balance, not the bank.
- Compare the three units one at a time only if the loaded test still leaves doubt about one of them.
The decision #
- These readings: no transformer comes out. The 329 V is a floating reference, the leg-current spread is unloaded exciting current, and unit #1 answered its tap change exactly as a healthy unit in a mismatched bank does. Restore identical taps, re-tag (a) as the odd leg, and run the loaded test.
- Loaded acceptance: 480 V phase-to-phase unbalance at 2% or less, and leg amps that come together once load dominates. NEMA MG-1-2021, the standard for motors and generators, sets the motor derating if you run above that.
- If one unit stands out from its two siblings in the individual comparison at identical taps, replace that unit — not the bank.
- If the load needs a grounded secondary system, that grounding is separate design work under the code section named above, not part of this repair.
- Until a deliberate ground reference exists, drop phase-to-ground readings from the diagnosis — they will keep sending you after healthy copper.
Questions asked
How much does unbalanced voltage derate the motor?
NEMA MG-1-2021, the motors and generators standard, derates motor output for unbalanced supply: to about 95% of nameplate at 2% unbalance and 88% at 3%, and operation above 5% unbalance is not recommended. The cost is thermal: negative-sequence voltage drives double-frequency currents in the rotor that heat it far out of proportion to the voltage error, so a motor that idles fine can overheat at load. Hold the bank at the accepted unbalance and the motor keeps essentially full rating; the motor's own documentation governs.
What would a genuinely shorted winding look like?
A shorted turn is a closed low-impedance loop fed by the healthy turns around it, so its current is limited by winding impedance rather than core flux. It pulls that current at every tap position, runs hot enough to smell or discolor varnish, and drags down and distorts the phase-to-phase voltage of the pair it feeds. None of that appears here: the volts held inside the computed unbalance and the current followed the tap, which is the opposite signature.
How do I compare the three units one at a time?
With the bank de-energized and disconnected, connect each unit alone to the same clean 240 V single-phase pair, the service pair and not the generated leg, at the same tap position, secondary open. Energize from outside the enclosure, log each no-load current with a true-RMS clamp, and de-energize between units. The three readings should sit close together; the unit well outside the other two is the one to replace. The open secondary rises near 480 V, so treat those terminals as live the whole time.
Why is the generated leg 200 V to ground instead of 208 V?
The high-leg formula gives 0.866 times 240, about 208 V, only for a stiff, symmetric source. A rotary converter synthesizes its third leg with the idler and its capacitors, so that voltage to the center tap depends on tuning and load, and reading a few percent low unloaded is ordinary. What matters is that legs 1 and 3 match and the phase-to-phase set stays balanced; adjust the converter's balance, not the transformer, if the generated leg sags too far once the motor loads it.