Explainer
Why sequence currents are equal for a ground fault on a delta bus
Short answer
At a single line to ground fault the positive, negative and zero sequence currents are equal, because the three sequence networks connect in series at the fault. Zero sequence never dominates the current; with a high-resistance grounded source neutral it holds most of the impedance, so the neutral resistor sets the fault current. A delta bus fed from that grounded star winding is a grounded system, not an isolated one.

On this page
For a single line to ground fault the sequence currents at the fault point are equal: I1 = I2 = I0, in magnitude and in phase. Zero sequence does not dominate, because the three sequence networks connect in series at the fault and one current flows through all three. What the grounding decides is the size of that current: I1 = V / (Z1 + Z2 + Z0 + 3Zn), with V the phase-to-neutral voltage at the fault and Zn the neutral grounding impedance of the source. The delta bus you described is fed from a star winding with high-impedance neutral grounding, so it is a grounded system, not an isolated one, and the earth-fault current returns through that neutral.
The fault connects the sequence networks in series #
For a bolted fault from phase A to ground, the conditions at the fault point are Va = 0 and Ib = Ic = 0. Feed those into the definitions of symmetrical components and every sequence current comes out the same: I0 = (Ia + Ib + Ic)/3 = Ia/3, and with a as the 120-degree operator, I1 = (Ia + aIb + a²Ic)/3 = Ia/3 and I2 = Ia/3. So I1 = I2 = I0 = Ia/3: the faulted phase carries Ia = 3I0 and the healthy phases carry nothing at the fault itself.
The voltage condition Va = 0 means V0 + V1 + V2 = 0. Each sequence voltage is the prefault driving voltage minus that network's own drop, and the balance holds exactly when the three networks form one series loop carrying one current. Protection texts, relay manuals and every short-circuit study package implement that same series connection, and it is why 'which sequence dominates' has no answer in the currents: there is only one current to share.
Equal currents, unequal impedances #
The three networks share the current but not the impedance. The positive- and negative-sequence networks are small; for a fault on this bus they are the transformer and cable impedances, and the two are close to equal. The zero-sequence network is where the grounding lives, and the neutral impedance enters it multiplied by three. The zero-sequence currents of the three phases are equal and in phase, so they add in the neutral, which carries 3I0; the drop 3I0 × Zn is charged to I0 flowing through 3Zn so the per-phase loop stays consistent.
With a high-resistance grounded neutral, 3Zn dwarfs everything else in the loop. Nearly all the impedance sits in the zero-sequence network and the fault current lands near the phase-to-neutral voltage divided by Rn. That is the only sense in which zero sequence dominates: it holds the impedance, never a larger current.
A delta bus fed by a grounded star is not isolated #
Trace the current instead of the labels. It leaves the faulted phase, enters earth, runs the grounding grid to the transformer's grounding connection, up through the resistor into the star neutral and back through the winding to the fault. The path exists because the source winding is a grounded star; whether the bus or its loads are delta changes nothing, since delta-connected loads sit between phases with no neutral point and take no zero-sequence current — the distinction worked through in why a grounded wye sources ground fault current and a delta does not.
The delta winding on the HV side closes the zero-sequence loop inside the transformer: the zero-sequence current circulates in that delta and never reaches the HV network, so the zero-sequence impedance seen from the bus ends at the transformer plus the neutral term.
The different case is a system with no grounded neutral anywhere — no grounding transformer, no grounded star winding. There the only return is the distributed capacitance of the cables and windings, the earth-fault current is the charging current of the system, and the series model with 3Zn does not apply; that path is the one traced in the ground fault current path for an ungrounded generator fault. The voltage class alone fixes only the driving voltage; the current needs the neutral impedance and the sequence data.
Ground fault on a 35 kV bus held to 10 A by the neutral resistor #
This runs your case with a typical high-resistance grounding figure: a bolted phase-A-to-ground fault on the bus, nominal prefault voltage, and the transformer's star neutral grounded through a resistor as the only deliberate return.
Inputs #
- Bus voltage: 35 kV line-to-line, the LV bus in your case, fed by the delta–star transformer.
- Design earth-fault current: 10 A, the value the grounding design holds the fault to. This figure is illustrative; the real number is in the grounding design records for your system.
- Sum of the sequence impedances seen at the fault before the resistor: 20 Ω, an example read off the transformer test report and the cable data for a fault right at the bus.
- Driving voltage: the phase-to-neutral value, 35 kV / √3 = 20.2 kV.
The rule #
The three sequence networks in series carry a single current: the phase-to-neutral voltage divided by the sum of the positive-, negative- and zero-sequence impedances plus three times the neutral resistance. The faulted-phase current is three times that, and the resistor itself is sized from the same voltage and the design current.
The arithmetic #
- Neutral resistor: Rn = 20207 V / 10 A = 2020.7 Ω, call it 2021 Ω.
- Its zero-sequence term: 3Rn = 3 × 2020.7 Ω = 6062 Ω.
- Series total: Z1 + Z2 + Z0 + 3Rn = 20 Ω + 6062 Ω = 6082 Ω.
- Sequence currents: I1 = I2 = I0 = 20207 V / 6082 Ω = 3.32 A.
- Faulted-phase current: Ia = 3 × 20207 V / 6082 Ω = 9.97 A; the residual 3I0 a relay measures is that same current.
The result #
The resistor provides 6062 of the 6082 Ω, 99.7% of the loop, so the fault lands within 0.3% of the design value. Leave the transformer and cable impedances out entirely and the current moves under half a percent; leave the resistor out and the same loop would push about 1010 A. The fault current is whatever the grounding design says it is, the three equal sequence currents are one third of it, and the whole figure is an estimate to confirm against the grounding design records and the equipment documentation.
The decision #
Set the ground overcurrent element — a 51N on the neutral or residual measurement — below the calculated fault current. Half of it, a 5 A pickup, absorbs resistor tolerance and keeps the element well inside the fault; any ground element set above the design current never operates for this fault, and the phase overcurrent elements, set to carry load, will not see it either.
The sensing has to resolve a small current: what a zero sequence CT does in ground fault protection covers the core-balance measurement, and when you pick the sensor, match it to the relay with the notes on selecting a zero-sequence CT for ground-fault relays. Whether the scheme trips or only alarms is a choice for the grounding design; that it must see the current is not.
Check the model against the plant #
Four things decide whether the numbers hold on the real bus. Whatever part of this means opening the resistor enclosure comes after lockout and a proven absence of voltage at its terminals, because during a ground fault the star neutral rises to near phase-to-neutral potential.
- The nameplate winding connection of the transformer feeding the bus, and that the star neutral actually lands on the grounding resistor.
- The resistor value in service, taken from the design records, since shorted or bypassed elements change the current.
- The sequence impedances from the transformer test report and the cable tables; for a delta–star transformer the zero-sequence impedance of the star winding sits close to its leakage impedance because the delta gives the zero-sequence current a circulating path.
- Every other grounding source on the bus — a second transformer in parallel, a grounding transformer on a tie — since each one adds a parallel return and shrinks the neutral term.
The decision for each case #
- Fed from a resistance-grounded star neutral, as in your case: use the series model. The sequence currents are equal, the neutral term carries nearly all the loop impedance, the fault current sits at the grounding design's value, and the protection decision is a ground element picked up below that value.
- No grounded neutral anywhere on the system: the resistor model does not apply. The earth-fault current is the charging current of the cables and windings, detection is a different problem, and nothing should be set from the formula above.
Questions asked
Can the neutral voltage be used to detect this fault?
Yes. During a ground fault the star neutral shifts to nearly the full phase-to-neutral voltage, so a voltage element across the neutral grounding resistor, ANSI 59N, sees a large definite signal even though the current is small. High-resistance grounded schemes commonly use that element or pair it with a neutral current element, and it needs no current sensor able to resolve a few amperes.
What does a ground relay actually measure for this fault?
A residual or neutral overcurrent element sees 3I0, the whole earth-fault current, not one third of it. A neutral CT at the resistor covers everything fed by that source, while a zero-sequence CT around one feeder's three phase conductors sees only that feeder's share of the ground current, which is what makes tripping selective between feeders.
What happens to the fault current if a second grounded transformer is paralleled on the bus?
The two grounding paths are in parallel. With two equal resistors the neutral impedance halves, the 3Zn term halves, and the earth-fault current roughly doubles, shared between the resistors. Re-check the ground pickup and each resistor's rating whenever the switching order changes how many grounded sources feed the bus.
Does the answer change for a fault through an arc or fault resistance?
Only the magnitude. The fault impedance carries the full faulted-phase current 3I0, so it enters the series loop as 3Rf and the denominator grows to Z1 + Z2 + Z0 + 3Zn + 3Rf. The three sequence currents stay equal to each other and simply shrink; a few ohms of arc add little to a loop already dominated by the resistor.
Do delta-connected loads on the bus change the ground-fault current?
No. A delta load connects phase to phase and has no neutral point, so zero-sequence current cannot flow into it and it never appears in the zero-sequence network. Its positive- and negative-sequence impedance sits in parallel with the source and is normally left out of fault calculations because the source impedance is far smaller.