How-to
Wiring a 0-10 V speed reference and fault relay to a VFD
Short answer
Connect the 0-10 V reference to the analog voltage input with its common to the analog common, set the low and high frequency endpoints first (for example 9 Hz and 90 Hz), assign fault indication to the multifunction relay (PD0052 = 3), and measure the contacts before wiring the fail-safe circuit: on the tested unit FB-FC was normally closed and FA-FB normally open, contradicting the manual.

On this page
Wire the 0-10 V signal to the drive's analog voltage input (VI on this class of small drive) and the signal common to ACM, set the analog frequency endpoints before anything else (one working setup used PD072 = 9 Hz and PD073 = 90 Hz), assign the fault relay with PD0052 = 3, and measure the relay contacts instead of trusting the labels. On the tested unit FB-FC was normally closed and FA-FB normally open, the opposite of the manual's drawing. If your drive already has the signal wired but ignores it, the causes are covered in why a VFD ignores the analog speed reference from the controller; this procedure is the full wiring and setup from the terminals up.
What goes where on the control terminals #
The analog and digital circuits have separate commons and you keep them separate:
| Signal | Terminal | Function |
|---|---|---|
| 0-10 V reference output | VI | Analog frequency command |
| Reference common | ACM | Analog common |
| Run, direction, reset commands | FWD, RVS, RST | Digital inputs |
| Digital input common | DCM | Digital common |
| Fault relay contacts | FA, FB, FC | Multifunction relay output |
The reference common goes to ACM, not to DCM. Mixing the two commons is a common cause of a speed signal that reads wrong or drifts. One variant of this drive family also offers a multi-mode analog input selected with PD0070 = 0 for analog voltage operation; confirm in the documentation for your exact model which terminal that code governs before relying on it.
Set the frequency endpoints first #
Before touching wiring, set what zero and full reference mean. The analog low endpoint and high endpoint are set separately, and an unset or reversed pair is why a drive runs flat out at zero command. The reported working setup used PD072 = 9 Hz as the low endpoint and PD073 = 90 Hz as the high endpoint, so zero volts commands 9 Hz and full reference commands 90 Hz. Example: at a commanded 5 V the output is 9 Hz + (5 V / 10 V) x (90 Hz - 9 Hz) = 9 + 0.5 x 81 = 49.5 Hz.
Wire and prove the analog input #
- Isolate the drive and verify absence of voltage before opening the terminal cover; all low-voltage wiring below is done de-energized.
- Set the endpoints (PD072 low, PD073 high) with the drive's keypad, low frequency first.
- Disconnect the controller and test the input with a 10K potentiometer: wiper to VI, one end to the drive's own reference supply, other end to ACM.
- Power up and confirm the output frequency rises smoothly across the endpoint range as you turn the pot up.
- Remove the pot, connect the controller's speed reference output to VI and its common to ACM. Use shielded cable for the reference pair, shield bonded at the drive end only.
- Command minimum and maximum speed and measure the voltage at VI: zero command should give the low endpoint, full command the high endpoint.
- If zero command gives maximum speed, check for swapped signal and common at VI and ACM, and confirm the endpoints are ordered low-to-high.
Assign and measure the fault relay #
Set PD0052 = 3 to assign fault indication to the FA/FB/FC multifunction relay (other values select run, zero speed, braking and more). Then measure, with the drive healthy and powered: on the tested unit FB-FC showed continuity (normally closed) and FA-FB showed open (normally open), with FB as the common. That contradicted the printed terminal diagram, so prove it on your drive with a continuity meter in the healthy state and again during a fault.
For a fail-safe controller input use the contact pair that is closed while the drive is healthy and opens on a fault — on the tested unit, FB-FC. That way a drive fault, a broken wire and a dead drive all open the circuit; a normally open contact only signals when the relay itself changes state.
Commissioning checks #
- Potentiometer sweep proves the analog input and endpoints before the controller is reconnected.
- Controller connected: measured VI voltage tracks the commanded speed from zero to full reference across the endpoint range.
- Relay monitored with PD0052 = 3: force a fault (for example by pulling a motor lead with the drive stopped and restarted under controlled conditions) and confirm the controller's fault input changes state.
- A correct result: speed rises with reference voltage, and the fail-safe input drops when the normally closed pair opens.
One decision for each case: signal to VI with common to ACM, endpoints set before wiring, PD0052 = 3 for the fault relay, and the measured closed-when-healthy pair — FB-FC on the tested unit — into the controller input.
Questions asked
Why does zero command give maximum speed?
The signal and common are swapped, or the low and high endpoints are reversed. Check that the 0-10 V output reaches the analog voltage input and the common reaches the analog common, then confirm the low endpoint is the lower frequency and the high endpoint the higher one.
Should the fault circuit use the normally closed contact?
Yes, for a fail-safe input: a closed-when-healthy contact opens on a fault, on a broken wire and when the drive is unpowered, so the controller sees all three as a fault. A normally open contact only signals when the relay itself changes state.
Can I keep the fault relay energized while the drive is powered off?
On drives that offer it, some manufacturers let you feed external 24 V DC into the control terminals so the fault relay stays energized with the drive off. That is the opposite of fail-safe wiring: decide which behaviour your safety chain needs before powering the relay externally.