Current IntelPower LibraryShop main store

Explainer

DC bus sharing on servo drives: one supply, one filter group

Variable frequency drives Published 10 min read By Current Intel engineering team

Short answer

A shared DC bus collapses the AC side to exactly one protected mains supply for the whole network, caps drives at six per passive line filter, and limits total motor cable behind that filter as PWM frequency rises. Size the single breaker and filter on the group's continuous current, not the nameplate sum.

On this page
  1. What changes when servo drives share one DC bus?
  2. How many mains supplies can feed one shared DC bus?
  3. Which supply layouts are allowed inside one DC bus network?
  4. How many drives can sit behind one passive line filter?
  5. How does PWM frequency limit the motor cables behind one filter?
  6. How do you size the single breaker and filter for the group?
  7. Do drives on a shared bus still need braking resistors?
  8. When should you split axes into a second filter group?
  9. Questions asked

Bridge the DC bus terminals of several servo drives and the AC side stops being a per-drive problem: the whole network becomes one load with one feed, one filter group and one motor cable budget. This article gives the three rules that decide the layout — a single protected mains supply per bus network, a hard cap on drives per passive line filter, and a motor cable total that falls as PWM frequency rises — then works one cabinet's example through filter, breaker and cable sizing, and closes with the split decision for larger machines. The cap values quoted are one drive family's documented limits for its 400 V class hardware; the one-feed topology rule is the part that generalizes, and your own drive manual supplies your numbers.

What changes when servo drives share one DC bus? #

Linking the DC bus terminals merges several drives' rectifier outputs into one energy pool where a descending axis regenerates and an ascending axis consumes that energy, and three documented limits come with it: one mains supply for the network, six drives per passive line filter, and a PWM-set cable budget.

A linked bus is a permanent conductor, not a switching arrangement: while it exists, every drive on it can feed every other, and the per-drive protection assumptions you used before linking stop holding. The reward for accepting the rules is real — vertical axes exchange braking energy electrically instead of burning it in resistors, so the group needs less resistor capacity overall.

The caps quoted through this article are the documented limits of one servo drive family's manual for its 400 V class drives. The topology rules — one feed, one filter group, a bounded cable total — transfer between families; the counts and lengths do not, so take your values from your own drive manual's common-bus, line-filter and fuse-protection sections.

How many mains supplies can feed one shared DC bus? #

Exactly one: once any two drives share bus terminals, the whole network must be fed from a single AC supply through a single set of fuses or one breaker, because a second fused feed can keep a faulted drive energized through the bus after its own fuse has opened.

The failure mode is a backfeed. Give three drives three fused AC feeds and bridge their bus terminals: when the fuse ahead of one drive opens on a fault, that drive keeps running on power backfed through the link from the other two drives' rectifiers, whose fuses have not opened. The protective device that just operated no longer disconnects the faulted section, and the isolation you expect from locking out one breaker does not exist. One drive family's manual draws exactly this layout crossed out in its fuse-protection figure for that reason.

One mains supply means one protected AC feed point into the group: one breaker or fuse set ahead of the line filter and the drives' AC terminals. Drives tapped from a distribution busbar behind that one device still count as one supply, and a second protective device anywhere on the network counts as a second supply even when both come from the same switchboard.

Which supply layouts are allowed inside one DC bus network? #

Three layouts exist and two are allowed: every drive on the AC feed plus the bus link, or a mixed layout where some drives hang on the bus alone with no AC connection; two or more separately fused feeds on one linked bus are prohibited.

Layout AC connection Bus link Protective device
All drives fed every drive on the single protected feed linked between all drives one upstream device sized for the group's continuous line current
Mixed only the rectifier-carrying drives on the feed DC-only drives hang on the link the same single upstream device; link conductors sized for the bus current they carry
Multiple feeds separate fused feeds per drive or group linked across the feeds prohibited: an opened fuse cannot isolate a drive backfed through the bus

The mixed layout is what a vertical-axis group usually wants: the drives that carry rectifier and inrush duty take the AC feed, the rest take power through the link, and every drive still sits behind the single protective device. Before distributing axes this way, the drive manual has to approve two details — which devices are listed for DC-bus-only operation, and how much bus current the terminals of a DC-only drive may carry, since those terminals supply everything that drive's motors draw.

How many drives can sit behind one passive line filter? #

Six drives per passive line filter, counting bus-linked drives the same as AC-fed ones, with the group's continuous line current kept inside the filter rating — 55 A for the filter class used in the worked example below.

The rating check runs on the group's continuous RMS line current rather than on the sum of drive nameplate ratings, because axes rarely draw peak current together. Below the filter rating, one filter serves the group; above it, the manual permits a second identical filter in parallel under its stated conditions. The drive-count cap is per filter, not per network: an 18-axis machine becomes three filter groups, every one of them behind the single protected feed, because a separate feed for any group would break the one-supply rule.

How does PWM frequency limit the motor cables behind one filter? #

One filter's motor cable budget at a 5 kHz PWM switching frequency is 75 m total across all its axes in the drive family used in the worked example, higher frequencies shrink that budget, and routed cable lengths — not straight-line distances — decide how many axes a group takes.

Grouping axes behind one filter concentrates the common-mode and cable-capacitance charging currents of every motor cable into that one component, which is why the cap is a group total rather than a per-drive value. Six axes sharing one 75 m budget average 12.5 m per axis (75 ÷ 6), and the sum has to include panel-internal routing, tray runs and service loops. If the routed total exceeds the budget at your configured frequency, lower the PWM frequency and accept its effects on current ripple, motor losses and control bandwidth, then re-check the drive's continuous output current, which derates as switching frequency rises; otherwise shorten the routes or move axes to another filter group that carries its own budget.

How do you size the single breaker and filter for the group? #

Size both devices on the group's continuous RMS line current, never on the nameplate sum: five 13 A single-axis drives plus one 8.8 A dual-axis module reach 73.8 A on nameplate but 44 A continuous under the example's motion profile, and that continuous figure picks the devices.

Worked example — one feed, one filter group.

  • Inputs: five single-axis drives and one dual-axis module on one 400 V three-phase feed; the motion profile's sizing report puts each single-axis drive at 8 A RMS continuous equivalent and the dual module at 4 A. These two continuous figures are illustrative inputs, so treat the result as an estimate: take yours from the drive family's sizing tool and confirm it against measured line current at commissioning.
  • Continuous group current: 5 × 8 A + 4 A = 44 A.
  • Nameplate check, not the sizing basis: 5 × 13 A + 8.8 A = 73.8 A, or 5 × 13 A + 2 × 8.8 A = 82.6 A if the dual module's rating is a per-axis figure. The manual's rating basis decides which reading applies; either shows why the nameplate sum overshoots.
  • Filter: the continuous group current sits below the 55 A rating of the family's passive line filter for this class, so one filter serves the whole group.
  • Breaker: the next approved protective-device value at or above the continuous group current and at or below the filter rating gives 50 A from the family's approved table, and the chain 44 A ≤ 50 A ≤ 55 A holds.
  • Drive count: five single-axis modules plus one dual-axis module is six drives, exactly at the per-filter cap.

Two boundaries finish the sizing. The breaker comes from the drive family's approved protective-device table rather than from a generic curve, because that table is what carries the coordination behind it — the same logic set out for using a motor circuit breaker on a servo drive infeed. And the protection decision is a code question too: NFPA 70, the National Electrical Code, 2023 edition, requires conductors and equipment to be protected against overcurrent in line with their ratings, and IEC 61800-5-1 sets the electrical safety requirements that adjustable-speed drives themselves must meet, so confirm the final selection with the authority having jurisdiction and the drive's documentation.

One safety step belongs before any of this wiring is built or reworked: de-energize the feed, wait the drive manual's documented bus-discharge time and verify absence of voltage at the bus terminals before touching them, because a shared network pools the capacitor banks of every drive on it and stores more energy than a single drive.

The decision for this example: the whole group runs on one protected feed through one filter, and nothing links it to a second feed.

Do drives on a shared bus still need braking resistors? #

Yes — sharing the bus only moves energy between axes, so a descending axis powers an ascending one and only the group's net surplus reaches a resistor, which is why the resistor is sized on that surplus across the whole motion profile, not on one axis's worst descent.

Run the group's profile as one energy balance: inertia, speed, torque and duty for every axis, summed over the cycle. The bus exchange cancels opposing flows first, and the resistor — integrated in each drive, or one external unit wired across the bus per the manual's connection rules — is sized on what survives that cancellation, for both peak power and repeated-duty energy. Integrated resistors fit when no axis dominates and the leftovers are small; their continuous and peak energy ratings are per drive and modest. One external resistor across the bus fits when the group's net surplus outruns the integrated units.

The physics of why that energy lands on the bus instead of turning into heat at the motor is the subject of why a motor-side braking resistor works on a PM servo. Note the sibling topology too: some systems put one central supply module on the AC side and feed the inverters from the shared bus instead of giving every drive its own rectifier. The application technique for one manufacturer's Kinetix 5700 multi-axis servo system requires a line reactor at the input of each 2198-P208 DC bus power supply so the modules share current evenly — the same input-impedance reasoning behind line reactor sizing for servo drives on 240 V single phase.

When should you split axes into a second filter group? #

Split when any one per-filter limit breaks — a seventh drive, a continuous current above what parallel filters can carry, or a routed cable sum over the PWM budget — and every split group stays behind the single protected feed, never behind a feed of its own.

Read the caps as per-filter, not per-machine, and the split decision writes itself. Each group keeps its own three checks: the drive count cap, the filter's current rating, and the motor cable total at the configured PWM frequency. Parallel identical filters behind one feed extend current capacity inside a group under the manual's conditions; they do not raise the drive count. What a split can never do is add a feed: a bus link reaching into a group with its own breaker recreates the prohibited two-supply layout, and a machine that genuinely needs two feeds needs two separate DC bus networks with no link between them.

An 18-axis machine on one shared bus is therefore three groups of six behind one protected feed, each with its own cable budget. If one group's budget still fails, drop that group's PWM frequency or shorten its routes rather than adding a feed.

Questions asked

What proves the shared bus is dead before I work on it?

A measurement, not elapsed time alone. De-energize the feed, wait the bus-discharge time stated in the drive manual for the network, because the pooled capacitor banks of a shared bus hold more energy and can take longer than a single drive rating, then verify absence of voltage at the bus terminals with a meter rated for the DC voltage present before touching anything.

Does a drive without an AC connection need its own fuse?

No mains fuse, because its only supply path is the shared bus behind the network single protective device. What the drive manual must provide is approval for DC-bus-only operation of that part number and a bus current limit for its terminals, and the link conductors are sized to that bus current. Check both against the manual revision matching your hardware before distributing axes.

Can I keep each drive on its own breaker and still link the buses?

No. A bus-linked network takes exactly one protected feed; individual breakers per drive create exactly the multi-feed layout the fuse-protection rules prohibit, because an opened breaker leaves the drive energized through the bus. Per-drive protective devices belong on designs where the buses stay separate. If you need per-axis electrical isolation for service, that is a design question the drive manual addresses; it cannot come from adding mains feeds to a linked network.

Do these caps apply to every servo drive brand?

Treat them as one manufacturer published values, not industry constants. What transfers is the structure, one feed per bus network, drives grouped per filter, cable totals bounded by switching frequency, while the numbers are published per drive family and manual revision. Read your own manual common-bus and line-filter sections, and re-check them whenever the hardware revision changes.

Keep reading

  • Selection guide

    Line reactor sizing for servo drives on 240 V single phase

    Size a servo-drive line reactor from the drives' documented single-phase input currents, never from motor kilowatts. A 3 kW servo group on 240 V has a 12.5 A ideal floor but draws near 23 A in practice, so each machine branch takes a 25 A, 3 % reactor with the maker's documented two-coil single-phase connection.

    Variable frequency drives

  • Selection guide

    Frequency converter sizing when a single-phase load regenerates

    A standard diode-front-end frequency converter cannot pass reverse power to the supply, so a single-phase load regenerating into one line pair charges the DC bus until the overvoltage trip. Size on per-line current and reverse power, not net kilowatts, and select a four-quadrant active-front-end converter or a rotary set rated for continuous regeneration and the single-phase unbalance.

    Variable frequency drives

  • Selection guide

    Sizing a VFD for a three-phase motor on single-phase input

    On single-phase input, size the drive's continuous output current at no less than twice the motor nameplate full-load amps when the drive's 50% derating applies, and feed it from a branch circuit sized to 125% of the drive's published single-phase input current — never from the ideal wattage estimate. For a 10 hp, 208 V motor that means a drive rated at least 61.6 A output.

    Variable frequency drives