Line reactor sizing for servo drives on 240 V single phase

Variable frequency drives Published 9 min read By Current Intel engineering team

Short answer

Size a servo-drive line reactor from the drives' documented single-phase input currents, never from motor kilowatts. A 3 kW servo group on 240 V has a 12.5 A ideal floor but draws near 23 A in practice, so each machine branch takes a 25 A, 3 % reactor with the maker's documented two-coil single-phase connection.

On this page
  1. What size line reactor does a 3 kW servo group need on 240 V single phase?
  2. Why can't you size the reactor from motor kilowatts alone?
  3. How much impedance should the line reactor have?
  4. Can a three-phase line reactor be wired for single phase?
  5. Should each servo drive get its own reactor or share one?
  6. When does a servo drive on a single-phase supply actually need a line reactor?
  7. Will a line reactor stop electrical noise in the CNC controls?
  8. What goes on the order for each machine?
  9. Questions asked

Two machines — a CNC router carrying four 750 W servo drives and a CNC mill carrying two 750 W drives plus one 1.3 kW drive — on a 240 V single-phase supply do not need four different reactor answers, and they do not need one sized from motor kilowatts. The kilowatts give a floor, the drive manuals give the real number, and the reactor order falls out of a two-branch sum. Work the floor first, correct it for how a single-phase rectifier actually draws current, group by machine branch, and buy one reactor per branch in the standard impedance class with the maker's single-phase connection sheet. The sections below carry the arithmetic step by step and end with the decision for both machines.

What size line reactor does a 3 kW servo group need on 240 V single phase? #

Size the reactor from the summed input current on each drive manual's single-phase rating page, not from motor kilowatts: a 3 kW servo group has a 12.5 A ideal floor on 240 V, draws near 23 A in practice, and takes a 25 A, 3 % reactor.

The floor is the lossless, unity-power-factor calculation: 3000 W ÷ 240 V = 12.5 A. No rectifier front end behaves that way. Assume the drives convert at 90 % efficiency with a true input power factor of 0.6 — example inputs typical of small capacitor-input drives, with the manuals' own figures replacing them — and the branch estimate becomes 3000 W ÷ (240 × 0.6 × 0.9) = 3000 ÷ 129.6 = 23.1 A. The next standard reactor frame above that estimate is 25 A.

Check the drop before accepting the frame: a reactor of this class and rating drops 0.03 × 240 = 7.2 V at rated current, so at 23.1 A the drop is 7.2 × (23.1 ÷ 25) = 6.7 V, or 2.8 % of the supply. That sits inside the class, with margin for a supply sagging toward the drive's undervoltage alarm.

The current rating is a minimum, not a target: the coil does the heating, so it must cover the summed input current of everything wired after it, moving one frame up whenever the manuals land between catalog sizes.

Why can't you size the reactor from motor kilowatts alone? #

Motor kilowatts give a lossless, unity-power-factor floor, while a single-phase rectifier front end draws current in narrow pulses between voltage peaks, so the true RMS input current runs far above the ideal bound.

The kilowatt rating describes shaft output after the drive's conversion losses; the input sees those watts through a power factor below one and an efficiency below one. The pulse shape makes it worse: a capacitor-input rectifier conducts near the voltage crests, and crest factor alone can double the RMS draw against an even sine. Drive makers therefore publish a separate single-phase input current for each frame — usually higher than the three-phase figure — and that published figure is what you sum for the reactor coil. The same asymmetry is why a VFD's input current can read higher than its output; servo inputs behave the same way at smaller scale. The estimate in the first section brackets the answer when a manual page is missing, but the manual wins every time you have it.

How much impedance should the line reactor have? #

Three percent impedance is the standard choice for most drive inputs; step to five percent only for heavy harmonic mitigation, and only after the drive manual shows it allows that much source impedance and the DC bus tolerates the larger drop.

Impedance sets the voltage drop at rated current, and that drop is what smooths the input current pulses and cuts the harmonics the supply sees. More impedance helps the supply but starves the DC bus; five percent on this supply drops 0.05 × 240 = 12 V at rated current, enough to matter at the far end of a long feeder, which is why the standard class stays the default.

Convert quotes so they compare. Inductance from a chosen class: L = (Z ÷ 100) × V ÷ (2π × f × I), with L in henries. The reactor in the first section works out to (3 ÷ 100) × 240 ÷ (377 × 25) = 7.2 ÷ 9425 = 0.00076 H, about 0.76 mH of total series inductance at 60 Hz. Run a millihenry quote the other way: a 2 mH coil offered for a 20 A branch gives Z = (377 × 0.002 × 20 ÷ 240) × 100 = 6.3 %, a heavy part that only fits where the drive tolerates the drop. Reactors exist for the supply side and the motor side; the input-versus-motor-side choice is a separate question, covered in choosing a line reactor or motor reactor for a VFD, and everything here is the input side.

Can a three-phase line reactor be wired for single phase? #

Only with the reactor maker's documented single-phase connection: most line reactors are built as three coils on one core, and several manufacturers publish a two-coil wiring sheet for single-phase use that states the resulting inductance, but the rating applies only if their sheet confirms it.

Two coils in series double the inductance of one coil; the second documented arrangement puts one coil in each of the two line conductors. The two wirings deliver different total inductance from the same catalog part, which is why the maker's sheet, not the datasheet headline, sets what you get. The coil current rating still bounds the branch under any wiring: pass more than a coil's rated current and it overheats. What needs the maker's confirmation is the connection method, the effective inductance in the current path for that method, and the thermal rating when only two of three coils carry current. A datasheet silent on single-phase use means a question to the maker before buying, not an assumption. And before any of this wiring: lock out the machine, then test for absence of voltage at the reactor and drive input terminals.

Should each servo drive get its own reactor or share one? #

Share by machine branch: all four drives of the router on one reactor and all three of the mill on another, each coil rated to its branch's summed input currents — individual per-drive reactors are the upgrade when panel space allows.

The machine is the natural group because its drives start and load together under one feeder, so the coil sees their sum whenever any of them runs. Rate that coil to the sum of the documented input currents, never to the ideal bound and never to a grouping sketch that has not been counted: four drives plus three drives is seven, a sketch that places only six has dropped one, and the recount happens before ordering. A shared coil couples everything on it — a reactor fault or a service outage takes the whole branch down, and a later drive addition on that machine forces a bigger frame. Drives that never run together should never share a coil, because the rating then has to cover the worst simultaneous pair and the saving is gone.

When does a servo drive on a single-phase supply actually need a line reactor? #

Check the drive manual first, then the supply stiffness: one drive maker's application note treats an input reactor as near-mandatory when the feeding transformer can deliver twenty times the drive's input current — the stiff-supply case where a small drive hangs on a huge transformer.

Work the stiffness ratio for this shop: a 45 kVA single-phase transformer delivers 45,000 ÷ 240 = 187.5 A, one twentieth of that is 9.4 A, and any branch drawing under about 9 A sits twenty times under that transformer. Both machine branches here clear the flag comfortably, which is the strong case for buying the reactors rather than debating them.

The manual outranks the ratio: installation instructions state when the maker requires an input reactor and how much source impedance the rectifier and its control power tolerate, and reactor catalogs publish selection tables by horsepower for exactly the single-phase-drive case.

No NEC article forces the reactor itself. NFPA 70, the National Electrical Code, 2023 edition, governs the conductors and overcurrent protection you land it with, and the drive's electrical ratings sit under IEC 61800-5-1 and its UL counterpart, so confirm the reactor requirement in the drive manual and with your local authority having jurisdiction. The same reactor trims supply harmonics and lifts true power factor somewhat; how a single-phase input drive's true power factor behaves and what raises it covers that side in detail.

Will a line reactor stop electrical noise in the CNC controls? #

No — a line reactor cleans the supply side and will not quiet conducted noise reaching the CNC controls; that noise needs the drive's input EMI filter, shielded motor cable and clean shield grounding at the drive end.

The reactor is a differential-mode part: it sits in series with the line current and smooths the current pulses that the supply reads as harmonics. Noise reaching position controls is usually common-mode, conducted onto ground through the drive's switching and the motor cable; that current flows in all conductors together, so it never sees the coil's differential impedance and passes essentially untouched. The fix list is different: the EMI filter the drive manual specifies at the input, shielded motor cable with the shield landed the way that manual shows, and physical separation between motor cable and control wiring in the tray. One component bought to fix both problems fixes one of them.

What goes on the order for each machine? #

Order one single-phase-rated reactor per machine: for the 3 kW router and the 2.8 kW mill, a 25 A unit in the standard impedance class with the maker's two-coil single-phase connection sheet, then re-check the frame against the seven manuals' summed input currents before you buy.

Machine branch Servo drives Connected power Ideal bound at the supply Example draw (PF 0.6, efficiency 0.9) Reactor frame
CNC router 4 × 750 W 3.0 kW 12.5 A 23.1 A 25 A
CNC mill 2 × 750 W + 1 × 1.3 kW 2.8 kW 11.7 A 21.6 A 25 A

Both frames in the standard impedance class, one reactor per machine branch, single-phase connection documented by the reactor maker.

Two checks close the order. Read each manual's single-phase input current column and add it up per branch: if a branch's sum lands above the example draw, the frame moves to the next catalog size, and if it lands below, keep the frame from the table anyway, because the margin absorbs the assumption spread. Confirm the maker's sheet for the two-coil connection states an inductance consistent with the impedance class, and land each reactor behind its own machine disconnect. That is the decision: two reactors, one per machine branch, the frames from the table, adjusted upward only where the manuals' summed input currents demand it.

Questions asked

Does a line reactor limit the inrush when a servo drive charges its DC bus?

No. Servo drives charge the bus through their own soft-charge resistor or relay circuit, and that circuit sets the inrush, so it stays wired exactly as the manual shows. The series reactor limits the current rise into the rectifier and smooths the running input pulses, which is a different job; size the reactor for the running branch current, not for the charging event.

What goes wrong if the reactor's current rating is too small for the branch?

The coils overheat and age their insulation first. A badly undersized iron-core coil can also push itself into saturation, where the inductance collapses and the impedance you counted on disappears. Size the coil to the summed documented input current and take the next catalog frame up; the margin also keeps the real voltage drop near what the class calculations assumed.

Can one reactor serve both machines if they share one feeder?

Electrically yes: sum the documented input currents of all seven drives and rate the reactor above that total. Practically it couples the machines, so isolation, service or a later drive addition on one machine now involves the shared coil and both feeders. Two branch reactors keep each frame near its own branch current and keep the machines independent.

Will the reactors bring the shop's supply harmonics into compliance on their own?

Probably not on their own. A standard-class reactor cuts the lower harmonic orders substantially, but compliance against IEEE 519-2022 is measured where the utility supply meets the building with the whole feeder running, including everything else on it. Treat the reactors as a large first cut, and if the utility or the building owner requires a number, have a harmonic study done before adding filters.

How are the feeder conductors to the reactors sized?

From the drive input currents, not the motor kilowatts. NFPA 70, the National Electrical Code, 2023 edition, requires conductors supplying power conversion equipment to have an ampacity of at least 125 percent of the equipment's rated input current. Sum the manuals' single-phase input currents per branch, apply that rule to the conductors and the overcurrent protection, and confirm the final sizes with your local authority having jurisdiction.

Keep reading

  • Selection guide

    Sizing a VFD for a three-phase motor on single-phase input

    On single-phase input, size the drive's continuous output current at no less than twice the motor nameplate full-load amps when the drive's 50% derating applies, and feed it from a branch circuit sized to 125% of the drive's published single-phase input current — never from the ideal wattage estimate. For a 10 hp, 208 V motor that means a drive rated at least 61.6 A output.

    Variable frequency drives

  • Selection guide

    Choosing a line reactor or motor reactor for a VFD

    Pick the side first. A line reactor goes between supply and drive input, sized on drive input amps at 3% impedance for transient buffering or 5% for harmonic reduction; a motor reactor goes between drive output and motor, sized on motor FLA, for reflected-wave protection on long shielded leads. The two are not interchangeable.

    Variable frequency drives

  • How-to

    Wiring a VFD R S T input from a 240 V single-phase supply

    The two hot conductors land on any two of the R, S and T line terminals (R and S is the common choice), the equipment grounding conductor lands only on the drive's dedicated earth terminal, and T stays empty. Measure hot-to-hot rather than to ground, and confirm the reading against the drive's rated input range before energizing.

    Variable frequency drives