Troubleshooting
Did the hi-pot test damage these arresters
Short answer
The logged test does not support the claim: 30 microamps at the requested test voltage is about 440 megohms and under half a watt, far below what damages a metal-oxide arrester, and an arrester actually seeing that voltage would have driven the current up and tripped the set. The burned arresters and the A-phase vacuum-bottle failure date to the re-energization or earlier; first establish AC or DC, the connection, and what stayed connected.
On this page
- The reading clears the test, not the equipment
- Working the 13.2 kV, 30 μA reading over the five-minute hold
- What a 10 kV rating means on this system
- Establish what the tester actually energized
- Record the evidence before resetting anything
- Matching each symptom to its next check
- Retest the cable, not the switchgear
- Questions asked
The numbers do not support the assumption. A leakage of thirty microamps works out to about 440 MΩ and 0.4 W at the requested test voltage, and a metal-oxide arrester that actually had that voltage across it would have conducted orders of magnitude harder and tripped the test set. The stable, trip-free hold is evidence that the arresters were not damaged during the test; the burned units and the A-phase vacuum-bottle failure point to the re-energization event or to damage that predated the test. What you must establish first is what the tester actually energized: AC or DC, conductor-to-ground or phase-to-phase, and whether arresters, switches and the breaker stayed connected.
The reading clears the test, not the equipment #
An insulation failure during a withstand test announces itself: the current rises sharply, the leakage trend breaks, or the set trips on overcurrent. The recorded hold showed none of that. The current sat in the microamp range, held steady through the final five minutes, and the set did not trip. Treat the logged test as having passed without any device in the connected circuit breaking down.
That clears the test as the damaging event. It does not certify every device that was connected, because an average phase current cannot tell you what voltage each device actually saw. Both statements matter for what you do next.
Working the 13.2 kV, 30 μA reading over the five-minute hold #
Inputs, with their source:
- Test voltage: 13.2 kV, the customer-requested level, held for five minutes after a one-minute step at 6.6 kV (the test record).
- Average leakage: 30 μA per phase (the test record).
- Hold time: 300 s.
- Illustrative arrester discharge: 28.5 kV at 10 kA for a 0.5 μs surge, a representative published point for a 10 kV duty-cycle distribution arrester. Use your arrester's own datasheet for the real figure.
The rules in words: resistance is voltage divided by current; power is voltage times current; energy is power times time; a surge's energy is discharge voltage times surge current times surge duration.
The arithmetic:
- R = 13,200 V ÷ 0.000030 A = 4.4 × 10⁸ Ω ≈ 440 MΩ
- P = 13,200 V × 0.000030 A = 0.396 W
- Energy over the hold: E = 0.396 W × 300 s ≈ 119 J
- One rated surge: 28,500 V × 10,000 A × 0.5 × 10⁻⁶ s = 142.5 J
Result: even in the worst case, where every microamp flowed through a single arrester, the whole hold deposits about 119 J, less energy than one surge that the same arrester must absorb repeatedly in service. At that power it would take roughly 356 s, longer than the entire hold, just to match a single rated discharge.
Decision: below about 140 J of total input, a hold at this level cannot destroy an arrester of this class, and the logged hold stayed under it. Combined with the stable current and no trip, the test is cleared as the cause of the damage.
What a 10 kV rating means on this system #
For distribution-class metal-oxide arresters, the maximum continuous operating voltage (MCOV) runs about 84% of the duty-cycle rating, so the nameplate 10 kV units here carry an MCOV of 8.4 kV. Station-class designs use a different ratio, as the current datasheets for 84 kV MCOV, 108 kV duty-cycle units show, so read the MCOV off the arrester itself rather than deriving it. IEEE C62.11-2020 defines the MCOV and duty-cycle rating and the tests behind them for metal-oxide surge arresters on 48 to 62 Hz power circuits above 1 kV.
On a grounded-wye 13.2 kV system the arresters see line-to-neutral voltage, 13.2 kV ÷ √3 ≈ 7.62 kV, comfortably under the MCOV. The application is correct for continuous service, the same duty logic behind why a solidly grounded transformer neutral needs no arrester. But the test voltage across such an arrester is about 1.6 times its MCOV, and metal-oxide blocks conduct steeply up there: the current climbs out of the microamp range within seconds. An arrester that stayed connected with the voltage applied conductor-to-ground would have pushed the average reading up and most likely tripped the set. The microamp reading is therefore direct evidence that the arresters were not across the test voltage during the logged hold.
Establish what the tester actually energized #
Read the test record, the set-up sheet and the lead placement, and answer each of these before anything else:
- AC or DC. A DC withstand converts to a resistance with the arithmetic above; an AC test does not, and applying the same ratio to an AC reading is a mistake.
- Conductor-to-ground or phase-to-phase. Only a grounded configuration can put voltage across an arrester at all.
- Whether each phase was tested separately or all three were tied together.
- Every device left connected per phase: switches, the breaker, arresters, transformers, instrument transformers.
- The test set's trip behavior and the raw current log by phase and by minute, not just the phase average.
- Where the leads landed relative to the splices between the old and new cable sections.
If the record cannot answer AC or DC and the connection, resolve that before any retest. The retest plan, and any assignment of blame, hangs on those two answers.
Record the evidence before resetting anything #
Do not begin by repeating the cable test. Build the sequence first:
- Which protection operated at the first re-energization, and its targets or event records.
- The A-phase vacuum bottle's condition: failed open, welded closed, or failed to interrupt. Record the state of the other two phases too.
- Photos of every arrester, with phase and location, taken before anything is removed.
- What was replaced or disconnected between the first test, the re-energization and the retest. A changed breaker or arrester state changes what the retest actually stressed.
- Whether the breaker and arresters had a known-good baseline before the first test. With no baseline, pre-existing damage stays on the table.
- Whether the test set tripped on the retest when the C-phase arrester was found shorted.
The C-phase short does not date itself: an arrester found shorted after a later retest may have failed at the re-energization, during the retest with a different connected circuit, or before any of it.
Matching each symptom to its next check #
| Symptom | What it indicates | Next check |
|---|---|---|
| Stable leakage, no trip, damage found later | No breakdown occurred in the connected circuit during the logged hold | Establish connection and connected devices; treat the damage as pre-existing or from re-energization |
| Breaker trips at first re-energization, A-phase bottle fails | A fault or an interrupter problem at energization | Read trip targets; inspect all three bottles before another close |
| Arrester measures shorted on the retest | A low-impedance path in the retest configuration; the finding does not date the failure | Disconnect it from parallel paths, confirm it out of circuit, replace it |
| Current climbing or the set tripping during any test | A conductive path somewhere in the connected circuit | Stop raising voltage, de-energize, isolate, then locate by phase and section |
Retest the cable, not the switchgear #
Opening the cubicle, the switch compartments or the cable ends starts with the circuit dead: de-energize, lock out, and test for absence of voltage before anything is opened or touched. NFPA 70E, 2024 edition, defines the electrically safe work condition that step establishes; confirm the site procedure with the authority having jurisdiction and the equipment instructions.
Then:
- Disconnect the cable from every arrester, switch, breaker and transformer before applying any withstand voltage. Cable tests are done on the cable alone, per the test plan and the equipment instructions for the cable and the test method.
- Test each phase separately with the others grounded, and log current per phase and per minute.
- After a DC test, discharge each phase and leave it grounded before re-energizing.
- Replace burned or shorted arresters; test apparently intact ones per the manufacturer's instructions before reuse.
- Judge the readings against the acceptance value for the insulation grade, the same discipline as the minimum insulation resistance for 600 V power cable tests, not against a phase average.
- Commission the breaker under its own maintenance procedure before the next close. A vacuum bottle that failed once is evidence, not a variable.
The decision for each case: the logged test did not damage the arresters, and its own record shows it. Where the arresters were disconnected during the test, the burned units and the C-phase short failed at re-energization or were already failing, and the vacuum-bottle failure plus switching overvoltage is where to look. Where the record shows the arresters stayed connected with the voltage applied conductor-to-ground, redo the analysis against what the set actually measured, but the microamp-level, trip-free hold already argues against the test as the cause either way.
Questions asked
Should the old and new cable sections have been hi-pot tested together?
No. Test the new sections at their installation level with everything else disconnected, and test the old sections afterwards at a maintenance level, also isolated. One combined test forces a single voltage onto insulation with two very different histories and hides which section any fault sits in.
Does a DC hi-pot leave a charge on the cable afterwards?
Yes. A DC withstand test leaves trapped charge in the insulation, mainly at splices and terminations. Discharge each phase and leave it grounded before anyone touches the ends or the circuit is re-energized; the stored charge is a shock hazard and can stress a breaker at closing.
Should the burned and shorted arresters be tested or replaced?
Replace them. A burned or shorted arrester is scrap; do not return it to service or use it to reconstruct events. An apparently intact unit from the same circuit can be field-tested per the manufacturer's instructions before it is reused, with the result recorded.
Would a test-set trip have proven an arrester failed during the test?
Not by itself. A trip proves a conductive path somewhere in the connected circuit, not which device failed. That is exactly why the cable is isolated before a withstand test: with only the cable connected, a trip or a climbing current points at the cable, by phase and section, and nothing else.