Feeding a rotary phase converter idler from a VFD
Short answer
Yes. A reported test ran a 4.0 kW, 240-380 V drive into a roughly 4 hp idler and started a 2 hp mill across the synthesized bus. Treat the idler as one more motor on the drive: size it on total current, strip every start and run capacitor, fit a sine-wave filter sized for the whole bus, and check each switched start against the drive's overload curve.
On this page
Yes — a VFD can feed the idler of a rotary phase converter, and a reported bench test shows the arrangement working: a 4.0 kW drive with 240 V single-phase input and 380 V three-phase output ran a roughly 4 hp star-connected idler and started a 2 hp milling motor across the synthesized bus. The mill started better than it ever had through the capacitor-balanced converter, and the workshop lights dimmed only slightly. The idler is not a cure-all, though: it is one more motor on the drive, not isolation. Size the drive on total current, strip every start and run capacitor, fit a sine-wave filter sized for the whole bus, and check each contactor closing event against the drive's overload curve before any of it becomes permanent.
The idler buffers, it does not isolate #
A spinning idler stores kinetic energy and holds a rotating field on the bus. When a contactor closes a motor onto that bus, the idler gives up part of the first current pulse while the drive's current loop catches up, which softens the voltage dip. A heavier idler flattens the dip further — the extra inertia is why the original builder planned to upsize the motor — but the energy still flows through the drive and the single-phase supply, so inertia changes the timing of the event, not its size.
The drive also carries the idler's magnetizing current the entire time the idler spins, before a single machine is started. That continuous reactive draw is why an idler's idle current looks so large on the supply side of any converter build, as Why rotary phase converter idle current is so high explains.
Opening a contactor under load interrupts inductive current, and closing onto a motor that is still coasting is worse: the coasting motor holds terminal voltage at its own phase and frequency, and the equalizing current when the two sources meet can exceed ordinary running current by a wide margin. The idler smooths these events; it does not absorb them to any published rating.
Strip the converter hardware before the drive connects #
The converter this idea replaces carried parts the drive makes unnecessary: a 240 V to 415 V step-up transformer, a start capacitor switched by a relay between the star point and the generated leg, and run capacitors trimming that generated leg's voltage. One of those run capacitors overheated and failed after about fifteen years, which is what started the whole exercise.
All of it comes off. The transformer duplicates voltage the drive already produces. The relay and start capacitor do a job the drive's own acceleration ramp does better. And capacitors do not belong on a drive output at any rating: every PWM edge drives capacitive current into them, that current stacks onto the drive's output load, and the capacitors heat toward failure — the same incompatibility Why a capacitor-run motor needs a special VFD describes for motors. Run capacitors on a converter also run hot just balancing the generated leg, the heating mechanism behind Why more run capacitance overheats a static phase converter motor. Keep the motor, connect it star to match the drive's 380 V output, and delete everything else.
Worked example: a 4.0 kW drive, a 4 hp idler and a 2 hp mill #
The inputs, with their sources:
- Drive: 4.0 kW continuous output, 240 V single-phase input, 380 V three-phase output — the reported test unit.
- Idler: approximately 4 hp, three-phase, star-connected — the reported approximate size, which is 4 hp × 0.746 kW/hp = 2.98 kW of shaft rating. Read the real nameplate current before buying anything.
- Load: a 2 hp milling motor, 2 hp × 0.746 kW/hp = 1.49 kW, started across the bus by its own starter.
The rule: total shaft demand that can coincide must stay under the drive's continuous output rating, and every across-the-line start must sit under the drive's published short-time overload curve.
The arithmetic:
- Worst-case simultaneous demand: 2.98 kW + 1.49 kW = 4.47 kW.
- Against the drive rating: 4.47 kW ÷ 4.0 kW = 1.12, or 112 % of continuous rating.
- Margin with the idler alone: 4.0 kW − 2.98 kW = 1.02 kW, about 25 % of the rating.
- Single-phase input floor: 4,000 W ÷ 240 V = 16.7 A, before drive losses and power factor push the real feeder current higher.
The result: the reported pairing ran. The idler spins unloaded, so its true continuous draw sits well below the 2.98 kW ceiling — mostly magnetizing current — and the mill rarely runs at nameplate, so the real coincident demand stayed under 4.0 kW. That agrees with what the shop observed: the mill started better than it had through the old converter, and the lights dipped only slightly.
The decision: this exact pairing is acceptable for occasional starts of the 2 hp mill with the idler unloaded. It is not sized to run idler and mill together at full nameplate load — that is 112 % of the drive's continuous rating — and it is not sized for the larger mill planned for that shop. Before buying anything, read the idler's nameplate current, measure the mill's running and starting current with a drive-rated clamp, and pick a drive whose continuous output current exceeds idler plus coincident load, whose overload curve covers the largest across-the-line start, and which is rated for single-phase input at that output. The single-phase sizing step has its own method in Sizing a VFD for a three-phase motor on single-phase input.
Fit a sine-wave filter sized for the whole bus #
The first measurement attempt told the story: on the unfiltered drive output, an ordinary multimeter's display scrambled, because the bus carries PWM voltage steps rather than a sine wave. Everything else built for sine power sees that same waveform. A sine-wave filter is a low-pass network installed between the drive and the bus that turns the PWM output back into a genuine sine and removes the spikes at the pulse edges; such filters are bulky and add real cost, which is why they ship as options rather than standard equipment.
Here the filter is not an option. The larger mill motor in that shop has insulation that is not rated for inverter-duty voltage pulses, so it must never see an unfiltered bus, and the same bus feeds meters, contactor coils and whatever else lands on the converter output. Size the filter for total bus current — idler plus every connected load — not for the idler alone. Accept its two penalties: added voltage drop and added heat, and no increase whatsoever in the drive's current capacity. Do not improvise a filter from loose inductors and capacitors either; an arbitrary LC combination can resonate with the motor inductance or push capacitive current back into the drive at the switching edges. Use a filter whose documentation explicitly covers this drive, this carrier-frequency range and this load arrangement, and set the carrier frequency the way that documentation requires.
While the bus is still unfiltered during bench tests, current readings need the right instrument: Measuring VFD and soft starter current with the right meter covers which clamp readings mean anything on a PWM output.
The commissioning sequence, in order #
One code note before any panel comes open: NFPA 70E, 2024 edition, covers electrical safety-related work practices and requires de-energizing and verifying the absence of voltage before work on equipment that could otherwise be energized; confirm the exact requirements that apply to you with your local authority having jurisdiction and the equipment documentation.
Then, in order:
- De-energize the supply, lock it out, and verify absence of voltage at the drive's input and output terminals before touching a single conductor.
- Remove the step-up transformer, the start capacitor with its relay, and every run capacitor. Wire the idler directly to the drive output, connected to match the drive's output voltage.
- Confirm the drive is rated for single-phase input at its full output, and size the input feeder from the input-current floor worked in the example above plus whatever single-phase derating the manual states.
- Mount the sine-wave filter between drive and bus, sized for total bus current, and set the carrier frequency its documentation requires.
- Energize and start the idler with every load isolated. Record acceleration time, peak current, steady current and output frequency, and confirm the drive's fault history stays clean. If the idler spins the wrong way, de-energize, lock off and verify again before swapping any two output leads.
- Connect one machine at a time, smallest first. For each, record the contactor closing current and the running current, and compare the closing step against the drive's published overload curve — an across-the-line start can draw six to eight times the motor's full-load current, so estimate the step from the nameplate before closing anything.
- Leave any contactor-switched motor off the bus unless that curve check passes with margin. Rewire a machine to run without switching, or give a large motor its own drive.
- Test a downstream machine VFD separately from the motors: its input is a rectifier that draws pulsed current, a different load shape from an induction motor's.
- Take the finished rig out of its bench state. The reported test ran from a step ladder beside open terminals; the permanent build belongs in a closed, bonded enclosure with a proper disconnect, branch protection and guarded terminals.
Where the drive-fed idler wins and where it loses #
Against the converter it replaces, the drive-fed idler wins on every electrical point that caused trouble: all three legs come from the drive itself, so there is no generated leg to trim; starting voltage is stiffer than a capacitor converter delivers; there are no electrolytic capacitors aging toward failure; and speed control comes along if a machine ever needs it.
It loses on robustness and on cost per horsepower. The drive is a single point of failure carrying every machine at once, and a general-purpose drive tolerates casual switching far less gracefully than a rotary converter's brute bus. That trade is the actual decision: for a shop that runs a known set of machines in a fixed pattern, the drive-fed idler with a sine-wave filter is the better machine; for loads switched on and off all day by people who will never read an overload curve, a purpose-built rotary converter remains the right tool; and if only one machine matters, give that machine its own drive and skip the idler entirely.
Questions asked
Can I leave the run capacitors connected to balance the output?
No. The drive generates all three legs itself, so there is no weak leg left to trim. Capacitors on a drive output pull capacitive current at every switching edge, stack that current onto the drive's load, and heat themselves toward failure, exactly the duty that cooked the reported converter's run capacitor after about fifteen years. Disconnect the start capacitor, its relay, and every run capacitor before the drive is ever energized.
Why did the multimeter scramble on the drive output?
An unfiltered drive output is pulse-width modulated: the voltage sits at full value or near zero, switching thousands of times per second, instead of following a sine wave. A meter built for sine power cannot make sense of that, so its display scrambles. Treat a scrambled reading as confirmation that the bus needs a sine-wave filter, and take current measurements on such an output only with an instrument rated for drive waveforms.
Does the idler protect the drive when a large load switches off?
Only partly. The spinning idler limits the momentary speed and voltage dip, but the interrupted inductive current and any regenerative energy still reach the drive's output stage, and the idler carries no published surge-absorbing rating to fall back on. Watch the drive's fault history and its DC-bus reading during switch-off tests, keep each switched load step small, and treat any overvoltage fault as the drive telling you the switching exceeds what it can absorb.
Can a machine's spindle VFD run from the VFD-fed idler bus?
It was done in the reported shop, where a lathe spindle drive ran from the converter bus. Understand the difference first: a downstream drive's input is a rectifier drawing pulsed current, not an induction motor's smooth demand, and most drive manuals say nothing about being fed from another drive's output. Run it as a separate, supervised test, watch the upstream drive's fault history, and confirm the arrangement with both manufacturers' documentation before making it permanent.
How should the drive be sized when the bigger mill joins the bus?
Start from measured current, not horsepower guesses: idler nameplate current, plus the larger motor's measured starting and running current, plus anything else that can run at the same time. Choose a drive whose continuous output current exceeds that total and whose overload curve covers the largest contactor closing event, and confirm it carries a full single-phase input rating at that size. If the manufacturer lists no single-phase rating for the frame, step up until one appears.