How to model an MCC bucket for an arc flash study

Electrical safety and codes Published 7 min read By Current Intel engineering team

Short answer

Model the MCC as a bus with the bucket breaker as a branch and the outgoing run as a cable. A magnetic-only HMCP clears a load-side fault only when the arcing current exceeds its pickup, including its plus 30 percent tolerance; the line side of the bucket breaker is cleared upstream and sets the bucket's worst case.

On this page
  1. Why can't the model show every tap and conductor inside the bucket?
  2. How does the bucket appear in the one-line model?
  3. When does a magnetic-only bucket breaker actually clear the fault?
  4. How much does 115 ft of 8 AWG cut the fault current?
  5. Which point sets the arc flash label for the bucket?
  6. What checks confirm the model matches the installed bucket?
  7. Questions asked

Model the MCC as a bus, the bucket breaker as a branch, and the outgoing run as a cable, then compare the arcing current at each point with the bucket breaker's magnetic pickup. That comparison decides whether a magnetic-only 50 A breaker clears a load-side fault or whether clearing falls to the MCC main. The line side of the bucket breaker is the worst case for that bucket, because the breaker cannot see a fault ahead of its own contacts. The method below fits any low-voltage MCC bucket, and the worked example uses a 600 A bus, a 50 A HMCP breaker and a 115 ft run of 8 AWG.

Why can't the model show every tap and conductor inside the bucket? #

IEEE 1584-2018, the guide for performing arc-flash hazard calculations, fitted its equations to a test database of more than 1800 arcs in cells with fixed electrode configurations and enclosure sizes, so extra detail inside a bucket adds precision the model cannot support. The working group tested MCCs with a smaller box than switchgear, and the accepted practice is to enter the enclosure dimensions of the smallest bucket in the arc flash equations.

A bucket holding mixed conductor sizes, a control transformer, an overload relay and a drive matches none of the tested cells. Drawing each of those components does not move the result closer to reality; it only moves it. Model the electrical path that carries fault current, keep the enclosure size and electrode configuration the software lists for that equipment class, and hold them fixed for every identical bucket.

Accept one limit on the output: an arc that sustains inside a congested enclosure can outlast the calculated clearing time, because the arc location and gap are unknowable in advance. Treat the calculated value as the study's documented basis for the label, not a prediction of a specific internal event.

How does the bucket appear in the one-line model? #

Model the MCC as a bus, the bucket breaker as a branch, and the outgoing run as a cable with its size, length and conduit method, so the software calculates the impedance from its own conductor tables. Gather these inputs before opening the study file:

  • The MCC bus voltage and rating, for example 480 V and 600 A.
  • The bucket breaker's frame and type, for example a 50 A magnetic-only motor circuit protector.
  • The magnetic dial setting read from the installed breaker, not the factory default.
  • The outgoing conductor: size, material, length and conduit, for example 8 AWG copper in PVC.
  • The upstream device that protects the bus: the MCC main or feeder breaker with its settings, or the fuse class and rating.

Read the dial setting with the bucket de-energized: apply lockout, test for absence of voltage and follow the plant's electrical safety program before opening the door or racking the unit out. Enter the run as a cable in the software rather than a hand-estimated impedance, and create calculation points at the bus, the line side of the bucket breaker, the load side of the breaker, and the far end of the run if a label belongs there.

When does a magnetic-only bucket breaker actually clear the fault? #

A magnetic-only breaker clears only when the arcing current exceeds its instantaneous pickup, and the manufacturer's time-current curve gives that pickup a tolerance of minus 20 percent to plus 30 percent of the dial setting. That tolerance drives the study decision: below 0.8 times the setting the breaker is guaranteed not to trip, above 1.3 times the setting it is guaranteed to trip, and inside the band the outcome is indeterminate, so the study treats the breaker as non-clearing there.

When it does operate, the magnetic element clears in roughly one to two cycles on the curve, and the incident energy stays low. When it does not, clearing passes to the MCC main or the upstream feeder device, which may operate in its short-time or long-time region and take seconds. Which device clears the fault sets the duration, the same selection problem covered in which breaker sets MCC arc flash duration. The starter's overload relay never enters this comparison; its curve sits in the seconds-to-minutes region and it cannot interrupt fault current.

How much does 115 ft of 8 AWG cut the fault current? #

In this worked example, 115 ft of 8 AWG copper cuts the bolted fault from 22 kA at the MCC bus to about 3.0 kA at the far end, well above the 650 A trip threshold of a 500 A dial setting. The example inputs are: 480 V three-phase, a bolted fault of 22 kA at the bus, 8 AWG copper in PVC conduit, and the impedance values of 0.78 ohms and 0.052 ohms per 1000 ft (resistance and reactance) that NFPA 70, the National Electrical Code, 2023 edition, lists in Chapter 9, Table 9.

The arithmetic:

  • Cable resistance: 0.78 ohms per 1000 ft times 0.115 = 0.090 ohm.
  • Cable reactance: 0.052 ohms per 1000 ft times 0.115 = 0.006 ohm.
  • Source impedance behind the bus: 480 V divided by (1.732 times 22,000 A) = 0.0126 ohm, treated as reactance.
  • Total impedance: square root of (0.090 squared plus (0.0126 plus 0.006) squared) = 0.092 ohm.
  • Far-end bolted fault: 480 V divided by (1.732 times 0.092 ohm) = 3,000 A, about 3.0 kA.

The arcing current at the far end sits below that bolted value, and even if it falls to half of it, 1.5 kA, it stays far above the 650 A threshold that guarantees the magnetic trip. So in this example the bucket breaker clears the load side in its instantaneous region, and the load-side incident energy is small. The result is an estimate to be checked against the governing code edition and the equipment documentation, with the dial setting field-verified as installed.

Which point sets the arc flash label for the bucket? #

The line side of the bucket breaker sets the bucket's worst case, because the breaker cannot clear a fault ahead of its own contacts and clearing falls to the MCC main or the upstream feeder device. Read that device's time-current curve at the arcing current for the line-side point: an arcing current that lands in the long-time region is the usual cause of an unexpectedly high energy value, and no bucket-level device can improve it.

Run the calculation at the reduced arcing current the standard requires as well as the nominal one, the case explained in why arc flash software reports 85% of the arcing current. Apply the standard's 2 s cap on exposure only where its escape conditions hold at that location; it is a policy input, not a trip time.

On labeling, commit to one method: calculate each bucket at its worst-case point and label it there, unless the owner's documented policy calls for a single label for the whole MCC, in which case the worst bucket sets that label. NFPA 70E, 2024 edition, requires an arc flash label on equipment that is likely to be examined or worked on energized; it does not dictate buckets versus one label, so record the choice in the study report and apply it uniformly. Confirm the requirement with the local authority having jurisdiction.

What checks confirm the model matches the installed bucket? #

Five checks catch nearly every bucket-model error: the dial setting against the calculated arcing current, the cable-length sensitivity, the upstream curve at the arcing current, method consistency across identical buckets, and the interrupting ratings behind the fault current.

  • Margin check. Confirm the load-side arcing current exceeds 1.3 times the installed dial setting. If it lands inside the tolerance band, model the breaker as non-clearing and let the upstream device set the time.
  • Length sensitivity. Rerun the run length 30 percent shorter and 30 percent longer. If the clearing device changes between runs, report the worst case on the label.
  • Upstream coordination. Read the upstream device's curve at the calculated arcing current and confirm the time the label carries. A time pulled from the wrong device is a common error.
  • Consistency. Identical buckets on one bus must produce identical results; a difference between them points to a data error, not a real distinction.
  • Ratings. Check that the bucket breaker's interrupting rating and the MCC's short-circuit rating stand up to the available fault current, the subject of MCC short circuit rating vs bucket breaker ratings.

Finish with a walk-down of the MCC against the model. The three errors found most often are a wrong breaker setting, a wrong upstream device and a wrong cable length, and each one changes the label.

Questions asked

Does the starter's overload relay help clear an arcing fault in the bucket?

No. An overload relay's inverse curve sits in the seconds-to-minutes region, and its contacts are not rated to interrupt fault current, so it never appears as the clearing device in the study. Only an instantaneous element, in the bucket breaker or upstream, clears an arcing fault.

What working distance belongs in a bucket calculation?

IEEE 1584-2018 pairs its low-voltage MCC enclosure class with a working distance of 455 mm (18 in). Use the value the software's equipment table assigns to that class, and change it only if a documented task at your plant puts the worker's face and torso closer to the arc.

Can a series fuse in the bucket take over as the clearing device?

Only when the fuse is actually in series between the fault and the source, and only above the fuse's current-limiting threshold. Below that threshold it clears on its total-clearance curve, far more slowly, so a small fuse in the bucket does not automatically shorten the clearing time the model uses.

Should identical buckets receive identical arc flash results?

Yes. Buckets with the same frame, dial setting, conductor and run length on the same bus get the same incident energy and the same label. A difference between them almost always traces to a wrong setting, cable length or upstream device in the model, and mixing label methods on one MCC is a documentation error.

Keep reading

  • Explainer

    Segmenting a long busway for arc flash studies

    Segment a tapped busway into one model bus per tap with the published section impedance between taps. Bolted fault current drops along the run, and the lower arcing current can push an upstream breaker into a slower clearing band, raising incident energy at interior taps an endpoint-only model never checks. Sample head end, middle and far end first, then label the whole run at the highest calculated value.

    Electrical safety and codes

  • How-to

    Which breaker sets MCC arc flash duration

    Use the MCC main breaker's clearing time only for faults on its load side. In an MCC with no documented arc-resistant rating — including early-1980s lineups — treat arc propagation ahead of the main as credible and take duration from the upstream 480 V switchgear breaker: at 20 cycles instead of 6, incident energy multiplies by 3.33. Where construction leaves the path uncertain, calculate both cases and label the higher result.

    Electrical safety and codes

  • Troubleshooting

    Checking a delta high leg arc flash calculation's numbers

    The 9.127 kA at the panelboard checks out against the 11.33 kA infinite-source terminal limit once utility impedance is counted. The 73 cal/cm² hinges on clearing time: the referred bolted current clears the 600 A primary breaker in 0.033 s, but IEEE 1584 sets device time from the arcing current, which falls below the 3,600 A pickup into the thermal band — so the label is credible until the study file shows otherwise.

    Electrical safety and codes