How-to
Making a 5 HP motor a self-starting rotary phase converter
Short answer
Connect the idler's nine leads for low voltage (1-7, 2-8, 3-9, with 4-5-6 tied together and insulated), feed single-phase power to two bundles, and add a run capacitor of about 33 µF per HP rated 1.56 times the line voltage to the third leg: the converter then starts itself and runs a 1.5 HP lathe motor. The 460 V controls must be reconnected or fed through a step-up transformer first.

On this page
- Group the nine leads for low voltage
- Feed the supply and make the idler self-start
- Worked example: sizing the run capacitor for a 5 HP idler on a 240 V line
- Pick a starting method when the run capacitor is not enough
- Convert the 460 V lathe controls
- Compare the idler's capacity
- Run the end-to-end verification
- Questions asked
You can make that 5 HP nine-lead motor a self-starting rotary phase converter. Join leads 1-7, 2-8 and 3-9, tie 4, 5 and 6 together and insulate the joint, feed your single-phase line to the 1-7 and 3-9 bundles, and connect a run capacitor of about 33 µF per horsepower from one supply line to the 2-8 bundle — 165 µF for a 5 HP motor, rated at least 1.56 times the line-to-line voltage. The generated third leg will then run the 1.5 HP lathe motor. The 460 V lathe controls must be reconnected or fed through a transformer before you connect them. The procedure below goes in stages, and each stage ends with a meter check that must pass before you move to the next.
Group the nine leads for low voltage #
Open the motor terminal box only with the motor isolated, locked out and proven dead with a voltage tester rated for that system; the same rule applies to every junction you open below.
- Read the connection diagram on the motor nameplate and confirm the wire markers against it before trusting any lead number.
- Join leads 1 and 7, 2 and 8, 3 and 9. These three bundles are the low-voltage (parallel-wye) connection, which puts the windings across the full 220/230/240 V line.
- Tie leads 4, 5 and 6 to each other and to nothing else; insulate that joint. It is the wye point.
- With the motor still isolated, measure each winding pair (1-4, 2-5, 3-6). Pass condition: low, near-equal resistance on all three, no continuity from any lead to the frame, and the 4-5-6 joint open-circuit to every other lead group.
Feed the supply and make the idler self-start #
- Mount a two-pole breaker or disconnect within reach of the idler so you can kill it from where you stand. A two-pole 40 A breaker covers the idler's trial runs; confirm the final protection against the motor's nameplate current, the National Electrical Code (NFPA 70, 2023 edition, which governs motor branch-circuit conductors and protection) and your local amendments with the authority having jurisdiction.
- Land the single-phase line on the bundle containing leads 1 and 7 and on the bundle containing leads 3 and 9. The bundle with leads 2 and 8 receives no supply; it becomes the generated third leg.
- Expect no start yet: two energized legs on a three-phase motor give a pulsating field with no torque at standstill, so the motor hums. Spun by rope or by hand, it keeps running and the idle winding picks up an induced voltage. That is the rope-start version, the bottom rung of converter designs.
- To make it self-starting, connect a run capacitor from one single-phase line, not both, to the 2-8 bundle. Size it at about 33 µF per horsepower of motor nameplate rating, rated at least 1.56 times the line-to-line voltage. Build the bank from AC motor-run capacitors in parallel; parallel capacitance adds directly.
- Discharge every capacitor through a resistor before you handle it, every time.
Check: with the capacitor connected, close the breaker with the shaft at rest. Pass condition: the idler accelerates on its own and holds speed, and the generated leg now reads close to the two supply legs.
Worked example: sizing the run capacitor for a 5 HP idler on a 240 V line #
Inputs:
- Motor nameplate rating: 5 HP, from the idler you already have.
- Capacitance rule: 33 µF per horsepower of nameplate rating, the published self-starting converter rule described by Habermann in IEEE Transactions.
- Line voltage: 240 V line-to-line, taken from your 220/230/240 V service for the worst case.
- Voltage-rating factor: 1.56 times the line-to-line voltage, from the same rule.
The rule in words: multiply the microfarads-per-horsepower figure by the nameplate horsepower, and buy capacitors whose AC rating is at least 1.56 times the line-to-line voltage.
Arithmetic:
- Capacitance: 33 µF/HP × 5 HP = 165 µF.
- Minimum voltage rating: 1.56 × 240 V = 374.4 V AC.
- On a 230 V line the minimum is 1.56 × 230 V = 358.8 V AC.
Result: 165 µF of run capacitance, rated 374.4 V AC minimum on a 240 V line. A 370 V AC motor-run capacitor is acceptable in practice; 440 V AC units give the full margin. Three 55 µF units in parallel give exactly the required total (55 + 55 + 55 = 165 µF).
Decision: connect the bank and close the breaker with the shaft at rest. If the idler accelerates and settles at speed, stop here. If it only hums, keep the run bank and add one of the starting methods below.
Pick a starting method when the run capacitor is not enough #
| Method | What it needs | Trade-off |
|---|---|---|
| Rope or foot spin | A pulley on the idler shaft | Free, but impractical for repeated starts |
| Pony motor | A small single-phase motor belted to the idler | Extra motor and belt; spins the idler up before the breaker closes |
| Start capacitors | A second contactor to switch them in and out, plus a timer relay to drop them out | Automatic starts; the start capacitors must leave the circuit at speed, because continuous duty is outside their rating |
Set the timer relay so the start capacitors drop out once the idler is up to speed; read the duty limit on the capacitor datasheet before you set it. A drive can also spin the idler up and steady the third leg, and feeding a rotary phase converter idler from a VFD covers what that setup requires.
Check: cycle the breaker several times. Pass condition: the idler starts on every attempt without hand assistance, and the start capacitors are out of the circuit once the timer relay times out.
Convert the 460 V lathe controls #
- Reconnect the 1.5 HP lathe motor for its low-voltage connection if it is dual-voltage; the nameplate diagram gives the lead pairing.
- Find the machine's control transformer on the schematic and check whether its primary has a 220-240 V tap. If it does not, replace it with a transformer rated for the converter's output, or supply the whole machine through a step-up transformer.
- Check every contactor coil and other device rated for the higher voltage against what actually feeds it after step 2.
- Size the lathe branch fuses from the lathe motor's nameplate current and the machine's electrical documentation. The idler's breaker protects the idler, not the lathe branch.
Check: before the motor leads are landed, apply the converter output to the control transformer alone. Pass condition: the secondary reads the voltage the contactor coils and control devices are rated for.
Compare the idler's capacity #
The idler runs the same whether it is wound wye or delta, but the output capacity differs:
| Idler winding | Capacity fraction | Output for this build |
|---|---|---|
| Wye | 2/3 of nameplate rating | 5 HP × 2/3 ≈ 3.3 HP, comfortably above the 1.5 HP load |
| Delta | 1/3 of nameplate rating | 5 HP × 1/3 ≈ 1.7 HP, a thin margin against the lathe motor's inrush |
Both cover the load; a delta-wound idler has little left for a hard across-the-line start. A balanced converter design, with capacitance split across both supply lines, holds the leg voltages closer but will not self-start; why a rotary phase converter needs three capacitor banks explains those banks. The self-starting arrangement here accepts some imbalance in exchange for a direct single-phase connection.
Run the end-to-end verification #
- With the lathe disconnected, close the breaker. Pass condition: the idler starts and settles at steady speed with no hum or buzz. Its no-load current will read high; that is normal, and why rotary phase converter idle current is so high explains the number you will see.
- Measure the three leg voltages at the converter output. Pass condition: all three close to one another and near the single-phase supply voltage.
- Energize the lathe control circuit. Pass condition: the contactor coils pull in cleanly and the control secondary reads its rated value.
- Start the lathe motor with the idler already running. Pass condition: it accelerates fully, the generated leg dips and then recovers, and nothing drops out.
- Repeat the start several times in a row. Pass condition: the idler self-starts every cycle and the three legs return to the same readings.
Questions asked
Can I keep the lathe at high voltage and transform the converter output instead of rewiring the machine?
Yes. One three-phase step-up transformer fed from the converter output lets the motor and controls stay exactly as wired. Size it for the lathe motor's locked-rotor current rather than its running power, because the voltage dip during an across-the-line start is what limits how small that transformer can be.
Would a VFD be simpler than a converter for one lathe?
For a single motor, usually. A drive rated for single-phase input and for the lathe motor removes the idler, the capacitor bank and the control conversion in one step. The converter earns its keep when two or more three-phase machines run from one self-built source.
Why must the capacitor bank use motor-run capacitors?
Because they are built for continuous AC duty. Start capacitors are electrolytic, intermittent-duty parts meant to be in circuit for a second or two; left connected, they overheat and can burst. Run capacitors, typically oil-filled polypropylene units, sit in circuit the whole time the idler runs.
Does the converter need balancing before the lathe runs?
Not for the first start. Run the lathe and measure the three legs under load. If the generated leg sits far below the two supply legs, part of the run bank can move to the other supply line for better balance, but that arrangement gives up self-starting, so pair it with one of the starting methods.
