Explainer
Medium voltage transfer switch for a 22 kV generator backup
Short answer
The device you need is called a medium voltage transfer switch: IEC 60038 places 22 kV in the medium voltage band, and the switch that separates generator from utility must carry that rating and close only after the utility side is open (break-before-make). An LV automatic transfer switch on the generator's 415 V output backfeeds the utility feeder. Below roughly 3 MVA, stepping down to 415 V, transferring at LV and stepping back up is the alternative worth pricing; above it, MV switchgear wins.

On this page
- Why the network voltage is filed under medium voltage
- Where the two sources meet decides what does the switching
- Four fixes that fail on this layout
- The transfer scheme that separates the two sources
- Line current per 1 MVA at the medium voltage bus and at 415 V
- Quantities to read before you specify
- Commissioning checks that prove the separation
- Questions asked
The switch you are hunting for exists, but it is filed under a different name: 22 kV sits inside the medium voltage band, so the product you want is sold as a medium voltage transfer switch, not a high voltage one. The generators and the utility meet on the same bus at that voltage, so the device separating them must carry that rating and be interlocked break-before-make, so the generator can never close onto a network still energized from the mains. An automatic transfer switch on the generator's low voltage output cannot do this job: it leaves the medium voltage network tied to the utility and backfeeds the grid. For installed generation below roughly 3 MVA there is a second route — step down, transfer at low voltage, step back up — paid for with two full-load transformers in series.
Why the network voltage is filed under medium voltage #
IEC 60038 (2009 edition) sets out standard system voltage classes and places systems above 1 kV up to 35 kV in the medium voltage band, and 22 kV lands well inside it. In North America, NFPA 70 (the National Electrical Code, 2023 edition) gathers installations above 1000 V in Article 490 and optional standby power systems in Article 702. Classification and connection requirements differ by country, edition and local amendment, so confirm both with the authority having jurisdiction and the equipment documentation before ordering anything.
That naming is why the search came up empty. A high voltage automatic transfer switch is not a product class for this duty; medium voltage automatic transfer switch assemblies are a standard catalogue item. ASCO's 7000 Series medium voltage transfer switches, ABB's Zenith medium voltage line and Eaton's medium voltage circuit breaker transfer switch assemblies all cover source transfer at this voltage class, and a published medium voltage ATS range spans 40 A to 4000 A of continuous current. Choose among them on ratings and on the local service support you can actually get.
Where the two sources meet decides what does the switching #
The layout puts around thirty pole- or ground-mounted medium voltage/415 V distribution transformers across the property, with the 415 V generators sitting at the network head. Each machine reaches the bus only through its own step-up transformer, and the utility lands on that same bus. The point where the two sources can energize the same conductor is that bus, and it fixes where the switching must happen.
An automatic transfer switch on the generator side switches only between the machine and its own step-up transformer. The medium voltage winding of that transformer stays tied to the farm bus, and the farm bus stays tied to the utility. When the mains fail, the generator therefore energizes the utility feeder through the step-up transformer and all the distribution transformers: backfeed onto a line a crew has every reason to treat as dead. Before anyone opens that step-up transformer's MV compartment or works on the pole gear, the farm side must be isolated at the transfer switch and the absence of voltage verified with an MV-rated detector — an open low voltage switch is not proof that a line is dead.
Four fixes that fail on this layout #
Four fixes come up first for a spread-out network like this, and each leaves a gap.
- Searching for a high voltage automatic transfer switch. The band name is wrong: the same equipment is catalogued as a medium voltage transfer switch, and under that name the products appear.
- An automatic transfer switch on the generator output. It transfers the machine against its own step-up transformer alone, and the backfeed path described above stays live.
- An automatic transfer switch at each of the distribution transformers. It isolates individual low voltage boards but never isolates the medium voltage network, and the generators sit at the network head, not at the boards.
- A manual isolator with no interlock. It works only while every operator follows the sequence every time, gives no automatic transfer, and nothing stops the two sources being closed together.
The transfer scheme that separates the two sources #
Specify the medium voltage device as a dedicated medium voltage automatic transfer switch, or as a medium voltage switchgear line-up with two interlocked positions — one for the utility incoming circuit, one for the generator's step-up transformer — driven by an automatic transfer controller. The interlock is break-before-make, also called open transition: both sources are never connected at the same time, and the dead time between them lets the residual voltage on the farm network decay before the generator closes in. Closing a generator onto a network still energized from the utility drives the phase-angle difference between the two sources across the generator and its step-up transformer as a fault-level inrush, and the interlock exists to make that physically impossible. A closed-transition scheme that deliberately parallels the two sources for a moment is a different design and needs the utility's written agreement before it is built.
Sequence of operation:
- Get the utility's connection requirements and the prospective fault level at the point of connection, and confirm in writing that a standby scheme with no export is allowed.
- Fit loss-of-mains detection on the utility side: undervoltage and phase-loss relays, the ANSI device functions 27 and 47, with a time delay long enough to ride through transient dips before commanding a transfer.
- On loss of mains: the utility switch opens, the dead time elapses, the generator starts and reaches stable voltage and frequency, then the generator switch closes.
- Pick up load in stages: energize the step-up transformer with the generator's excitation ramped if the controller supports it, then bring the distribution transformers back in stages so their magnetizing inrush does not stack on the generator.
- Return to mains: hold stable utility voltage for a set time, open the generator switch, then close the utility switch — the same break-before-make rule applies in both directions.
Line current per 1 MVA at the medium voltage bus and at 415 V #
The inputs, and where each comes from:
- Block size: 1 MVA (1,000,000 VA) — an illustrative block chosen so the two voltages can be compared; the farm's own generator nameplates set the real number.
- 22,000 V line-to-line — the farm network voltage from the case (the 22 kV system).
- 415 V line-to-line — the generator output voltage from the case.
- Balanced three-phase load.
The rule: for a balanced three-phase load, line current equals apparent power divided by the square root of three times the line-to-line voltage, I = S / (√3 × V), with S in volt-amperes and V in volts. This is the standard three-phase power relationship, not a table value, so treat the results as estimates and check them against the nameplates and the equipment documentation.
The arithmetic:
- At the medium voltage bus: I = 1,000,000 VA / (1.732 × 22,000 V) = 1,000,000 VA / 38,104 V ≈ 26.2 A
- At 415 V: I = 1,000,000 VA / (1.732 × 415 V) = 1,000,000 VA / 718.8 V ≈ 1391 A
- Ratio: 1391 A / 26.2 A ≈ 53, which is simply the voltage ratio 22,000 V / 415 V
Result: on the medium voltage side, 1 MVA of transfer duty asks the switch for 26.2 A; at 415 V the same block asks for 1391 A. Medium voltage gear is small in conductor terms, and its cost sits in insulation and fault-interrupting capability instead. Scaled to 3 MVA the two sides read 3 × 26.2 A ≈ 79 A on the medium voltage side against 3 × 1391 A ≈ 4173 A at 415 V, which is around the top of standard low voltage power-breaker frames.
Decision: below roughly 3 MVA of installed generation, the step-down, low-voltage-transfer, step-up detour is worth pricing against a medium voltage transfer switch. Above that, the low voltage transfer current and the two full-load transformers tip the balance clearly to medium voltage switchgear, where this whole case needs only tens of amperes of continuous rating. The detour also puts two transformers in series with the farm load, and their impedances add; the drop through the pair is worked the same way as in calculating voltage drop through step-up and step-down transformers.
Quantities to read before you specify #
- Generator nameplate: kVA, kW and power factor. The machine must carry the connected farm load plus magnetizing inrush and motor starting; collapse during transformer energization shows up as voltage and frequency sag followed by an undervoltage trip, which is a sizing problem rather than a switching problem.
- Rated maximum voltage of the switch: above the system's highest operating voltage, read from the switchgear rating table rather than from nominal.
- Short-circuit withstand and interrupting rating: above the prospective fault level at the switch location, taken from the utility's fault-level statement. The study takes the generator's rated MVA, not its operating load, the way the IEC 60909 short-circuit calculation guide sets out, and it must cover the bus with each source closed in turn — the generator-side arc-flash modeling problem described in where no breaker clears the arc on a generator-side bus.
- Step-up transformer vector group and impedance, from the nameplate and test report: the vector group must match the network if anything ever runs in parallel, and the impedance limits the generator's contribution to the fault level. A distribution-class transformer working as the generator's step-up runs against its usual direction, and why dry-type transformers usually step down and when they step up covers what that changes.
- Combined magnetizing inrush of the step-up transformer and the distribution transformers: the generator and its protection must tolerate it on energization; read it from the transformer manufacturer's inrush data and the generator's transient reactance on its datasheet.
- Transfer time and dead time: set to the load's ride-through and long enough for residual voltage to decay; both live in the transfer controller and are confirmed by the commissioning tests below.
Commissioning checks that prove the separation #
- Generator running, utility switch open: measure the voltage on the utility side of that switch with an MV-rated voltage detector or the switchgear's voltage-presence indicator. It must read zero before anyone treats the feeder as isolated.
- With the interlock engaged, attempt to close both switches, manually and from the controller. Both attempts must be blocked.
- Simulate loss of mains at the undervoltage relay and record the time from detection to generator switch closing; compare it with the ride-through of the loads that matter.
- Check phase rotation and phase angle across the open contacts before the first live transfer.
- Run a load test while recording generator voltage and frequency at each transformer energization stage, and compare the dips against the generator datasheet limits.
The decision for this farm in one line: the generators and the utility meet on the medium voltage bus, so the standby scheme needs a medium voltage, break-before-make transfer switch at the intake — unless the installed generation stays below roughly 3 MVA, where stepping down, transferring at low voltage and stepping back up lets standard low voltage gear do the switching at the price of two full-load transformers carrying the whole farm load.
Questions asked
What do the ANSI device numbers 27 and 47 detect?
They are two of the device function numbers defined in IEEE C37.2. Number 27 is the undervoltage relay: it picks up when the utility voltage collapses or falls below its setpoint. Number 47 is the phase-sequence voltage relay: it detects phase reversal, loss of a phase or severe imbalance. A transfer controller applies both with a definite time delay, so a transient dip or a nearby fault clearing does not command a transfer.
Can the generator and the utility ever be closed together?
Only in a closed-transition design, which is a different scheme from the break-before-make layout described above. It needs a sync-check function confirming that voltage magnitude, frequency and phase angle agree before the second source closes, vector groups matched on both transformers, and the utility's written agreement, because the two sources parallel for a short time. Standby-only schemes almost always use open transition and keep the sources permanently separated.
Does the dead time between sources have a fixed setting?
It is set from the site, not from a catalogue table. The controller holds both switches open long enough for the residual voltage on the network to decay, so the right number depends on the transformer and motor load the farm holds. Record how long the low voltage boards take to fall below the generator's closing threshold after the utility switch opens, then set the dead time above that measurement with margin.
What must be rechecked if the utility upgrades its network?
The prospective fault level at the point of connection. A utility that installs larger transformers or shortens its feeders raises the fault current available at the intake, and switchgear whose interrupting rating passed at installation can end up below the new level. Ask the utility for an updated fault-level statement after any known network change, and after any modification to the farm's own step-up transformer.