Modeling mixed fuse types in a fused switch for arc flash
Short answer
Model one case, not three. Record the fuse type in each pole, lay the manufacturer curves over the arcing-current range the study evaluates, and represent the switch with the slowest curve in that range; then replace the mixed fuses with one matched set and rerun. If a fuse cannot be identified, flag it and use an approved generic worst-case fuse entry as a documented assumption.

On this page
- Why equal ampere ratings do not settle the model
- The two arcing currents the comparison must cover
- The procedure
- When the curves cross inside the window
- When a fuse cannot be identified
- Worked example: three types in one 480 V feeder switch
- Replace the set, rerun, and report
- The decision for each case
- Questions asked
Model one case, not three. When the poles of a fused switch hold different fuse types, the right representation is the fuse curve that is slowest anywhere across the arcing-current range the study evaluates — a single bounding curve, not a run per phase assignment. Read every installed curve at both arcing currents the calculation requires, put the slowest one into the model, and keep the comparison in the study file. Then correct the installation: recommend one matched set of a single fuse type and ampere rating, and rerun the affected buses with the verified curve once that work is done.
Why equal ampere ratings do not settle the model #
The ampere rating pins a fuse near its minimum-melt region. Everything above that on the time-current curve comes from the fuse type and its internal design, so curves of different types cross: one type opens in milliseconds at tens of kiloamperes yet takes tenths of a second a few kiloamperes lower, while another does the reverse through the overload region. The governing fuse changes with the current you evaluate, and a switch labelled 400 A says nothing about which of three curves applies. The model element has to be the documented curve of the exact type in the pole. The same slowest-branch envelope logic used in coordination studies is described in time-current curves need the slowest branch envelope. Physically the arc is fed until the last pole's fuse opens, which is one more reason the slowest curve is the honest representative.
The two arcing currents the comparison must cover #
IEEE 1584-2018, the IEEE Guide for Performing Arc-Flash Hazard Calculations, does not treat arcing current as a single number. The arc current varies during one event — the standard estimates it through a cycle-by-cycle window — and it requires the incident energy at each bus to be calculated twice: at the calculated arcing current and at a reduced arcing current that covers the random variation. The reduction uses a variation factor of 0.5 below 1000 V open-circuit voltage and 0.1 at 1000 V and above, and the calculated variation comes out noticeably larger at 480 V than at 600 V or 2700 V. For this task the two currents define the comparison window: every installed curve is read from the reduced arcing current up to the calculated one, and the model run itself carries both energy calculations.
NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, requires the arc flash risk assessment these results feed; confirm the method against the owner's study specification and the authority having jurisdiction. Software still built to the 2002 edition applies a fixed reduced case instead, which is covered in why arc flash software reports 85% of the arcing current.
The procedure #
One field pass, one curve overlay, one model run:
- Isolate, then identify. De-energize, lock out and test for absence of voltage before opening the switch; then record each pole — fuse type or class, ampere rating, voltage rating, manufacturer — and photograph the markings. Do not assume the three poles match; a mixed set is exactly what you are hunting.
- Pull the curves for what is installed. Manufacturer time-current curves for those exact fuses, not a typical curve for the class. A missing curve goes to the unidentified-fuse step below.
- Take the two currents from the study. At the switch's bus: the calculated arcing current and the reduced arcing current from the variation calculation.
- Overlay the curves across the window. Plot every installed curve on one log-log grid between the two currents; the mechanics of reading several curves on one sheet are covered in reading time-current characteristic curves for protective devices.
- Find the bounding curve. A fuse curve gives its longest clearing time at the lowest current, so read each curve at the reduced arcing current first. The longest time there is the candidate; it is the bounding curve only if no other curve crosses above it anywhere up to the calculated arcing current.
- Model the switch once. Use the bounding curve for the protective device, run the single case, and file the overlay with the study notes.
- Raise the corrective action. Recommend replacing the mixed fuses with one matched set, then rerun as described at the end.
When the curves cross inside the window #
If one curve is slowest at the reduced arcing current and a different one is slowest at the calculated arcing current, no single curve bounds the whole window. Model both candidates, one run each, and report the higher incident energy of the two complete runs — two documented runs instead of three, each already carrying both of the standard's energy calculations. Do not average the curves, invent a composite, or choose by class reputation; the plotted read decides.
When a fuse cannot be identified #
Record the gap explicitly: switch, pole, what is unknown. If the study library holds an approved generic non-current-limiting worst-case fuse entry, use it for that switch as a documented conservative assumption — a stand-in for missing data, not an identification, and the report should say so in those words. The assumption retires itself once a verified matched set is in place, so the replacement belongs on the corrective-action list either way.
Worked example: three types in one 480 V feeder switch #
Hypothetical example with every input stated; in a real study the currents come from the fault study and the times from the manufacturers' curve sheets. A 480 V, 60 Hz three-phase switchboard feeds a 400 A fused bolted-pressure contact switch whose poles hold three different 400 A fuse types of the same voltage class — call them A, B and C. The study at that bus gives a bolted three-phase fault current of 21 kA, a calculated arcing current of 9.2 kA — 9.2 ÷ 21 ≈ 0.44, consistent with the familiar rule of thumb that arcing current lands near half the bolted value at this voltage — and a reduced arcing current of 6.1 kA. The comparison window therefore runs from 6.1 kA to 9.2 kA.
Reading the three curves inside that window:
| Current | Type A | Type B | Type C |
|---|---|---|---|
| 6.1 kA (reduced) | 0.02 s | 0.35 s | 0.06 s |
| 9.2 kA (calculated) | 0.01 s | 0.10 s | 0.02 s |
Type B is slowest at both edges of the window and nothing crosses above it in between, so B is the bounding curve and the model is one run with B's curve. The choice is not cosmetic: at the reduced current B clears in 0.35 s against 0.02 s for A, and 0.35 ÷ 0.02 ≈ 17.5, so a model built on A would understate the clearing time — and with it the calculated energy at that current — roughly seventeenfold.
Replace the set, rerun, and report #
Corrective action: replace all three fuses with one matched set of a single type and ampere rating, chosen by comparing candidate curves against the upstream and downstream devices — that selection is covered in selecting replacement fuses by time-current curves. After the work, verify the markings in every pole, update the model with the verified curve and rerun the affected buses; the rerun is what belongs on the updated label, and the bounding-curve result stands until the replacement is done. If the chosen set is a faster type the energy can drop sharply; how much a fuse class alone can cut the calculated energy is a separate question, covered in when a Class L fuse actually cuts arc flash energy.
The decision for each case #
| What the switch holds | Model | Runs |
|---|---|---|
| One curve slowest across the whole window | That bounding curve | 1 |
| Two curves trading places inside the window | Both candidates, keep the higher energy | 2 |
| A fuse type that cannot be identified | Generic worst-case entry, flagged as an assumption | 1 |
| A verified matched set after replacement | The verified curve, rerun | 1 |
In every case the study file names the installed types, the comparison window and the curve that was used.
Questions asked
Do I have to model three cases, one for each fuse type?
No. Comparing the three curves at the two arcing currents first usually shows one type slowest across the whole range, and that bounding curve covers every phase assignment in a single run. If you prefer the three-case approach, taking the highest incident energy of the three gives the same conservative answer, but it leaves three models to build, check and defend instead of one.
Does the bolted pressure contact design of the switch change the model?
No. The study element is the fuse curve; the contact system only determines that the poles are fused and how the switch is operated. Model the protective device with the bounding fuse curve and keep the switch itself as the isolation point. What the study must capture is which fuse interrupts the arcing fault, and that comes from the curve comparison, not the switching mechanism.
The mixed fuses were probably installed after an old fault. Can the survivors stay?
Replace all three as a matched set even when the survivors look undamaged. A fault strong enough to open one fuse can stretch or notch the elements of its neighbours without any visible sign, and a stressed element no longer follows its published curve, so both the protection and the study rest on an unknown. Verify type and ampere rating in every pole after the replacement and rerun.
Does the current-limiting range ever make the choice irrelevant?
Almost. Where both evaluation currents fall inside the current-limiting range of every installed type, each fuse clears in less than half a cycle and the published curves commonly stop at 0.01 s, so the type choice barely moves the result. The mismatch matters when the arcing current sits on the slower, steeper part of the curves, which is the usual situation for arcing currents of a few kiloamperes on a low-voltage feeder.