Current IntelPower LibraryShop main store

How-to

Retapping a 380 V machine transformer for a 240 V supply

Power distribution and transformers Published 7 min read

Short answer

On a 240 V supply, the 208 V primary tap puts the 380 V secondary at 438.5 V, 9.6% over a 400 V machine. Re-tap the primary to the 230 V connection for 396.5 V, and land the fourth wire on protective earth: a three-phase delta feed has no neutral.

On this page
  1. Read the supply and both nameplates first
  2. Why the as-shipped tap fails on your supply
  3. What the 230 V tap gives
  4. The fourth wire is protective earth
  5. Size the feeder from the machine, not the tap you came from
  6. Re-tap the primary and energize in steps
  7. When to stop and escalate
  8. Questions asked

Move the primary links to the 230 V connection and land the fourth wire on protective earth. The transformer as shipped is strapped 208 V in, 380 V out; fed from your 240 V supply that tap drives the secondary to 438.5 V, 9.6% over the machine's 400 V rating. On the 230 V tap the same supply gives 396.5 V, and the machine runs where it belongs. A three-phase delta supply has no neutral, so the fourth conductor at the three-pole breaker is the protective earth, not a current-carrying conductor.

Read the supply and both nameplates first #

Three records before any lug moves:

  • Machine nameplate: supply voltage and phase count (a 400 V, three-phase machine here) and full-load current (15 A).
  • Transformer nameplate: the primary taps, the secondary voltage for each tap, the kVA rating, and the connection diagram inside the terminal cover.
  • The panel, with a meter rated for the voltage: line-to-line voltage on all three pairs, then each phase to ground.

What those readings decide:

  • Three line-to-line readings within a few percent of the supply you were promised: carry on.
  • One phase reading markedly higher to ground than the other two, which sit near 120 V: a high-leg delta. The machine still sees full line-to-line voltage, so it runs; land the fourth conductor on the grounding bar, never on the high leg.
  • Only single-phase service available: stop. A three-phase machine transformer cannot be fed from two legs of a single-phase panel, and the phase-conversion routes are a different job altogether, covered in Powering a 600 V three-phase machine from 240 V single phase.

Why the as-shipped tap fails on your supply #

A tap fixes the turns ratio, and the secondary scales linearly with what you put in. Worked from the nameplate data in this case, a 380 V secondary on a 208 V primary:

ratio = 380 V / 208 V = 1.827

V_out = 240 V x 1.827 = 438.5 V

438.5 V / 400 V = 1.096, so +9.6% at the machine.

Three reasons that is a reject rather than a judgement call:

  • Any drive inside the machine rectifies to the peak of the line, so the DC bus sits at 1.414 x 438.5 V, about 620 V, against 566 V at nameplate. That bus runs permanently closer to its overvoltage trip point and dissipates more heat.
  • IEC 60204-1:2016, the standard for the electrical equipment of industrial machines, expects a machine to operate correctly on a supply within 10% of nominal voltage, so the margin is gone before the supply itself moves; a supply 5% high, 252 V, gives 252 x 1.827 = 460 V, or +15%. Confirm the machine's own stated band in its documentation.
  • The machine's internal control transformer and every coil and contactor run about 10% hot for their whole service life, and the failure mode is nuisance trips and early component failures, not one clean fault you can point at.

Decision: the as-shipped tap is not usable on this supply. Re-tap.

What the 230 V tap gives #

The table assumes the secondary stays 380 V on whichever primary tap you choose, which is what multi-tap machine transformers normally do; read the nameplate row to confirm before trusting any figure below, because these are calculated values, not measurements.

Primary tap Ratio (380 V / tap) Secondary at your supply Against the machine rating Decision
As shipped 1.827 438.5 V +9.6% Reject
230 V 1.652 396.5 V -0.9% Use this
240 V (if listed) 1.583 380.0 V -5.0% Use this

The 230 V row is the target: 380 V x (240/230) = 396.5 V. If the nameplate lists a 240 V primary, that tap is better still, because the output lands exactly on the secondary rating. If the as-shipped connection is the only one listed, no link change can fix the overvoltage; the stop conditions at the end cover that case.

The fourth wire is protective earth #

The supply is three-phase delta: the three conductors on the breaker are phases, and there is no neutral to carry one. The fourth conductor is the protective earth. NFPA 70, the National Electrical Code (2023 edition), Article 250, requires the equipment grounding conductor to run with the supply conductors and to bond the enclosures it serves; confirm the local earthing arrangement with the authority having jurisdiction and the equipment documentation. In practice that conductor lands on the machine's PE terminal and bonds the transformer enclosure, and nothing else. Never land it on a phase, and never on a secondary terminal.

Prove it with the panel off: continuity from the fourth conductor back to the panel's grounding bar. The phase-to-ground patterns from the first section tell you which flavour of delta you have, and none of them changes where this wire lands.

Size the feeder from the machine, not the tap you came from #

Worked from the 15 A nameplate at the machine rating, three-phase:

S = 1.732 x 400 V x 15 A / 1000 = 10.39 kVA

Primary current at your supply = 10 390 VA / (1.732 x 240 V) = 25.0 A

On a true 208 V supply the same load drew 10 390 / (1.732 x 208) = 28.8 A, so moving to the higher tap and supply reduces primary current slightly.

Decisions: the transformer nameplate must show at least that 10.4 kVA. Treating the 25 A as continuous, the minimum ampacity is 25 x 1.25 = 31.3 A, and 10 AWG copper in the 75 C column of NFPA 70 Table 310.16 (35 A) covers it. A 30 A three-pole breaker carries the load with margin; if inrush trips it on energization, 35 A is the next standard size that still protects that conductor. These are estimates from the nameplate, so verify them against the governing code edition and the equipment documentation for your installation conditions.

Re-tap the primary and energize in steps #

Everything below begins with the supply locked out and proven dead: zero volts phase-to-phase and phase-to-earth, all three phases, on a meter verified against a known live source before and after. That step is not optional.

  1. Photograph the primary links and the secondary terminals exactly as found.
  2. Move the primary links to the 230 V terminals exactly as the diagram inside the terminal cover shows, and torque the lugs to the value marked on the cover.
  3. Leave the secondary links as shipped and leave the machine disconnected from the secondary.
  4. Land the three phase conductors on the primary and the fourth conductor on the PE terminal.
  5. Energize and measure the three secondary line-to-line voltages unloaded: expect roughly the calculated 396.5 V, with all three phases within about 1% of each other. A large spread points to a misplaced link or a loose lug, so de-energize and look. If a correctly sized breaker still trips on this first close, transformer inrush is the cause, and Stopping breaker trips on 25 kVA transformer inrush covers the fixes.
  6. De-energize, connect the machine, and re-energize.
  7. Under load, confirm the secondary line-to-line voltage sits inside the machine manual's tolerance band, clamp the primary current on each phase against the 25 A figure, and check phase rotation and any first-start fault display per the machine manual.

When to stop and escalate #

  • No 230 V or 240 V primary on the transformer nameplate: replace the transformer with a unit whose primary matches the supply and whose secondary is 380 to 400 V, rated for at least the 10.4 kVA worked above, or get the machine or transformer manufacturer's answer, sending nameplate photos and your measured line-to-line voltages.
  • Secondary voltage outside the machine manual's stated band after the re-tap, measured under load: stop and escalate with the same records.
  • Three line-to-line supply readings that differ from each other by more than a few percent: fix the supply before judging the transformer.
  • A first-start fault that only clears when you push the secondary back toward 438 V: something else you changed is wrong. Work back through the measurements; never move the tap up to mask a machine fault.

Questions asked

My 240 V supply sometimes runs at 252 V. Does the 230 V tap still hold?

Yes. 380 V x 252/230 = 416.3 V, which is 4.1% above the machine nameplate and still comfortably inside the plus or minus 10% band the machine standard assumes. The same 252 V on the as-shipped tap would give about 460 V, which is exactly why that tap has to go.

Is 396.5 V too low for a machine rated 400 V?

No. It is 0.9% below nameplate, and machines in this class are normally designed around the 380/400/415 V utilization band, where 380 V, or 5% under, is an everyday condition. Check the machine manual's stated band, but do not chase the last volt by moving back to the as-shipped tap.

The nameplate has no 230 V or 240 V tap. What are my options?

Replace the transformer with a unit whose primary matches the supply and whose secondary is 380 to 400 V at a rating of at least the machine's 10.4 kVA, or ask the machine or transformer manufacturer for the correct part. A buck-boost transformer sized for the machine load is the other documented route when a replacement main transformer is not practical. Do not keep the as-shipped tap and hope.

Do the secondary connections change when I move the primary taps?

No. Only the primary links move; the secondary stays strapped exactly as shipped. Expect the unloaded secondary to read a few volts above the calculated figure because there is no load drop yet, and it settles once the machine draws current. If one secondary phase reads far off the other two, a primary link is misplaced: de-energize and compare against the diagram in the terminal cover.

Why does the fourth wire go on the earth terminal and not a neutral block?

Because the fault-clearing path needs it there. Current from a ground fault must return on that conductor to the panel grounding bar so the breaker opens; a neutral carries load current, and a delta machine feed has no load current on a fourth conductor. Landing the wire anywhere else either does nothing for fault clearing or puts line voltage on the frame.

Keep reading

  • How-to

    Powering a 600 V three-phase machine from 240 V single phase

    The nameplate works out to 20.8 kVA of apparent power. Fed from the single-phase shop service, that is about 87 A before converter and transformer losses, so the machine needs a rotary phase converter sized to its total demand plus a reverse-connected step-down transformer, unless tracing shows the internals run on 200 to 220 V. Verify loaded voltage balance before releasing the machine to production.

    Power distribution and transformers

  • Selection guide

    Sizing a padmount transformer for a 120/240 V delta load

    Select the 300 kVA four-wire delta padmount and reject the 225 kVA unit: the center-tapped winding runs at 129% of its rating during the start on the smaller unit and 97% on the larger one. The choice holds only with a written tapped-section rating covering the start and continuous loading calculated here; otherwise use a single-phase bank or a 208Y/120 V wye secondary.

    Power distribution and transformers

  • Selection guide

    Replacing a 45 kVA 12 kV pole-mount three-phase transformer

    Order a 12.47 kV-class three-phase pole-mount and run it on its 2.5% below-rated tap: that holds the secondary about 1.3% low at a typical measured bus. If your reading sits lower, use the 5% tap, or build the bank from three 15 kVA 7200/12470Y-120/240 V single-phase units in wye at 125 A per phase.

    Power distribution and transformers