Reversing rotation on a star-delta starter: which two phases

Motors and motor starters Published 6 min read By Current Intel engineering team

Short answer

For a one-time direction change, exchange any two incoming phases at the dedicated supply termination ahead of the entire starter and leave every star and delta connection untouched: the rotating field follows the phase sequence, so the star start and the delta run reverse together. For forward and reverse in normal operation, add a mechanically and electrically interlocked reversing contactor pair upstream and close it before the star-delta sequence begins.

On this page
  1. The one-time swap, step by step
  2. Why one exchange reverses star and delta
  3. Worked example: the one-time swap on a 480 V star-delta starter
  4. At-will reversing: the interlocked pair upstream
  5. The checks before the machine goes back
  6. Questions asked

To reverse a motor started through a star-delta starter, exchange any two of the three incoming phases at a termination that feeds this starter alone, upstream of the main, star and delta contactors, and change nothing else. The rotating field follows the phase sequence, and a star-delta starter only changes how the windings are connected, so that one exchange reverses the star start and the delta run together. If the machine must change direction in normal operation rather than once, a fixed swap is the wrong design: fit a reversing contactor pair ahead of the starter, interlocked mechanically and electrically, and prove the chosen direction closed before the star sequence begins. The steps below cover both jobs, the checks that close them, and one worked case.

The one-time swap, step by step #

  1. Isolate, lock out and verify. Open and lock the breaker or disconnect feeding the starter and any separate control supply, then test for absence of voltage at the line terminals before a conductor is touched. NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, requires that electrically safe work condition; your site's procedure and the authority having jurisdiction set the exact steps.

  2. Confirm the swap point is dedicated. Everything downstream of a phase exchange reverses, so the exchange belongs at the lugs, breaker or disconnect that feeds this starter and nothing else.

  3. Label before you disconnect. Mark the three line conductors and the positions they occupy. On an old panel where nothing is marked, the approach in identifying terminals on an old star-delta starter panel gets the winding ends sorted before any wire moves.

  4. Exchange two phases. L1 and L3, L1 and L2 or L2 and L3, any pair works, because the field reverses when any two of the three lines trade places, as why any two phase swaps reverse a three-phase motor shows. Land each conductor on the other's position and tighten to the torque the starter's documentation specifies.

  5. Touch nothing downstream. The six motor leads stay on the contactors they occupied, the star point stays as wired, and the delta connections stay exactly as found.

  6. Restore and test. Refit covers and guards, clear the lockout under the site procedure, and give a momentary start with the driven machine safe to turn. Direction correct: the job is done. Wrong or uncertain: isolate and verify again before opening anything.

Why one exchange reverses star and delta #

A three-phase supply makes a rotating field whose direction is set by the order of the phases. A star-delta starter never changes that order: the star contactor ties the winding finishes into a common point, and the delta contactor reconnects those finishes across the lines, with every winding still fed in the supply's sequence. Because the exchange sits upstream of all three contactors, both the star path and the delta path deliver the reversed order, and the motor turns the new way from the first instant of the star start.

Star changes magnitudes, not direction. Each winding sees the line voltage divided by the square root of three during the star phase and full line voltage in delta, and the star start draws about one-third of the delta-start line current and torque at the same slip. The swap leaves those ratios exactly as they were.

The one place the exchange must not be made is inside a single branch of the starter. Cross two phases in the delta contactor's wiring only, and star produces one field direction while delta produces the opposite: the motor starts, then plugs itself at the transition, and the surge reads like a transition fault. The cure for that pattern is to move the exchange upstream, not to adjust the transition.

Worked example: the one-time swap on a 480 V star-delta starter #

The case is the commissioning one behind this article: a star-delta starter installed and healthy, a shaft that turns the wrong way, and a machine that will run in one direction from now on.

Inputs:

  • Supply: 480 V three-phase, through a breaker dedicated to this starter, the common plant voltage this site's motor articles use.
  • Motor: six winding ends brought out to the starter, nameplate connections matching the existing star-delta circuit, which the starter type itself requires.
  • Requirement: one direction, fixed for good, which is the job as posed.

The rule, in words: exchange any two incoming phases at the dedicated supply termination; the field sequence reverses everywhere downstream, and the star and delta magnitudes do not change.

The arithmetic:

  • Lines exchanged: 2 of the 3, at the dedicated termination; connections opened inside the starter: 0.
  • Star-phase winding voltage after the swap: 480 V divided by the square root of three, so 480 V ÷ 1.732 = 277 V, identical to before the swap.
  • Star-start line current: about one-third of the delta-start line current at the same slip, a ratio, so also identical before and after.

Result: the motor accelerates in star and runs in delta in the new direction, with the same winding voltages, currents and torques it had when it turned the old way.

Decision: for this job the swap is the whole design, two conductors traded at one termination and nothing else rewired. The threshold is the operating requirement: the moment an operator must command both directions in normal running, a fixed swap is the wrong tool, and the interlocked pair below becomes the job.

At-will reversing: the interlocked pair upstream #

  1. Keep the star-delta starter as built and put two more contactors ahead of it. The forward contactor passes the phases straight through; the reverse contactor crosses two of them, the same principle as why reversing a three-phase motor needs two contactors, applied one stage upstream. Size both for the motor's full-load and start duty.

  2. Interlock the pair both ways. A mechanical interlock between the two contactors prevents simultaneous closure by construction, and each coil circuit carries the other's normally closed auxiliary contact so the controls cannot command both at once. Closure of both is a dead short between two phases.

  3. Sequence direction before starting. The controls prove the selected direction contactor closed first, then release the star-delta sequence: star start, timed transition, delta run. The opposite direction stays blocked while any start or run command is alive, and the sequence resets on stop.

  4. Stop before reversing. The controls take a stop, or a proven zero-speed signal, before they accept the opposite direction; this starter carries no plugging rating.

  5. Treat a redesign of the main contactor as a redesign. Replacing the starter's main contactor with the reversing pair is a valid circuit in experienced hands, but it redraws the power and control diagrams; the upstream pair is the smaller, checkable change.

The checks before the machine goes back #

  • Direction: confirm on the first momentary start against the machine's direction arrow. Before that first start, what a phase rotation tester tells you about motor direction lets you verify the new sequence at the supply termination with the starter still locked out.
  • Transition: the star-to-delta transfer should look and sound as it did before the work, with no deeper kick and no trip. A trip that appears only at transition after the swap points at a winding-end connection disturbed during the job, not at the exchange; that is the investigation in fixing star-delta starter breaker trips at transition.
  • Running current: measure all three phases in delta and compare them with the motor nameplate and the overload setting. Direction does not change the magnitude, so a current that differs from before the swap means something else moved.
  • Overload: the setting stays where it was; only placement decides what current the relay sees in a wye-delta circuit, which overload relay placement in a wye-delta starter circuit works through.
  • Sharing: if the feeder turned out to serve other motors, the exchange point was wrong. Re-isolate and move it to the dedicated termination before anything else on that feeder starts.

Questions asked

Can I swap two phases at the motor terminal box instead of at the supply?

No. On a star-delta starter all six winding ends run to the contactors, and the terminal box holds links between them. A swap made there changes only part of the circuit, so the motor can turn one way in star and the opposite way in delta, and the transition becomes an abrupt reversal at speed. Make the exchange upstream of the whole starter so every winding sees the new sequence.

The motor turns correctly in star but reverses when it goes into delta. What is wrong?

That symptom means the delta contactor is connecting the windings with a phase transposed: star and delta are producing opposite field sequences. Isolate and verify, then check the six winding ends against the wiring diagram and land each finish on the phase the delta pattern requires. The exchange for rotation belongs upstream, where it reverses both connections together.

Does reversing change the overload or protection settings?

No. Direction does not change current magnitude, so the overload stays set from the motor nameplate as before. What matters is placement: a relay in the delta branch of a wye-delta circuit carries winding current, which is the line current divided by the square root of three, and is set accordingly. Leave both the setting and the position exactly as they were.

Will the swap reverse other motors on the same feeder?

Yes, if it is made at a point that feeds anything else: a phase exchange reverses every three-phase motor downstream of it. Use the breaker or disconnect dedicated to this starter, or the starter's own supply lugs. Single-phase loads keep their voltages, but any phase-sequence relay or voltage-monitoring three-phase device on that feeder may now alarm or trip and needs checking before restart.

Can the operator reverse this motor while it is running?

Not with this starter. Applying the opposite sequence to a spinning motor plugs it: braking torque appears and the current runs far above the direct-on-line start the contactors were selected for, so the contactors, protection and driven mechanics all see a duty nobody sized them for. The controls must take a stop, or a proven zero-speed signal, before accepting the opposite direction command.

Keep reading

  • Troubleshooting

    Why neutral-side switching trips a smart DOL starter

    Move the direction changeover contactor to the line side so the starter feeds the selected winding directly, and leave the run capacitor between the CW and CCW terminals: in the tested 110 V, 2.6 A circuit that raised successful starts from about 1 in 20 to 19 in 20. Return-side switching lets capacitor charging current through the unselected winding distort the current the starter measures at closure, so its residual-current diagnostic reports a missing path.

    Motors and motor starters

  • How-to

    Identifying terminals on an old star-delta starter panel

    A1 and A2 are the contactor coil terminals, and the coil's labeled voltage must sit within the 85 to 110 percent band IEC 60947-4-1 requires against the control supply. NO only means a contact is open at rest; its traced wiring decides whether it is a start or holding contact. With the panel locked out and verified dead, tracing the six motor leads through the contactors is what proves a star-delta scheme.

    Motors and motor starters

  • Explainer

    What a phase rotation tester tells you about motor direction

    A phase rotation tester fixes the order of the three supply phases at the points you connect, not the way a motor will turn. To predict direction before the first start, match that supply reading with a motor-rotation reading taken while the isolated shaft is turned in the required direction from a recorded viewing end, then land the leads in exactly that pairing. Any two conductors crossed anywhere downstream of the test point reverse the result.

    Motors and motor starters