Why reversing a three-phase motor needs two contactors
Short answer
Motor 1 needs two contactors: a three-phase motor reverses only when two of its three supply lines trade places, and one contactor delivers one fixed sequence. Wire the reverse contactor with two lines crossed, interlock the pair mechanically and electrically, and dwell long enough for the shaft to stop between directions. Motor 2, one direction only, needs a single contactor.
On this page
- Can a three-phase motor be reversed with one contactor?
- How do the two contactors get wired to reverse the motor?
- What keeps both reversing contactors from closing at the same time?
- How long must the motor be off before it reverses?
- How do I sequence the two motors with relay logic?
- Where does the overload relay go with two contactors?
- What size and duty rating do the contactors need?
- What should I check before the first run?
- Questions asked
Motor 1 needs two contactors, and no relay trick reduces that number. A three-phase induction motor's direction is set by phase sequence — the order in which the three line voltages reach the motor terminals — and a contactor is a fixed wiring that delivers exactly one sequence. The reverse sequence has to come from a second contactor with two of the three lines crossed, and that pair must be interlocked so they can never close together, because closing together is a phase-to-phase dead short. Motor 2 runs one direction only, so one contactor carries it. Here is the wiring, the interlock, the relay sequence for your pushbutton cycle, and the numbers that set the dwell and the ratings.
Can a three-phase motor be reversed with one contactor? #
No — one contactor connects one fixed phase sequence, and an induction motor runs the way its sequence points. Motor 1 needs two contactors wired as a reversing pair; Motor 2, single direction, gets by with one.
Rotation follows the rotating stator field, and the field's direction is the order in which the three line voltages reach their peaks. Swap any two of the three lines and that order — and the field — reverses; the physics of why any pair works is in why any two phase swaps reverse a three-phase motor. A contactor cannot make that swap: its poles are one-to-one links between line and load terminals, so whatever relay logic surrounds it, one contactor always presents the same sequence. Only a drive changes sequence electronically. On a nine-lead dual-voltage motor, do the swap on the three incoming lines (T1, T2, T3 on NEMA-marked motors) and never disturb the tied leads.
How do the two contactors get wired to reverse the motor? #
Both contactors take the same three lines on their top side, and the reverse one crosses two of them on its load side: forward feeds the motor L1-L2-L3 in order, reverse feeds the same motor with L2 and L3 exchanged.
| Motor line | Forward contactor ties it to | Reverse contactor ties it to |
|---|---|---|
| A | L1 | L1 |
| B | L2 | L3 |
| C | L3 | L2 |
Call the motor lines A, B and C — placeholders for whatever the terminal block actually reads (T1/T2/T3 on NEMA-marked motors, U/V/W on IEC ones). Both contactors' line sides parallel straight onto L1, L2 and L3; the cross lives only between the load-side terminals and the motor. The two load sides then join, and one set of three conductors runs from that junction through the overload relay to the motor. A contactor by itself is not motor protection — the overload is what makes the pair a starter, the distinction drawn in motor starter vs contactor: using a starter as one.
What keeps both reversing contactors from closing at the same time? #
Two interlocks, always both: a mechanical interlock that physically blocks the armatures from pulling in together, and an electrical interlock that wires each contactor's normally closed auxiliary contact in series with the other's coil.
Here is what the interlock buys you. Forward closed ties B to L2 and C to L3; reverse closed ties B to L3 and C to L2. Close both and L2 sits hard against L3 through four closed main poles — a bolted phase-to-phase fault limited only by supply impedance. No operating sequence makes that safe, so the protection has to live in the hardware. The mechanical interlock is a lever or block between the two contactor bodies, and complete reversing assemblies come from the factory already joined and cross-wired. The electrical interlock means the reverse coil is literally not fed while a forward auxiliary contact is closed, and vice versa — it survives a welded auxiliary or a jammed pushbutton where the drawing's intended sequence would not. A third layer, the normally closed contact of each pushbutton in the opposite rung, is good practice on top of, never instead of, the first two.
How long must the motor be off before it reverses? #
Long enough for the shaft to be standing still, plus margin: with a measured 1.8 s coast-down, the off-delay belongs at 3 s, and even an intentional plug reversal still wants roughly 40 ms of dead time just to clear the arc at changeover.
Reversing a still-spinning motor is plugging. The motor sees slip near 2, line current near locked-rotor level, and contactors rated for breaking stall current. Your cycle does not need any of that: the right limit ends travel, and there is time to let the shaft coast.
Worked example, illustrative inputs. Motor 1 is a 2 hp, 460 V, three-phase motor with a nameplate full-load current of 3.4 A — the value NFPA 70, the National Electrical Code, 2023 edition, Table 430.250 lists for 2 hp at 460 V for conductor and short-circuit sizing (the nameplate figure governs the overload setting).
Coupled to the load, the shaft stops 1.8 s after the forward contactor opens, timed with a chalk mark and a stopwatch. Off-delay = 1.8 s × 1.5 = 2.7 s, so set the dial to 3 s. The 1.5 factor is working margin — a field rule — for a colder gearbox or a heavier workpiece, not a code value. That 3 s dwell is 3000 ms, seventy-five times the ~40 ms minimum changeover interval, and it means the reverse contactor always closes on a stationary motor. Decision: with this dwell in the logic the pair runs in ordinary AC-3 duty (next section); shorten the dwell below the real coast-down and you are plugging, which reopens the rating question.
How do I sequence the two motors with relay logic? #
Chain it so each step enables the next: the start button seals Motor 1 forward, the right limit stops forward and fires Motor 2 through the interval timer, the timer ends Motor 2, the dwell timer releases Motor 1 reverse, and the left limit ends the cycle.
The rungs, with the interlocks built in:
- A cycle relay (CR) picks up on the start pushbutton through the stop pushbutton's normally closed contact and seals itself with its own normally open contact; every branch below sits behind a CR contact.
- Forward: CR contact, right-limit NC (opens on the limit), the reverse contactor's NC auxiliary, then the forward coil; the forward NO auxiliary seals the branch from the start pushbutton.
- At the right limit: its NO contact energizes an interval timer — a single-shot unit whose contact closes the instant its coil sees voltage and drops after the set time. That contact runs Motor 2's contactor; a 6 s Motor 2 run means 6 s on the dial.
- Timer done: its contact drops Motor 2 and energizes the off-delay (3 s in the example), whose contact, with the left-limit NC and the forward NC auxiliary in series, feeds the reverse coil.
- Left limit: its NC contact drops reverse, and its spare NO contact drops CR so the cycle — not just the motor — ends.
Put the power-interruption behavior in on purpose. As drawn, a supply dip drops CR and nothing restarts until someone presses start, which is what IEC 60204-1:2016, the machine electrical equipment standard covering stop functions and the prevention of unexpected start-up, expects of a machine like this; NFPA 79, 2024 edition, the electrical standard for industrial machinery, carries the same expectation for machines built to it. Never let a limit switch that is still made restart motion on its own. When the sequence outgrows relays, the same chain of timers, limits and seals becomes a ladder program — a pulse-count sequence in S7-1200 ladder logic shows the pattern.
Where does the overload relay go with two contactors? #
One overload relay, downstream of the junction where the forward and reverse load sides join, covers Motor 1 in both directions; set it to nameplate full-load current, and give Motor 2 its own relay behind its own contactor.
The motor draws the same line current under either sequence, so one thermal element in the combined path sees both directions and a second buys nothing. Set the dial to the nameplate amperes as covered in setting overload relays from motor nameplate full-load current; for a motor that reverses into a jam-prone load, the trip-class and jam considerations in selecting overload and jam protection for a reversible motor are the next read. Mount the reset where an operator can reach it without opening the power section.
What size and duty rating do the contactors need? #
Size each contactor by the motor's full-load current in IEC 60947-4-1 AC-3 duty — squirrel-cage start and stop at speed — and move to AC-4 only if the machine plugs, meaning it reverses before the shaft stands still.
The utilization categories come from IEC 60947-4-1:2018, the product standard for contactors and motor starters: AC-3 covers closing onto and breaking a motor running at speed; AC-4 covers starting, inching and plugging, where the contacts break locked-rotor current. Your cycle with its dwell is squarely AC-3. Order each reversing contactor with at least one NO and one NC auxiliary contact — the seal-in and the interlock consume them — and match coil voltage to the control supply, 120 V from a small control transformer being the usual choice. For the example motor at 3.4 A, the smallest AC-3 frames carry several times that figure, so choose on coil voltage, auxiliary count and the starter's listed short-circuit rating with your branch protection, and confirm the details with your authority having jurisdiction and the equipment documentation, since editions and local amendments differ.
What should I check before the first run? #
With the disconnect locked out and absence of voltage verified at the motor terminal box, confirm the phase mapping first, then prove the interlock, then run the cycle uncoupled before coupled, in that order.
- Phase mapping: continuity from each line through each contactor to the motor leads matches the table above, overload between junction and motor.
- Interlock proof: with control power only, hold forward energized and command reverse — the reverse coil must not pick up — then repeat the other way; with all power off, try to press both armatures by hand and confirm the lever stops the second.
- Direction bump: uncoupled, jog forward; if it turns the wrong way for the machine's convention, swap B and C at the junction, never inside the motor.
- Limits and timers: run the full cycle and confirm the right limit drops forward before Motor 2 starts, Motor 2 runs its set interval, the dwell expires before reverse closes, and the left limit ends the cycle.
- Power drop: open the control supply mid-cycle; everything drops and the machine waits for the start button.
- Then couple the load, repeat the timing checks loaded, and remeasure the coast-down coupled — it sets the dwell.
Questions asked
Does Motor 2 need a second contactor too?
No. Motor 2 turns one direction only, so one contactor, its own overload relay, and the interval timer that fixes its run time are the whole job. The second contactor exists only because Motor 1 must be fed two different phase sequences.
Which two phases should I swap for reverse?
Any two — the motor responds to the sequence, not to which pair moved. Keeping L1 straight through and crossing L2 and L3 is the drawing convention because it reads cleanly. What matters is that the schematic, the contactor labels and the panel wiring agree on the same pair.
What actually happens if both contactors close together?
L2 and L3 get bolted together through the closed main poles, a phase-to-phase fault fed at the supply's available short-circuit current. The overload relay is far too slow to matter; the branch fuse or breaker clears it, provided its interrupting rating meets the available fault current at that panel.
Can a VFD replace the two reversing contactors?
Yes. A drive reverses by electronically changing its output sequence and can run the limit-switch and timer logic itself, but it brings parameter setup, a stopping method to configure and drive-specific wiring rules instead of relay hardware. For one fixed cycle on two small motors, the interlocked contactor pair is the simpler build.