Troubleshooting
Running two motors on one VFD with output contactors
Short answer
One VFD can run a 3 hp motor and a 1/2 hp motor one at a time: size the drive for the larger motor, connect each through its own interlocked output contactor, change over only with the drive disabled, and give each motor its own overload relay set from its own full-load current. If both motors must ever run together, use two drives.

On this page
Yes — a 3 hp milling-head motor and a 1/2 hp auxiliary motor that never run at the same time can share one VFD sized for the larger motor, and a bare selector switch is the wrong way to change between them. Build the output side properly: one contactor per motor, the two contactors interlocked mechanically and electrically, the changeover done only while the drive is disabled, and one overload relay per motor set from its own full-load current. The soft start the drive provides does not stand in for those relays: configured for the larger motor's current, its electronic overload cannot see trouble on the smaller one. Below are the contactor scheme, the changeover sequence, the overload settings for both motors, and the faults this wiring produces when a rule slips.
One shared drive or two independent drives #
Only one motor runs at a time, so the shared drive never carries two loads and can be treated as a single-motor drive on the larger motor: its continuous rated output current at the machine's supply voltage needs to meet or exceed that motor's nameplate full-load current, and the smaller motor draws a small fraction of the drive's rating. The contactors do the selecting, and the drive only knows which motor is connected through its own motor data.
| Arrangement | One shared VFD | Two VFDs |
|---|---|---|
| Selecting the motor | Two interlocked output contactors | Each motor stays on its own drive |
| Changeover | Drive disabled, contactor transferred, drive re-enabled | Independent run commands |
| Overload protection | Drive tracks the large motor; each motor also carries its own relay | Each drive set for its own motor |
| Where it fails | A contactor moves while the drive is enabled, or both close together | Needs the panel space, supply capacity and a second set of settings |
The deciding case is duty. While the two motors stay mutually exclusive, one drive with interlocked contactors is the simpler system, with one set of line-side protection to maintain. If a job ever needs both motors turning together, the shared drive is out, and so is any single protective device spanning both motors — that is the arrangement behind why two motors behind one overload relay trip or burn. Two drives, each configured and protected for its own motor, is the correct build for simultaneous duty.
Interlocking the two output contactors #
Put one contactor between the drive output terminals and each motor, sized for that motor's full-load current. Give the pair a mechanical interlock — the accessory sold for reversing-starter contactor pairs — and an electrical one: each contactor's normally closed auxiliary contact sits in the other contactor's coil circuit, so neither coil can pull in while the other contactor is closed. Both closed together hands the drive a phase-to-phase fault through two motor windings; the interlock is what prevents that event, and both halves of it get tested before the drive ever runs.
Then let the contactor state gate the drive: wire the auxiliaries so the enable or run circuit is complete only when exactly one contactor is closed. A hand selector switch can do the switching instead, but it leaves the disable-the-drive-first step in the operator's memory; wire the panel so the interlock does the remembering.
The changeover sequence #
Open the panel only de-energized: lock out, verify absence of voltage at the drive and contactor terminals per NFPA 70E, 2024 edition, and treat the drive's DC bus as charged until the manual's wait time has elapsed.
- Cancel the run command and let the drive ramp the running motor to a stop.
- Remove the drive enable so the output stage is blocked.
- Wait the interval the drive manual specifies between blocking the output and interrupting it; the manual's figure governs this drive, not habit.
- Open the live motor contactor, with the interlock holding the other one open.
- Select the other motor and confirm exactly one contactor is closed.
- Restore the enable, give the run command, and check rotation direction on the first changeover of each motor.
Never transfer under power. Breaking a conducting drive output puts a voltage spike on the output transistors, and closing a contactor into an enabled drive — or into a spinning motor — drives a surge into the same stage; most drive manuals bar load-side switching while the drive is live and print the permitted sequence. A load-side contactor that only moves while the drive is off is the arrangement the practice supports.
Setting the overload relays for a 3 hp and a 1/2 hp motor on 230 V #
Inputs #
- Motor ratings: 3 hp and 1/2 hp, three-phase induction motors, from the machine in question.
- Service: 230 V, three-phase, 60 Hz, the usual machine-tool supply; the example assumes it, and at 460 V or 200 V the matching row of the same table applies with identical arithmetic.
- Full-load currents: 9.6 A and 2.2 A, from NFPA 70, National Electrical Code, 2023 edition, Table 430.250, which lists approximate full-load currents for three-phase motors; a readable nameplate current replaces these, because the NEC takes overload settings from the nameplate rather than the table.
- Multiplier: 125% of full-load current for a motor marked with a service factor of 1.15 or higher (or a temperature rise not over 40 °C), 115% for every other motor, from the same NEC at 430.32, which limits how far above rated current an overload may pick up.
The rule #
Set each motor's overload pickup at the multiplier times that motor's full-load current and no higher, and protect each phase of a three-phase motor, which a three-pole relay per motor covers — the NEC at 430.37 puts overload protection in each ungrounded conductor.
The arithmetic #
- 3 hp motor, service factor 1.15 or better: 9.6 A × 1.25 = 12.0 A pickup.
- 1/2 hp motor, service factor 1.15 or better: 2.2 A × 1.25 = 2.75 A pickup.
- Either motor marked service factor 1.0 instead: 9.6 A × 1.15 = 11.0 A and 2.2 A × 1.15 = 2.5 A for that motor.
Result #
Overload pickups of 12.0 A and 2.75 A for the two relays — 11.0 A and 2.5 A where a nameplate shows service factor 1.0. These are estimates: the nameplate full-load current replaces the table value wherever the plate reads, and the authority having jurisdiction confirms the final settings.
The decision #
Fit a three-pole overload relay in each motor contactor at those pickups, and wire each relay's normally closed trip contact into the drive enable so a trip blocks the output — the wiring that stops one VFD when either motor overload trips carries straight over to this panel. The drive's own motor-overload setting stays at the large motor's rated current and protects nothing but it.
The mismatch is the reason. A 2× overload on the small motor reads 4.4 A, about 46% of that setting, and an electronic overload that never sees 100% never trips — the small motor overheats until its windings fail while the drive reports light load. Even a stall, roughly six times rated current at about 13 A here, barely crosses the setting on a trip curve timed for the larger motor's thermal capacity. If the drive stores a second motor data set and the selection wiring switches it, verify the switched data against the newly selected motor before enabling; wrong motor data leaves a drive humming at a motor that will not turn, the failure traced in fixing wrong motor data on a spindle VFD.
What this wiring trips and burns #
- Overcurrent fault the instant a contactor closes: the transfer ran while the drive output was still alive — the enable came back before the contactor settled, or the manual's wait was skipped. Re-run the sequence and gate the enable through the contactor auxiliaries.
- Short-circuit trip or a damaged output stage with neither motor running: the contactors closed together — welded main contacts or a bypassed electrical interlock. Test each contactor with its coil de-energized; a welded unit shows continuity with no coil power, and the interlock gets repaired before the drive re-enables.
- The small motor runs hot or fails while the drive reports light load: it is riding on the large motor's overload setting. Give it its own relay at the pickup from the worked example; no drive tuning serves both motors across a gap that wide.
- A relay nuisance-trips a healthy motor: the pickup was copied from the other motor or left at the table value after the nameplate current became known; reset the relay from the nameplate current with the NEC multiplier.
- A motor turns backwards after its first changeover: the selected contactor's load-side phasing does not match that motor. Swapping any two of the three leads at that one contactor reverses that motor only — the same rule that makes any two phase swaps reverse a three-phase motor anywhere.
When the shared drive stops being the answer #
For mutually exclusive motors, build the shared drive: one VFD rated at or above the large motor's nameplate current, two mechanically and electrically interlocked output contactors, the enable gated through exactly-one-selected auxiliaries, changeover by the manual's sequence with the output blocked, and a three-pole overload relay per motor at its own pickup. The first job that needs both motors together ends the arrangement: two drives, each with its own motor data, overload and protection, is then the build, and no intermediate setting or shared device bridges the gap.
Questions asked
How do I test the contactor interlocks before the drive ever runs?
With the panel locked out and the drive input isolated, energize the control circuits from their own supply. Each selection command must close exactly one contactor, the second selection must close nothing until the first is released, and the enable circuit must read open whenever zero or two contactors are closed. The drive and its DC bus stay de-energized for the whole test.
Can I use a rotary selector switch instead of two contactors?
A break-before-make rotary switch rated for the motor current can select between them, but the changeover then lives in the operator's memory: moved while the drive is still enabled, it interrupts a live output and closes into an energized drive, which trips or damages the output stage. Interlocked contactors whose auxiliaries block the enable unless exactly one motor is selected take that memory out of the loop.
Why does the drive show a short-circuit fault with both motors off?
Suspect the contactors first. If both main contacts are welded, or both coils were energized together, the two motor windings are joined at the drive output and the drive sees a phase-to-phase fault through them. Test each contactor with its coil de-energized: a healthy one shows open main contacts, a welded one shows continuity with no coil power. Replace the damaged contactor and repair the interlock before re-enabling.
Where does branch short-circuit protection go in a shared-drive panel?
On the drive's line side. NFPA 70, 2023 edition, sizes power-conversion-equipment supply conductors at no less than 125% of the drive's rated input current in Part X of Article 430, and the line-side breaker or fuses carry the branch duty. On the output side each motor keeps its own overload relay; add nothing else there unless the drive manual calls for it.
Can I just turn the drive's overload setting down to protect the small motor?
Lowering it protects the wrong motor twice. The large motor now nuisance-trips on every hard cut, while the small motor still sits far below the reduced setting, so genuine overloads never register — one protection point cannot span a gap of roughly four to one in motor current. Per-motor overload relays at each nameplate pickup are the fix, not a lower drive setting.
