Current IntelPower LibraryShop main store

How-to

Stopping one VFD when either motor overload trips

Variable frequency drives Published 7 min read

Short answer

Wire 24 V DC from the drive through each MPCB trip contact to its own digital input, set both inputs as external fault, and make the fault stop a coast. One tripped overload then latches a drive fault, names the motor, and takes torque off the healthy motor at once. Keep the series-contact stop as a fallback and leave Safe Torque Off to the safety concept.

On this page
  1. Why the drive cannot protect each motor alone
  2. Three landing points for the trip, and the one to pick
  3. Wiring the two fault inputs, step by step
  4. Configuring the drive for an immediate stop
  5. Worked example: two identical motors on one PowerFlex 525
  6. When to split the motors across two drives
  7. Questions asked

Run 24 V DC from the drive's control power through each MPCB trip contact to its own digital input, program both inputs as an external fault, and set the fault stop to coast. One tripped overload then latches a drive fault at once, the input that caused it names the motor, and the healthy motor loses torque in the same instant instead of carrying the machine alone. The series-contact stop you sketched works, but it merges both motors into one anonymous stop and lives inside the start logic, where someone can rewire it away. Keep Safe Torque Off out of this job: that input belongs to the machine's safety concept, not to overload annunciation. The drive's own overload model cannot police two parallel motors, so the per-motor MPCBs you already planned stay the protection — the wiring below only tells the drive what they have decided.

Why the drive cannot protect each motor alone #

A drive measures one output current: the sum of whatever its paralleled motors draw. One motor can sit well above its own nameplate while the pair's total still reads normal, so the overload decision has to be made per motor at the breaker, and only the result passed on to the drive. A manufacturer application note for 140M motor-protection circuit breakers (publication 140M-AT003) documents exactly this arrangement at a multi-motor drive output: one MPCB per motor gives each motor its own overload protection and each branch its short-circuit protection. This duty is typically filled from the 140M family; 140M-C2EB10X is one such breaker.

The code lands on the same side. NFPA 70, the National Electrical Code, 2023 edition, covers adjustable-speed drive systems in Article 430, Part X, and 430.124 requires individual overload protection for each motor when one drive serves more than one motor — the per-motor MPCB is that device. Confirm the requirement with the local authority having jurisdiction and the equipment documentation, because editions and local amendments differ.

Set each MPCB dial from that motor's own nameplate full-load current, the same discipline as setting overload relays from motor nameplate full-load current. Keep the drive's electronic overload as protection for the drive and its output group: set it to the sum of both nameplate full-load currents, or disable it where the drive's multi-motor instruction permits it, and never to a single motor's value. What the drive does when its own overload model trips is a different failure path, covered in why a VFD reports a motor overload fault.

Three landing points for the trip, and the one to pick #

  • Series contacts in the stop or enable chain. Both trip contacts in series with the run permission: any trip opens the chain and the drive stops. It works, but both motors share one anonymous stop, and the interlock exists only as long as the start logic stays wired that way — the day start and stop move to the network, the interlock can disappear with them.
  • Safe Torque Off. STO, defined in IEC 61800-5-2 (2021), removes torque without a ramp and without depending on drive firmware, which is what makes it attractive. It is a safety function: its wiring, reset behavior and validation belong to the machine's safety concept. An overload trip is protective-device duty. Spend a fault input on it and keep STO for the safety tasks it exists for.
  • 24 V DC through each trip contact to its own digital input. Each MPCB contact sources the drive's 24 V DC to a separate input assigned as an external fault. Any trip latches a fault at once, the input state names the motor, and the scheme survives later changes to the start logic. Build this one.

The contact logic is the same skill as wiring overload relay contacts to the coil and the PLC: know the normal state and the tripped state before you land the wire.

Wiring the two fault inputs, step by step #

  1. Isolate the drive input and both motor branches, lock them out, and test for absence of voltage before opening the panel or any terminal cover.
  2. Verify each trip contact with a meter: open in normal running, made when the breaker trips. Operate the MPCB's test function to see it change. Do not infer the tripped state from an "NO" or "NC" label — check the auxiliary block actually fitted.
  3. Run the drive's 24 V DC control power through MPCB A's trip contact to digital input 1, and through MPCB B's to digital input 2. Keep the two runs separate and label both ends.
  4. Assign both inputs to the external fault function and set the fault stop to coast, as covered next.
  5. With the machine inhibited from running but control power up, watch both inputs in the drive's I/O status while you open and remake each trip contact.
  6. Prove the stop at standstill: hold one contact in its tripped state and command a start — the drive must fault before it produces any output. Repeat for the other input.
  7. Record the parameter numbers, terminal numbers and contact states in the panel documentation, so the next technician can tell an overload fault from a normal stop.

Configuring the drive for an immediate stop #

On the PowerFlex 525, digital inputs are assigned in the T06x parameter group. A documented field configuration sets the input parameter to 41 for "external fault", and the drive then latches fault F093 "Freeze Fire". Function numbers and fault codes follow the drive series and firmware revision: confirm the number and the code in the manual for the drive in your panel before you write alarm text, and do not copy an identifier from another machine.

Set the fault stop to coast. A deceleration stop holds controlled torque on the healthy motor for the whole ramp — exactly the one-motor-running window that damages this machine — while a coast stop ends switching at once and lets the mechanics coast down. In IEC 60204-1 terms that is a stop by immediate removal of power (stop Category 0) rather than a controlled stop with power removed at standstill (Category 1), and this machine's damage mechanism picks Category 0 behavior for an overload trip.

The fault latches until acknowledged. Read the two input states over the drive's network link for alarm text that names the motor, but let the wire do the stopping: network status is annunciation, not the trip path.

Worked example: two identical motors on one PowerFlex 525 #

The inputs, each with its source:

  • One PowerFlex 525 feeding two identical three-phase motors that start together and share one speed, per the application.
  • One MPCB between the drive output and each motor, as the multi-motor application note specifies (publication 140M-AT003; 140M-C2EB10X is one breaker of the family used in this duty).
  • Control power from the drive: 24 V DC.
  • Two digital inputs, each assigned as external fault (T06x set to 41 in the documented 525 configuration).
  • Fault stop: coast.
  • Each motor's nameplate full-load current: call it F, read from that motor's nameplate.

The rule in words: the drive's current sensor sees the sum of both motor currents, while each MPCB compares only its own motor's current against its own dial.

Both motors at full load:

F + F = 2F

That is the drive's overload setting — the sum of the two nameplate values. Now an unbalanced pair, using illustrative multiples: motor A at 1.2F, motor B at 0.8F:

1.2F + 0.8F = 2.0F

The total equals the drive's setting exactly, so the drive's overload model reads a fully loaded, healthy pair and holds. Only MPCB A, dialed at F, sees the 0.2F of overcurrent on its own motor. Treat the 1.2 and 0.8 as an illustration: the real trip time comes from the MPCB's time-current curve, not from this arithmetic.

Result: MPCB A trips, its contact makes, 24 V DC lands on input 1, the drive latches its external fault and coasts. Motor A was already disconnected by its breaker; motor B loses torque in the same instant.

Decision: dial each MPCB to its own motor's F, set the drive overload to 2F (or off, where the drive's multi-motor instruction allows it), and treat any trip contact closure as a latched fault with a coast stop — never a ramped stop, because the healthy motor is the one still driving the machine.

When to split the motors across two drives #

One drive is the right answer while three things stay true: the motors always start together, they always run at the same speed, and the machine is never allowed to run on one motor — faults included, since any fault anywhere stops both. That is what you wired.

The moment the process needs one motor alone, separate speeds, or real per-motor current data instead of a trip bit, move to two drives, each sized to its own motor, with the run commands paralleled from the same start source. The protection wiring then collapses back to the ordinary single-motor case. Make that call at design time: adding the second drive later costs far more panel work than specifying it now.

Questions asked

What if the drive has only one spare digital input?

Tie both trip contacts in parallel to that single input as an external fault. You keep the immediate latched stop and lose only the which-motor identity, which you recover by reading the tripped breaker's flag at the door. Two separate inputs are worth the second terminal whenever the panel has one to spare.

Which fault code will the drive show when an MPCB trips?

It follows the input function you assign. On the PowerFlex 525, one documented configuration sets a T06x input to 41 for external fault and reports F093 "Freeze Fire"; another documented setup uses input function 12 and reports F002, with the documentation also referencing F094 "Function loss" on that path. Confirm the function number and fault code for your firmware before writing alarm text.

Should the drive's electronic overload be set to one motor's full-load current?

No. With both motors healthy and loaded, the pair draws twice one motor's nameplate current, so a single-motor setting nuisance-trips on normal operation. Set it to the sum of both nameplate values, or disable it where the drive's multi-motor instruction allows, and leave the per-motor protection to the MPCBs.

Can I add contactors so one motor can be dropped for service?

Yes, as isolation, with the drive stopped and locked out — a maintenance disconnect, not a control function. Do not open a contactor in a running drive's output as part of routine control; interrupting drive output under load can trip the drive on overvoltage. On this machine, one-motor running is the condition the fault wiring exists to prevent.

How do I reset after an overload trip?

Clear the cause first: the drive's fault names the input, and the tripped MPCB shows at its flag. The breaker will not reset until its thermal element cools. Reset the MPCB, acknowledge the drive fault at the keypad or over the network, then restart per the machine's normal sequence. If the same motor trips again, measure its current share before the second reset.

Keep reading

  • Troubleshooting

    Why a pump makes less pressure on a VFD than a starter

    At 16 A against a 12.5 A nameplate FLA, with 40 psi instead of 80 at a full-frequency command, the motor is slipping heavily rather than running at full speed. Check pump rotation first, then the drive's motor-data and volts-per-hertz settings against the nameplate. The drive's frequency and rpm displays are commanded and calculated values, not measurements of the shaft.

    Variable frequency drives

  • Troubleshooting

    Why a VFD reports a motor overload fault

    A motor overload fault on a VFD means the drive's electronic thermal model accumulated heat from current above the motor's entered rated current. Compare measured current with both the nameplate full-load current and the drive's entered value before changing any setting: the fix is the load, supply, cooling, or the typed-in number, almost never a raised limit.

    Variable frequency drives

  • Troubleshooting

    Why a VFD overvoltage fault shows with no motor connected

    With the motor disconnected, no energy returns to the drive, so an overvoltage fault can only mean the DC link is being charged past its trip level from the line side. Measure all three line-to-line voltages: sustained high input, a capacitor-switching transient, or a failed sensing board are the remaining causes, in that order of testing.

    Variable frequency drives