Selection guide
Selecting DOL starter components for a single phase motor
Short answer
For a 0.55 kW single phase motor with a nameplate FLC of 4.6 A, select the motor circuit breaker GV2LE10 (6.3 A), the overload relay LRD10 (4–6 A) set to 4.6 A, and contactor LC1D09M7 from the Type 2 coordination table, and wire two poles of both protective devices in series.

On this page
Select a single phase DOL starter by the motor's nameplate full-load current, not its kilowatt rating. For a 0.55 kW single phase motor with a nameplate FLC of 4.6 A, the selection is motor circuit breaker GV2LE10 (6.3 A) for short-circuit protection, thermal overload relay LRD10 with a 4–6 A range set to 4.6 A, and contactor LC1D09M7 as the associated device in the Type 2 coordination table. Both the breaker and the overload must be wired with two poles in series, because a single-phase current through one pole of a three-pole thermal device causes nuisance tripping.
Why the nameplate current decides the selection #
A DOL starter closes a contactor that applies full supply voltage to the motor, with a separate short-circuit device and a separate thermal overload. Two motors can share a 0.55 kW rating and carry different currents at different voltages, so the current basis has to come from the nameplate. Here that basis is the motor's nameplate current.
Each component is then matched to that one number:
- The overload range must include the nameplate current with adjustment room on both sides. LRD10 covers 4–6 A, so the target rate sits inside the range.
- The motor circuit breaker's thermal-magnetic range must also include it. GV2LE10 is marked 6.3 A as its upper setting.
- The contactor is not sized by rule of thumb but taken from the manufacturer's Type 2 coordination table for the current level. For this level, the table associates LC1D09M7.
The coordination tables are built on IEC 60947-4-1, which defines Type 2 coordination as: after a short circuit, no damage to the starter and no change in its rating, so it continues in service. That result is only valid for the exact combination listed in the table. Confirm the combination against the current edition of the table and the equipment documentation, and confirm any installation requirement with the local authority having jurisdiction.
The selection table #
| Function | Device | Rating or range | Why it fits this motor |
|---|---|---|---|
| Short-circuit protection | GV2LE10 motor circuit breaker | 6.3 A setting | Thermal range includes 4.6 A; listed combination for Type 2 |
| Thermal overload | LRD10 relay | 4–6 A range | Nameplate current sits inside the range; dial set to it |
| Switching | LC1D09M7 contactor | 9 A AC-3 class | The Type 2 table association for this current level |
The originally proposed combination of GV2L10, LC1D32M7 and LRD08 fails on two counts: the LRD08 range does not reach the motor's current, so it cannot be set correctly, and the LC1D32M7 contactor is not the table's association for this current level, so the Type 2 result cannot be claimed for that mix. An oversized contactor does not improve protection; it only departs from the tested combination.
Worked example: setting the overload dial #
The overload dial is set to the nameplate FLC, not to a measured running current:
- Nameplate FLC: the nameplate value stated above
- LRD10 range: 4–6 A
- Dial setting: the nameplate FLC
- Check: 4 A ≤ 4.6 A ≤ 6 A, so the setting sits inside the range with 0.6 A of adjustment below and 1.4 A above.
The setting is correct as long as the motor runs at or below its nameplate value in normal service. If the measured running current runs consistently above the nameplate value, the cause is on the load or supply side, and the fix is not a higher dial setting. The same nameplate-first rule applies when you set an overload relay for a three phase motor.
The two-pole series wiring rule #
A three-pole thermal device works by bimetal heating in each pole. If single-phase current passes through only one pole, the other poles carry nothing, the device's differential action sees an imbalance between poles, and the starter nuisance-trips. The manufacturer's single-phase scheme therefore routes the current through two poles of the GV2LE10 and two poles of the LRD10 in series:
- Supply in, through pole 1 and pole 2 of the breaker in series.
- Continue through pole 1 and pole 2 of the LRD10 in series.
- Through the contactor poles to the motor, with the same series treatment the contactor's own diagram shows.
Follow the wiring diagram printed inside the device cover or in its product data for the exact terminal numbers; do not improvise terminal assignments from the device names. Changing the overload dial cannot fix a misrouted pole arrangement, and correct wiring cannot rescue an out-of-range relay. The two checks are independent.
Before opening the starter enclosure: isolate the circuit, lock it out, and test for absence of voltage at the line terminals. Single-phase work is still live work until you have verified it dead.
Verifying the selection before return to service #
With the circuit isolated, trace the power path and confirm the current passes through both series poles of each protective device with no pole bypassed. Compare the installed catalog references with the coordination table for the exact combination. During a controlled functional test, watch the current through starting and running: a trip on starting points to the breaker's magnetic setting or a locked load, while a trip after minutes of running points to the overload setting, the pole routing, or a genuine overload. Record which device operated before changing anything. If you are rebuilding an older starter, the same nameplate-first approach applies when replacing a discontinued IEC contactor.
The decision #
For the 0.55 kW single phase motor discussed here: use GV2LE10, LRD10 set to the nameplate FLC, and LC1D09M7, with two poles of the breaker and two poles of the overload in series per the product diagrams. Reject the GV2L10, LC1D32M7 and LRD08 combination. For any other motor, repeat the same three steps: take the FLC from the nameplate, pick the overload range and breaker setting that contain it, and take the contactor from the Type 2 table row for that current level.
Questions asked
Is GV2L10 with LC1D32M7 and LRD08 correct for a 4.6 A single phase motor?
No, but only two of the three parts fail: the breaker GV2L10 covers this current, while the LRD08 relay tops out below 4.6 A and the LC1D32M7 contactor is not the Type 2 table association at this level. Keep the breaker only if the current table lists it in a combination with LRD10 and LC1D09M7; otherwise use GV2LE10, LRD10 and LC1D09M7, with two poles of each protective device in series.
Why must two poles be wired in series on a single phase DOL starter?
Single phase current through only one pole of a three-pole thermal device leaves that device's other poles unloaded, and the resulting imbalance between poles can cause nuisance tripping. Passing the current through two poles in series shares the heating and keeps the device operating as its bimetal design expects.
What is the difference between Type 1 and Type 2 coordination?
IEC 60947-4-1 defines both. After a short circuit, Type 1 allows the contactor or overload to be damaged and requires replacement before restarting, while Type 2 requires no damage and no change in rating so the starter can continue service. Type 2 is achieved only with the exact breaker, contactor and overload combination listed in the manufacturer's table.
