Setting a GS20 drive for braking resistor deceleration stops

Variable frequency drives Published 7 min read By Current Intel engineering team

Short answer

With a braking resistor installed on B1 and B2, set P06.01 (overvoltage stall prevention) to 0 so the resistor carries the deceleration energy and the drive holds its programmed ramp. Then confirm the resistor leads land on B1 and B2 alone and that its resistance and duty match the model's selection data.

On this page
  1. What overvoltage stall prevention does during a ramped stop
  2. De-energize and verify before opening the terminal cover
  3. The checks, in order
  4. Parameters the commissioning sheet touches
  5. Worked example: resistance and duty arithmetic
  6. The decision, case by case
  7. Questions asked

Setting P06.01, overvoltage stall prevention, to 0 is the one braking-related change from the factory parameter set once a braking resistor sits on B1 and B2 — and it is the last step of the job, not the first. During a ramped stop a GS20-driven spindle becomes a generator: the regenerated energy either stretches the drive's ramp or heats the resistor. With stall prevention disabled and a verified resistor in place, the drive finishes the programmed ramp on time and the resistor takes the energy. The verification comes first: read the fault history, de-energize and verify the DC bus, trace the resistor wiring, and measure the element against the drive documentation for the frame. Worked through below for a 5 hp, 230 V mill spindle, with the decision committed for each outcome.

What overvoltage stall prevention does during a ramped stop #

In a decelerating motor the rotor runs ahead of the drive's output frequency, so power flows back into the DC bus and the bus voltage climbs. Overvoltage stall prevention watches that climb and, past a threshold, slows the rate at which the output frequency falls — the drive stretches the ramp so generation never outruns what the bus can absorb. That is the correct behavior when there is nowhere for the energy to go. With a braking resistor installed, the drive's braking circuit switches the resistor across the bus and the element turns the regenerated energy into heat, which lets the ramp finish on schedule. Leave stall prevention enabled with a resistor fitted and the drive keeps preferring the stretch: stops run long and the resistor idles. Disable it with an open or missing resistor and the bus climbs until the drive trips overvoltage inside the first ramp.

Dynamic braking through a switched resistor is one of several AC motor braking methods for single and three phase motors; the same energy balance is why a motor-side braking resistor works on a PM servo — the resistor, not the ramp, absorbs the regeneration.

De-energize and verify before opening the terminal cover #

The GS20 manual requires input power to be disconnected before wiring the drive, and its bus capacitors hold charge after the line side goes off. NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, covers establishing an electrically safe work condition — de-energize, lock out, and verify absence of voltage — before opening a drive or terminal chamber; confirm the requirement with your authority having jurisdiction and the equipment documentation. Wait the discharge interval the manual publishes for the frame, then measure the bus terminals dead with a meter rated for the DC bus voltage before touching B1, B2, +1, +2 or DC-. Every check below assumes that state.

The checks, in order #

  1. Read the fault before clearing it. Record the displayed code and when it appears: inside a deceleration ramp only, at steady speed, or on a start. A trip on a start is a different fault family — the OC1 overcurrent fault during acceleration causes are where to look then, not the braking circuit.
  2. Read P06.01 at the keypad. The commissioning sheet is not a readback; the drive holds whatever the last write left. Confirm the live value before deciding anything.
  3. Trace the resistor wiring with the bus verified dead. The manual for the series says the external resistor connects to B1 and B2 only, and it forbids jumping DC- to DC+, DC- to +2/B1 or DC- to B2; +1/DC+ and DC- exist for a common DC bus arrangement. Leave +1, +2 and DC- as the frame's main-circuit diagram shows, and leave the factory link between +1/DC+ and +2/B1 where it was installed unless that diagram says otherwise. Both resistor leads land on B1 and B2 and nothing else shares those terminals.
  4. Measure the element. Lift one resistor lead so no parallel path shadows the reading. Check continuity end to end, then resistance, and compare the measured ohms against the braking-resistor table for the GS23-2010 frame in the manual's wiring chapter. Check any thermal contact wired into the resistor circuit for continuity as well.
  5. Check the duty. Count stops per minute, multiply by the decel time, and compare that duty with the element's datasheet and the documentation's braking data at the measured resistance. The worked example below shows the arithmetic.
  6. Apply the setting, then test. Set P06.01 to 0 and run an unloaded stop, watching the bus reading on the drive's monitor if the model displays one. Bus voltage climbs and the trip fires — back to step 3, the hardware is the problem. The ramp completes on time — the job is done.

Parameters the commissioning sheet touches #

Nothing outside this list changes for a resistor-braked stop; these are the sheet's rows that matter.

Parameter Value on the sheet Role in the stop
P00.21 1, external terminals run and stop come from the terminal strip, so dropping the run input starts the ramp
P00.22 0, decel ramp a stop ramps the output down instead of coasting
P01.13 3.0 the programmed deceleration time, in seconds
P05.01 13.6 motor FLA for the drive's motor thermal model, in amperes
P06.01 0, disabled, with a braking resistor installed hands bus control during the ramp to the braking circuit
P06.44 1, no latch, when STO is used STO latch behavior; no braking role

P05.01 does double duty on a small motor: configuring the GS20 P05.01 minimum motor FLA for small motors walks through that floor. If the sequence needs a ramp that ends above zero speed rather than at it, the GS20 deceleration to non-zero speed settings page covers how that ramp behaves.

Worked example: resistance and duty arithmetic #

Every number in this example is an illustrative input; the real inputs are the resistor nameplate, the measured element resistance and the machine's actual stop rate. Take a 230 V class drive, a ramp of 3.0 s from 60 Hz, one full stop every 20 s, and an element marked 100 Ω and 1,000 W.

The bus of a 230 V class drive sits near the rectified line peak when idle: 230 V × 1.414 ≈ 325 V DC. While the braking chopper conducts, the element sees roughly that voltage, so its pulse power is P = V² ÷ R = 325² ÷ 100 = 105,625 ÷ 100 ≈ 1,056 W. The braking duty is 3.0 s ÷ 20 s = 0.15, so the element's average dissipation is about 0.15 × 1,056 W ≈ 158 W, and the current through the element is V ÷ R = 325 V ÷ 100 Ω = 3.25 A.

Decision from these inputs: the 1,000 W nameplate covers 158 W of average load with wide margin, but the element must tolerate bursts near 1.1 kW lasting 3.0 s — that short-time capability is what the resistor's datasheet and the documentation's braking data govern, and it is where undersized elements fail. Resistance above the table's range starves the braking current — 3.25 A here — and the stop overruns even with the setting correct; resistance below the range pushes more current through the chopper and element than they are rated to carry. Treat the result as an estimate and check it against the element datasheet and the manual's braking-resistor table for the frame.

The decision, case by case #

Wiring traced, measured resistance inside the frame's table, duty inside the element rating: apply P06.01 = 0 and keep it there. That setting plus verified hardware is the entire braking change from the factory set.

P06.01 already reads 0 and stops still overrun: writing it again repairs nothing. Either the element cannot absorb the duty or the programmed ramp is longer than the process accepts; lengthen the ramp only if the sequence tolerates the longer stop, otherwise fit an element with more duty.

Overvoltage trip on the first ramp after disabling stall prevention: an open braking path — a broken element, a lug that never landed on B1 or B2, a failed chopper. Measure the circuit before re-enabling anything.

No resistor installed, or removed for service: stall prevention stays enabled at its factory value; disabled prevention with no absorption path is a guaranteed bus overvoltage trip.

Resistor overheats or its thermal contact opens on repeated stops: cut the stop frequency, accept a longer ramp, or fit a correctly rated element — hardware, not parameters.

Do not repair any of these with a parameter reset: restoring defaults also wipes the terminal and analog configuration the sheet set up, and the sheet's reset entry is a commissioning action, not a fix. And a number outside the sheet's list is not part of this braking configuration; read any such parameter's description in the manual's parameter chapter before changing it, because a parameter number alone is not a commissioning basis.

Questions asked

Can a switch or contactor sit in the braking resistor circuit?

Only if the drive documentation provides for it. An open resistor path is invisible at standstill, but with overvoltage stall prevention disabled the first ramped stop into that open path climbs the DC bus into a trip. Switch a resistor only with the drive locked out for maintenance, never as part of the stop sequence, and keep the resistor permanently connected otherwise.

Does STO remove the need for a ramped stop?

No. STO removes torque capability and the spindle coasts or stops by friction; it does not ramp anything down. The sheet's P06.44 value of 1 sets the STO latch behavior and has no braking role. Use STO for its safety function and produce the controlled stop by dropping the terminal run command so the ramp runs.

How hot should a working braking resistor get?

Warm to hot by design, because its average dissipation equals the regenerated energy per stop times the stop rate — roughly 158 W average on the example 1,000 W element at 15% duty. Discoloration, a burning smell, or a thermal contact that keeps opening means the element's duty rating is exceeded; the fix is a higher-rated element or fewer stops, not a parameter.

Do braking resistor ratings transfer between GS20 frame sizes?

No. Permitted resistance and braking duty are listed per frame size, so a table printed for a smaller or larger GS20 frame does not transfer to the GS23-2010. Use the braking-resistor table in the wiring chapter for the installed frame, together with the dynamic braking documentation the manual references, and compare your measured ohms against that table only.

Keep reading

  • Troubleshooting

    Why intermediate circuit voltage goes out of permitted range

    An intermediate circuit voltage out of permitted range fault means the drive's DC bus left the window its own documentation defines. The timing names the cause: a bus that sinks on acceleration points to the incoming supply, a bus that spikes on deceleration points to regenerative energy, and a slow drift points to aging DC bus capacitors or a failing supply unit. Fix the side the timing names.

    Variable frequency drives

  • Explainer

    Why a motor-side braking resistor works on a PM servo

    Because your motor has a permanent-magnet rotor, it becomes a generator the moment the shaft keeps turning with the drive disconnected: close a three-phase resistor bank across the motor terminals and the generated current produces torque that opposes rotation. An induction rotor loses its field in a fraction of a second, so this is a PM-servo arrangement, built as a fail-safe path that brakes even when the inverter is dead.

    Variable frequency drives

  • Troubleshooting

    Why a VFD DC bus overvoltage fault appears at random

    One ~670 V DC sample sitting between steady ~570 V readings in a 400 V drive's fault log is the fingerprint of a regenerative spike lasting a few milliseconds. An overhauling load through a high-ratio gearbox pumps energy back faster than V/Hz control and the brake chopper can absorb it. Move the drive to sensorless vector control, run auto-tune, lengthen the decel ramp and raise the regen power limit.