Sizing a 480 to 120 V three-phase servo drive transformer
Short answer
Use a dry-type three-phase transformer with a 480 V primary and a 120 V secondary, sized kVA = 1.732 × 120 V × I_line / 1000 per amplifier and summed over the bank, then take the next standard size. Skip SCR-type regulators and energize with the amplifier disconnected, measuring all three secondary voltages first.

On this page
Use a dry-type three-phase transformer with a 480 V delta primary and a 120 V delta secondary, and set its kVA from the servo amplifier's documented input current: kVA = 1.732 × 120 V × I_line / 1000, summed over every amplifier on the secondary, then take the next standard size. Skip the SCR-type voltage regulator; the amplifier maker warns that those introduce conducted noise. Energize the transformer with the amplifier disconnected so you can measure all three secondary line-to-line voltages before anything expensive is attached to them.
Set the kVA from the amplifier's documented input current #
The rated input current comes off the amplifier nameplate and its installation manual, not from the model number and not from the machine's oldest wiring documents. On one real installation the delivered paperwork called for a 220 V input while the amplifiers actually needed the three-phase secondary voltage; reconcile the current diagram and the nameplate before anything else.
Worked example — three servo amplifiers, each with a documented rated input of 10 A at 120 V, 60 Hz, fed from a 480 V three-phase supply:
- kVA per amplifier = 1.732 × secondary line-to-line voltage × 10 A / 1000 = 2.08 kVA
- bank total = 3 × 2.08 kVA = 6.23 kVA
- the common three-phase dry-type series steps 6 kVA to 9 kVA, and 6.23 kVA is already past 6 kVA before any panel load, so the example lands on a 9 kVA unit
If the same secondary feeds contactor coils, relays or a 24 V DC power supply, add those input ratings to 6.23 kVA before you pick. The result is an estimate; check it against NFPA 70, the National Electrical Code, 2023 edition, Article 450, which covers overcurrent protection for transformers, and against the transformer's own catalog data, and confirm the installation with your authority having jurisdiction.
Some drive manufacturers size the servo transformer from peak current during acceleration instead of the continuous rating; how bus voltage and peak current set the transformer size for a servo motor walks through that method. The nameplate's rated input already covers continuous duty; peak-current sizing yields a smaller transformer with less voltage stiffness under load, so follow the drive maker's documented rule either way. The same load-current arithmetic decides sizing a step-down transformer for a 110 V UPS; only the voltages and the load list change.
Choose the construction #
Order a dry-type three-phase transformer, 480 V delta primary, delta secondary at the amplifier's rated input, 60 Hz. A general-purpose distribution transformer does the job; a drive-isolation type adds heavier winding insulation and an optional electrostatic shield between the windings, which helps when the amplifier's rectifier front end distorts the current enough to heat the secondary.
Keep the secondary delta. The amplifier needs three-phase only, and a wye secondary on that line-to-line system would give a line-to-neutral value of 69 V (the line-to-line figure divided by 1.732), which none of the single-phase loads on the bus can use. A delta secondary with no neutral also keeps the secondary bus free of the unbalance questions a neutral would raise.
Why not an SCR-type voltage regulator #
On the installation behind this article, the amplifier manufacturer warned that an SCR-type regulator would create a noise problem, and that warning matches the physics rather than a quirk of one product. An SCR regulator shapes its output by switching the supply part-way through each half-cycle, and that chopping puts conducted noise on the bus that the amplifier's encoder and analog circuits live behind. A transformer converts by turns ratio alone and never switches. A transformer changes the voltage; it does not regulate it, so if your 480 V bus sags badly you solve that at the supply, not at the control transformer.
The open-delta option, and its 57.7 percent limit #
Two single-phase 480-to-120 V transformers wired open delta do produce genuine three-phase power at the secondary voltage, and they are much easier to find than a three-phase unit with that secondary. The cost is capacity: an open-delta bank delivers 1.732 × each unit's kVA rating, which is 57.7 percent of what a closed delta of the same units would carry, and the open corner lets the secondary voltages shift under unbalanced load, which a servo amplifier feels on its input.
Continuing the example, each single-phase unit must be at least 6.23 kVA / 1.732 = 3.60 kVA, so the next standard size, 5 kVA, gives a bank of 1.732 × 5 kVA = 8.66 kVA. The same physics that caps the bank's kVA also decides how big a motor an open delta bank can start; the constraints there apply to your bank too.
Verify before you connect the amplifier #
De-energize, lock out and test for absence of voltage before you open any panel or terminal box; NFPA 70E, 2024 edition, covers that verification and the protective equipment it requires. Then:
- Confirm the required input voltage from the amplifier nameplate and the current wiring diagram. Do not trust older documentation; the 220 V conflict with the nameplate value on this installation was real and was only settled when a corrected diagram arrived.
- Check every device that will sit on the secondary bus. A regenerative shunt rated 120–150 VAC is correct on a drive bus of that voltage and destroyed on anything higher.
- Energize the transformer with the amplifier leads open and measure all three secondary line-to-line voltages. Each pair should read 120 V within the transformer's documented tolerance band.
- Confirm the phase rotation against the wiring diagram before closing the amplifier leads.
- Connect the amplifier, run it and re-measure the input voltage under load. Sag beyond the drive's documented input window means the transformer is undersized for the actual duty.
Grounding and overcurrent protection #
NFPA 70, 2023 edition, Article 450 requires overcurrent protection on the transformer sized from its tables; NFPA 79, the Electrical Standard for Industrial Machinery, 2024 edition, governs the machine control circuit on the secondary, including conductor fusing. Confirm both with your authority having jurisdiction and the machine documentation. Whether you bond one secondary line to ground or run the secondary bus floating changes how a ground fault announces itself; the trade-offs are laid out in grounded versus floating control transformer secondaries in MCCs.
The decision, for each case: one three-phase 480 V delta-to-delta transformer, kVA set from the documented input current and summed over every amplifier plus the panel loads, and no SCR regulator in the path. Where only single-phase units are available, two of them in open delta work if 57.7 percent of their combined closed-delta rating still covers the load. In every case, measure the secondary voltages with the amplifier disconnected before you connect it.
Questions asked
Can three single-phase 480 to 120 volt transformers do the same job as one three-phase unit?
Yes. Wire them delta-delta and the bank delivers three times each transformer's kVA rating, the same as one three-phase unit of equal total capacity. Match the impedance and connection of the three units, and verify all three secondary line-to-line voltages at energization exactly as you would for a single three-phase transformer.
Why did the amplifier manufacturer reject an SCR-type voltage regulator?
SCR regulators control their output by chopping the supply waveform part of the way through every half-cycle. That switching puts conducted electrical noise on the secondary bus, and a servo amplifier's sensitive circuits, encoder signals and analog references among them, sit directly behind it. A transformer changes voltage by turns ratio alone, with no switching, so it adds none of that noise.
What kVA does one amplifier drawing 10 amps at 120 volts need?
1.732 × 120 V × 10 A / 1000 = 2.08 kVA, so the next standard size, typically 3 kVA, covers it with headroom for a few contactor coils or a small power supply. Add any panel control loads that share the same secondary before you round up to the next catalog size.