Explainer
What decides if an open delta bank can start a 25 HP motor
Short answer
In an open delta bank each transformer carries the full motor line current, not the 58% of a closed delta, so a 25 kVA teaser caps the bank at 43.3 kVA of balanced load while the 100 kVA unit carries its single-phase load plus the motor share. Whether the motor starts and survives comes down to terminal-voltage balance through acceleration, not 25 HP against 25 kVA.

On this page
Bank a 25 kVA transformer with an existing 100 kVA unit to feed a 25 HP motor, and the number that decides the application is not the 125 kVA nameplate sum. In an open delta each transformer carries the full motor line current — there is no 58% sharing as in a closed delta — so the small teaser sets the bank's three-phase ceiling while the existing unit carries its 66 kVA single-phase load combined with the motor share. Whether the motor starts and survives comes down to the currents in those two units and the balance of the motor-terminal voltages through acceleration. Here is the current sharing, the arithmetic, and the decision for each case.
Why the teaser carries the full motor current #
In a closed delta the line current is 1.732 times the current in each transformer winding, so each unit carries about 58% of the motor's line current. Remove one unit for an open delta and that sharing is gone: the two remaining windings sit line to line, and each carries a full line current. Two consequences follow.
The teaser must be rated for the bank's line-to-line voltage times the motor's line current, divided by 1000, before anything else is counted. And the bank's balanced three-phase capacity is 1.732 times the smaller unit's kVA: with a 25 kVA teaser that ceiling is 43.3 kVA, whatever the partner's nameplate says. For two identical units the same rule reads as 86.6% of the two nameplates added. A bank rating is never the sum of its nameplates.
What the existing unit really carries #
The motor current through the big unit and its single-phase load current sit at different phase angles, so they add as vectors: the total is larger than either alone and smaller than their arithmetic sum. The conservative screen adds the two currents arithmetically at the bank voltage and compares the result with the unit's rated current, its kVA times 1000 divided by that voltage. A unit that passes the screen is fine on paper; a unit that fails it may still survive in reality, but only measured currents and power factor angles will defend that.
The gap between the nameplate and today's demand is 34 kVA, and it is only a paper margin: converted to current at the bank voltage, the single-phase load takes most of the winding, and the motor's share rides on top. Horsepower will not settle it either. HP is mechanical output; the electrical demand comes off the motor nameplate. Take full-load current from the nameplate — the same number that sets its overload relay, as covered in setting overload relays from motor nameplate full-load current — and take locked-rotor current and acceleration time from the motor data, because the start, not the run, usually sets the voltage dip.
Worked example: 16 kVA at 230 V on an open delta #
Inputs, all from the documented open delta example in the transformer bank capacity reference this article checked: a balanced three-phase load of 16 kVA, a line-to-line voltage of 230 V, and two identical transformers.
The rule in words: in an open delta every transformer carries the full line current; the line current of a balanced three-phase load is its apparent power divided by 1.732 times the line-to-line voltage; and each unit must be rated for that voltage times that current.
The arithmetic:
- Line current: 16,000 VA ÷ (1.732 × 230 V) = 16,000 ÷ 398.4 = 40.2 A.
- Each transformer carries that current at full line-to-line voltage, so each unit needs 230 V × 40.2 A ÷ 1000 = 9.2 kVA.
- For contrast, in a closed delta each winding would carry 40.2 ÷ 1.732 = 23.2 A.
- The next standard single-phase rating above that product is 10 kVA, and two such units deliver 0.866 × 20 kVA = 17.3 kVA as a bank.
Result: the 16 kVA load needs two 10 kVA units in open delta, and the bank tops out at 17.3 kVA.
Decision, with its threshold: specify each unit at no less than the voltage-times-current product — 9.2 kVA in this case — because anything smaller is overloaded by the balanced load alone, before a single-phase load or a start is counted. The same product is the ceiling on your teaser: its rated kVA times 1000, divided by your bank voltage in volts, is the most motor line current it can carry.
What this decides for the 25 HP application #
Four screens decide the bank, and each is arithmetic or a measurement, not a rule of thumb.
- Run screen: motor running kVA is 1.732 times nameplate volts times full-load amps, divided by 1000. It must sit under the teaser's ceiling of 43.3 kVA, and the sharper test is current: full-load amps times the bank voltage must not exceed the teaser's rated kVA times 1000.
- Start screen: locked-rotor amps through both units' impedance plus the source's, checked against your flicker limit and the motor's ability to accelerate. A start draws several times run current for seconds; this is where open delta banks usually fail a motor application.
- Existing-unit screen: rated current minus the single-phase current at the bank voltage leaves the room for the motor share, with the arithmetic sum as the conservative bound.
- Balance screen: measured motor-terminal unbalance at or below 1% with the motor loaded, the point where the NEMA MG-1 derating curve begins.
Voltage balance, not nameplate arithmetic #
With a wye primary the bank draws from two primary phases and the neutral, and neutral impedance displaces the neutral point — which reaches the secondary as magnitude and angle error that the two transformers do not correct. Their own regulation adds a second error: the teaser works at a far larger fraction of its rating than its partner, so the two windings drop different voltages and the secondary voltages come out unequal even on a stiff primary. Choosing a teaser whose impedance and regulation match the existing unit keeps that difference small.
The motor pays in current, not just voltage: winding current unbalance runs six to ten times the voltage unbalance, so a few percent at the terminals becomes double-digit current unbalance and extra winding heat. NEMA MG-1, the U.S. standard for motors and generators, derates a polyphase induction motor on an unbalanced supply following its published curve, and open delta banks are a recognized cause of the condition; the field symptoms are unequal phase currents and overload trips on a motor that measures healthy. NEMA figures unbalance as the largest line-to-line deviation from the average of the three, as a percentage of that average.
Taking those readings means an open terminal box on a running circuit. Under NFPA 70E, 2024 edition, the U.S. workplace electrical safety standard, that is energized work: open the box only after lockout and a verified absence of voltage, and capture the running values only under your site's energized-work permit, with the PPE and the voltage-rated meter the permit names; your site's electrical safety program and the equipment documentation set the rest. Record all three line-to-line voltages and phase currents before the start, through it, and at full load.
The phase-loss case that backfeeds the motor #
Most open delta banks in service are three-unit banks that lost a transformer or a primary phase; the connection keeps three-phase service alive at reduced capacity. The failure to design for is a primary phase lost while your motor is running: the motor keeps spinning, generates into the dead winding, and backfeeds through the teaser to hold the single-phase load — duty that can grossly overload the motor and the small unit while the motor itself runs single-phased. The line currents an ordinary overload relay watches can stay near normal, which is why some phase-loss schemes never see it; why phase loss monitors miss single-phasing on an open delta covers which protection responds on this supply. Give the motor a scheme that does.
The decision #
- Run the open delta when all four screens pass: the teaser's rated current covers the motor's full-load amps, the existing unit passes the conservative sum, the calculated start dip stays inside your flicker limit and the motor's acceleration capability, and terminal unbalance measures at or below 1% under load.
- Build a three-transformer closed delta instead when the start dip or the balance screen fails: three windings share the motor at about 58% each and share the regulation error too. A third unit does not fix a weak neutral or a tilted primary — that work belongs on the source side of the bank.
- Justify the bank with the four screens and the measured voltages, never with the 125 kVA nameplate sum or the 34 kVA gap on the existing unit.
Questions asked
How much capacity does a delta bank lose when one unit fails and it runs open delta?
Two identical units in open delta deliver 86.6% of their added nameplates, which is 57.7% of what the same two units delivered inside the original three-unit bank. A bank of three 25 kVA units therefore falls from 75 kVA to 43.3 kVA when one unit comes out, not to two-thirds. That is why the teaser, not the surviving unit, sizes a mixed bank, and why an open delta is an emergency or light-load connection rather than a planned full-capacity one.
Can I add the single-phase kVA and the motor kVA to check the existing transformer?
Only as a deliberate overstatement. The two currents add vectorially: the root of the sum of their squares plus twice their product times the cosine of the angle between them, so the true total sits below the arithmetic sum. If both loads drew at nearly the same power factor the angle would be small and arithmetic addition nearly exact. A motor's power factor differs from resistance load, so treat the arithmetic sum as the screen and the vector sum, built on measured currents and angles, as the defense.
Should the single-phase load stay on the bank at all?
Prefer to move it when a circuit for that load exists. With only the motor on the bank, both units carry motor current alone, the stacked duty on the big unit disappears, and the single-phase contribution to neutral drop goes with it. The teaser still sets the ceiling at 1.732 times its own kVA, and the start and balance screens still apply, but the bank is then being asked to do one job instead of two.
Do both transformers see the motor's starting current?
Yes. During acceleration both windings carry the locked-rotor line current, so the start screen checks both units, and the voltage dip is the combined result of source impedance and both units' regulation at several times rated current. Winding heating over the few seconds of a start is rarely the limit; the terminal-voltage dip and the motor's ability to accelerate through it usually are.

