How-to
Sizing a three-phase motor to replace a 7 kW DC motor
Short answer
Size the replacement by shaft torque, not by kilowatts. The 7 kW DC motor at 3000 rpm delivers 22.3 N·m, and the three-phase motor and drive must hold that torque continuously from 800 to 2000 rpm, roughly 1.9 to 4.7 kW at the shaft. Check low-speed cooling, the torque curve above base speed, gearbox torque limits and the 380 V winding connection before ordering.

On this page
Size the replacement three-phase motor by the torque the machine needs over its speed range, not by matching 7 kW. At its 3000 rpm rating point the DC shunt motor delivers 9550 × 7 / 3000 ≈ 22.3 N·m, and it turns the machine through the 20:1 gearbox from 800 to 2000 rpm at the motor shaft, which is 40 to 100 rpm at the machine. Whatever motor and drive you fit must hold the measured load torque continuously across that whole span on the 380 V three-phase supply. The steps below turn the DC nameplate, a current record taken on the running machine and the gearbox data into a motor frame and a drive current you can order; the worked example shows the arithmetic for this exact case.
Read the real load before you convert #
The nameplate records what the DC motor could deliver; it does not tell you what the machine actually takes. Measure the demand before ordering anything. Clamp a DC ammeter around one armature conductor and log the reading at every production condition, writing the motor speed and the process load beside each reading. At constant shunt-field flux, armature current rises almost in proportion to shaft torque, so the log converts into a torque profile; the total supply current does not, because it also carries field current. If the DC controller weakens the field anywhere in the working range, current stops tracking torque and you need the motor's torque-speed data instead of a current conversion.
Keep steady and transient duty separate. The torque that accelerates the machine equals the equivalent inertia times the angular acceleration, J_eq × α, which comes out in N·m when J_eq is in kg·m² and α is in rad/s²; log each peak with its duration and how often it repeats.
Treat the 200 V nameplate figure as a supply rating, not an operating point. Multiplying it by a measured current gives electrical input, which includes armature copper loss, field loss and brush and core losses, not shaft power.
Before you open the DC panel or the drive to connect instruments, de-energize, lock out and verify absence of voltage at the terminals; NFPA 70E, 2024 edition, covers the safe work practices for this, and your local authority having jurisdiction and plant procedure set the details.
Worked example: 7 kW at 3000 rpm through a 20:1 gearbox #
Inputs, each with its source:
- Rated shaft power: 7 kW, from the DC motor nameplate.
- Rated speed: 3000 rpm, from the nameplate.
- Working range: 800-2000 rpm at the motor shaft, the stated duty.
- Gearbox ratio: 20:1, the stated coupling to the machine.
- Supply: 380 V, three phase, the stated system.
The rule, in words: shaft torque in N·m equals 9550 times shaft power in kW divided by shaft speed in rpm, and rearranged, the power a constant-torque load draws at any speed equals the torque times that speed divided by 9550. It is the identity P = T × ω with ω in radians per second; 9550 is the unit factor between kW, rpm and N·m.
The arithmetic:
- Rated motor torque: 9550 × 7 / 3000 = 66,850 / 3000 = 22.3 N·m.
- Machine speed span: 800 / 20 = 40 rpm at the slow end, 2000 / 20 = 100 rpm at the fast end.
- Power with rated torque held at every speed: at the slow end, 22.3 × 800 / 9550 = 17,840 / 9550 ≈ 1.87 kW; at the fast end, 22.3 × 2000 / 9550 = 44,600 / 9550 ≈ 4.67 kW.
- Gearbox output torque at the rating point, before losses: 20 × 22.3 = 446 N·m; multiply by gearbox efficiency as a fraction for the real figure.
Result: the old motor's rating point is that torque at rated speed, the machine runs at 40 to 100 rpm, and the gearbox can be called on for up to 446 N·m at its output.
Decision: if the current record shows the machine taking close to rated torque continuously, the replacement is a motor and drive that hold 22.3 N·m from the slow end to the fast end of the range, about 1.87 kW of shaft work at the slow end and 4.67 kW at the fast end. If the record shows a lighter duty, the measured torque decides and the DC nameplate stands only as the ceiling. These figures are nameplate estimates; check them against the gearbox and motor documentation and against the wiring rules that govern the installation before ordering.
The sizing steps #
Work through them in order; each step feeds the next.
- Set the torque target. Take the largest continuous torque in the log as the target the new motor must meet. The old motor's rating point is the most load this machine has ever been proven to carry, so it also works as the ceiling.
- Sort the envelope. With roughly constant torque, power rises with speed, so the fast end sets the power rating and the slow end sets the cooling question. With roughly constant power, torque climbs as speed falls and the slow end sets the torque. Log peaks separately from the continuous figure.
- Pick the base speed. Fit an inverter-duty motor; NEMA MG-1 Part 31 covers motors fed from drives in the North American market. On a 50 Hz supply the common base speeds are about 2900 rpm for two poles and 1450 rpm for four poles, and the whole working range fits below a two-pole base with no field weakening anywhere. A four-pole motor leaves the fast end of the range above base speed, where available torque falls. On a 60 Hz supply the same sums use about 1740 rpm for four poles and 3480 rpm for two poles.
- Check the curve above base speed against the target. Illustration, with the demand at the full rating point: a 7.5 kW two-pole frame holds 9550 × 7.5 / 2900 ≈ 24.7 N·m everywhere in the range, while a 5.5 kW four-pole frame holds 9550 × 5.5 / 1450 ≈ 36.2 N·m up to base speed and only about 36.2 × 1450 / 2000 ≈ 26 N·m at the fast end if constant power held, so the four-pole pick clears the target only if the maker's curve confirms it at 2000 rpm. Above base speed the drive sits at its voltage ceiling and flux falls with frequency; the classic symptom is a drive reading low output voltage with the motor short of torque, the pattern set out in why a VFD shows low output voltage and the motor has no torque.
- Verify continuous duty at the slow end. A shaft-mounted cooling fan slows with the motor and moves much less air, so continuous torque there can fall below the catalogue figure; hold the slowest continuous duty against the motor's curve at that speed and specify a separately powered blower or the next frame up if it sits near the limit. The same torque-first view of low-speed duty is set out in a torque-based VFD sizing guide for low-speed drilling. Confirm the nameplate duty marking too: S1 under IEC 60034-1 is the continuous rating, and any other duty letter is a limited-duty figure.
- Size the drive on current, then on braking. Its continuous output current must cover the chosen motor's rated current, and its overload rating must cover each logged peak for its stated time; a kilowatt label only matches one motor at one voltage and speed. This current-first method is the same one used in sizing a VFD for a three-phase motor on single-phase input. If the load can overhaul on deceleration, add the drive maker's braking resistor or regenerative option, sized for the braking energy and the cycle rate.
- Check the mechanical train. Keeping the 20:1 ratio leaves the machine speeds unchanged; confirm the gearbox's continuous and peak torque ratings and its permitted input speed span cover the new motor, and set the drive's torque or current limit so a jam cannot pass more torque than the gearbox allows. Check shaft size, key and coupling fit, and if the machine must hold position at standstill, fit a holding brake, because running torque is not a brake.
- Connect the winding and the circuit for 380 V. Set the leads to match the supply, which decides the current the drive must feed, the same choice worked through in wye or delta winding for a 200 hp 480 V motor. Where NFPA 70, the National Electrical Code, 2023 edition, governs, its Article 430 covers conductor and protection sizing for the new motor circuit; confirm the requirement with your local authority having jurisdiction and the equipment documentation.
The decision for each case #
Machine close to rated torque across the whole range: order the 5.5 kW four-pole inverter-duty motor with the maker's written confirmation of torque at the fast end, or the 7.5 kW two-pole frame if you want every speed below base with no curve to verify. Either way, the drive's continuous current matches the chosen motor, and its torque limit is set to what the gearbox allows.
Lighter duty on the record: re-run the worked example with the measured torque in place of the nameplate figure and take the smallest frame that clears it at the slow end, on cooling, and at the fast end, on the curve. The measured number decides; the DC nameplate does not.
Short peaks dominating the record: size the continuous duty on the thermal figure, match the drive's overload rating to each peak's size, duration and repetition, and if the machine overhauls on deceleration, order the braking hardware with the drive.
Questions asked
What is the torque formula in imperial units?
Use T (lb·ft) = 5250 × P (hp) / n (rpm); 5250 does for horsepower and rpm what 9550 does for kilowatts and rpm. For example, a 10 hp motor rated 2500 rpm delivers 5250 × 10 / 2500 = 21 lb·ft. To compare with a metric figure, 1 lb·ft equals about 1.356 N·m.
Does the same kilowatt rating mean the same motor?
No, the torque depends on the speed the rating is quoted at. Taking the 7 kW example figure: about 23 N·m at a 2900 rpm base, about 46 N·m at 1450 rpm and about 70 N·m at 960 rpm. That is why the conversion is done at torque and speed, and why two motors with the same kilowatt label are not interchangeable.
What does the duty marking on a motor nameplate mean?
IEC 60034-1 grades duty with S-numbers. S1 is continuous duty: rated load for an unlimited period. S2 is short-time duty: rated load for a stated number of minutes from cold, then a rest. A short-time power figure is always higher than the same frame's continuous rating, so an S2 number must never be compared against a machine that runs without rest pauses.
Does the replacement have to keep the same gearbox ratio?
No. The ratio is a design variable: raising it reduces the torque the motor must produce and multiplies more at the output, while the motor turns faster for the same machine speed. For example, doubling the ratio halves the motor-side torque target but doubles the motor's top speed. Re-run the worked example with the new ratio before changing it, and recheck the gearbox's input speed limit.

