Sizing a VFD for a 1 HP 220 V motor on single phase
Short answer
Size the drive by output current, not horsepower. This 1 HP, 220 V, three-phase motor draws 2.5 A at full load, so the drive needs at least 3.6 A of continuous output current; a 2 HP, 230 V single-phase-input frame rated about 7.5 A carries the single-phase rectifier's extra heat with room to spare. Stay on 230 V single-phase input rather than a 120 V voltage-doubler input.

On this page
Size the drive by its continuous output current, not by the horsepower printed on either nameplate. Your motor reads 1 HP, 208-220/440 V, 2850/3450 rpm, and draws 2.5 A per line on the 220 V connection, which after margins sets a minimum drive output of 3.6 A at 230 V. Any single-phase-input frame in that voltage class listing at least that much output current will run it; in this size the 2 HP frames of dedicated single-phase-input series, rated near 7.5 A, are the practical pick, because the surplus rating pays for the rectifier heat that single-phase input adds. Stay on the full-voltage single-phase supply rather than a 120 V voltage-doubler input.
What the nameplate fixes #
Read the plate as a sizing document before shopping. One horsepower is 0.75 kW at the shaft. Dual voltage means one stator winding that reconnects: parallel for the low-voltage connection, series for the high-voltage one, which is why the line current halves between the two columns of the plate. The two speeds are the two-pole winding at 50 Hz and at 60 Hz, so on North American shop power the shaft runs at the 60 Hz figure. Connect the motor for the low-voltage hookup. A drive in that voltage class cannot feed the series connection usefully: it tops out near its rated output voltage, the volts-per-hertz ratio falls to half, and torque goes with it. The nine-lead arrangement of a dual-voltage motor and where each lead lands is covered step by step in wiring nine-lead dual-voltage motor leads to a VFD (article:wiring-nine-lead-dual-voltage-motor-leads-to-a-vfd).
Size by output current, not horsepower #
The rule you can carry to any motor: the drive's published continuous output current, at the output voltage you will actually use, must exceed the motor's full-load current with a margin for continuous duty and transients. The 1.5-times-horsepower rule heard in North American shops is a shortcut for the same calculation under assumptions about typical motor current and single-phase rectifier heating; it overbuys on an efficient motor like this one and can undershoot on a slow, high-current one. The nameplate current is the exact number.
One datasheet detail matters here. If a drive lists only a three-phase-input rating, manufacturers commonly require halving the continuous output current when the input is single phase, because the rectifier and DC bus then see ripple current a three-phase feed never produces. Dedicated single-phase-input frames have that derate already built into their published ratings, which is why the table below only considers those.
Worked example: a 2.5 A, 220 V, 1 HP shaper motor #
Inputs:
- Motor full-load current from the plate: 2.5 A per line on the 220 V connection, three-phase, 60 Hz.
- Service factor on the drive side: 1.15, an example allowance for continuous duty at rated load.
- Transient margin: 1.25, an example allowance for acceleration and cutter-head load steps.
Rule in words: multiply the full-load current by both margins; the product is the smallest continuous output current the drive may list.
Arithmetic:
- 2.5 A × 1.15 = 2.875 A
- 2.875 A × 1.25 = 3.59 A, which rounds up to 3.6 A
Sanity check the plate against physics: √3 × 220 V × 2.5 A = 953 VA, about 0.95 kVA into the motor at full load, consistent with 0.75 kW of shaft output through a typical older motor's efficiency and power factor.
Result: any drive listing at least 3.6 A of continuous output current at 230 V, three-phase output runs this motor.
Decision: typical 1 HP frames of dedicated single-phase-input series list about 4.2 to 4.8 A, so they clear the bar on paper. The frame to buy is still the 2 HP one, near 7.5 A, because on single-phase input that surplus is rectifier and DC-bus headroom, not motor power.
Why single-phase input needs that headroom #
On three-phase input, six rectifier diodes share the work and the bus sees low ripple. On single phase, two diodes at a time carry every load peak, the DC bus ripple grows, and heating in the rectifier and the bulk capacitors rises with it. The input current also runs higher than the output current on these small drives, because the line current flows in narrow peaks rather than a smooth sine; why VFD input current can be higher than output current (article:why-vfd-input-current-can-be-higher-than-output-current) walks through that arithmetic. The rectifier, bus and inverter stages behind all of this are covered in how a VFD works: rectifier, DC bus and inverter stages (article:how-a-vfd-works-rectifier-dc-bus-and-inverter-stages).
The bus voltage tells you what each input really delivers. On direct rectification the bus sits near the supply peak — √2 times the line voltage, roughly 325 VDC on this supply. A voltage doubler on 120 V reaches roughly 340 VDC, close to the same place. Heating is the catch: pushing the same power through half the input voltage doubles the current, and resistive heating goes with the square of the current, so four times the heat lands in the rectifier and everything upstream. That is why 120 V input is fine at 1 HP and a poor choice above it.
Input options compared #
| Shop supply | How the drive builds its bus | Bus voltage | Verdict for this 1 HP motor |
|---|---|---|---|
| 230 V single phase | direct rectification | about 325 VDC | preferred; simplest wiring and least rectifier stress |
| 120 V single phase | doubler-type drive with the target output voltage, for example the KB Electronics KBDF-24D class | about 340 VDC | acceptable at 1 HP; move up a voltage class for anything larger |
| 115/120 V single phase into a drive without a doubler | direct rectification | about 163 VDC | cannot reach the needed output voltage; not usable for this motor |
Wiring, conductors and grounding #
De-energize the supply, lock it out and verify absence of voltage at the drive terminals before opening anything; the DC bus capacitors hold about 325 VDC after the power goes off, so wait the discharge time the manual states before touching power terminals.
Feed the drive from a two-pole breaker with two hots and a protective earth conductor to the drive's line terminals, marked R and S on many frames and L1 and L2 on others; the manual's terminal drawing governs. Wiring a VFD R S T input from a 240 V single-phase supply (article:wiring-a-vfd-r-s-t-input-from-a-240-v-single-phase-supply) shows that layout terminal by terminal. Size the input conductors at 125% of the drive's rated input current, which is what NFPA 70, the National Electrical Code, Article 430 Part X on adjustable-speed drives requires for the branch serving the drive; confirm the current edition and any local amendments with your authority having jurisdiction and the drive manual. Note the basis: 125% of the drive's input rating, not of the motor's full-load current, because on these small drives the input current runs above the output.
From the output side, U, V and W go to the three motor leads, one motor per drive, and the protective earth lands on the motor frame, bonded to the same ground the drive chassis uses. Keep the motor leads under about 15 m. Longer leads let the PWM switching edges hammer the winding insulation; past that length, lower the drive's carrier frequency setting or fit a dv/dt filter on the output, and on an old winding confirm the insulation system is rated for inverter duty before relying on it.
Parameters to set before the first run #
Keypad defaults on small drives are often European, with a 50 Hz base, so set the motor data group to the plate before the first run:
- Rated voltage: the low-voltage connection value from the plate.
- Rated current: the nameplate full-load current. This number also draws the electronic overload curve, which is why a VFD motor overload current setting takes nameplate FLA (article:why-a-vfd-motor-overload-current-setting-takes-nameplate-fla).
- Rated power: 0.75 kW.
- Rated frequency: 60 Hz, and set the maximum output frequency to match it.
- Rated speed: the 60 Hz nameplate speed, 3450 rpm on this plate, which the drive uses for slip compensation.
Then run the motor unloaded and slowly, confirm rotation direction and steady current, and only after that put the cutter head on.
The decision for each case #
- Shop supply is the full single-phase feed: buy a 2 HP frame from a dedicated single-phase-input series, continuous output near 7.5 A, well clear of the minimum; connect the motor low-voltage, program the 60 Hz motor data, size the input conductors at 125% of the drive's input current.
- Shop has only 120 V: the same current rule applies; choose a doubler-type drive with the target output voltage that clears the minimum. At 1 HP this is acceptable, and it is the point beyond which a higher-voltage circuit earns its keep.
- You already own a larger three-phase-rated drive: halve its published continuous output current for single-phase input and check it still clears the minimum; if it does, it will run this motor without buying anything.
Questions asked
Does a 1 HP rated single-phase-input VFD run this motor, or must it be a 2 HP frame?
Either works if the datasheet's continuous output current clears the minimum that the nameplate current, a 1.15 service factor and a 1.25 transient margin set. Typical 1 HP frames in dedicated single-phase-input series list about 4.2 to 4.8 A of output and will run it. The 2 HP frame near 7.5 A is chosen for rectifier and DC-bus headroom on single-phase input, not because the motor needs more power.
Can the drive run the motor connected for the 440 V hookup?
No. A drive in the lower voltage class tops out near its rated output voltage, and the series connection is built for twice that. Feeding it half its designed voltage halves the volts-per-hertz ratio, so torque collapses long before rated load. Use the low-voltage parallel connection with a drive matched to it, and set the drive's rated motor voltage to match that connection.
Is an oversized drive harmful to a smaller motor?
No, provided the drive's motor data group holds the smaller motor's rated current, because that is the number the electronic overload curve follows. An oversized frame adds rectifier and DC-bus headroom, which is genuinely useful on single-phase input. The habit to avoid is copying the drive frame's horsepower into the motor parameters; those parameters describe the motor, never the drive.
Can one VFD feed two motors, run one at a time?
Not as a routine setup. The drive's motor model and its overload protection assume the one motor described in its motor data, and opening the output circuit under load stresses the inverter. Run one motor per drive output. Switching between machines needs the drive's own documentation to sanction the scheme, typically with interlocked contactors and the drive at zero speed.
What changes if the shop only has 120 V?
The current rule does not change: pick a doubler-type drive with 115/120 V input and 230 V output whose continuous output current clears the same minimum. The doubler charges its bus to roughly 340 VDC, close to what direct rectification of the higher supply gives. At 1 HP that is acceptable; above 1 HP, run the higher-voltage circuit instead, because rectifier heating rises with the square of the input current.