Troubleshooting
Soft starter ground fault at crossover points to motor data
Short answer
Set the starter's rated motor current to the motor nameplate value (305 A in this case, not the 315 A starter rating) and match the trip class. Ground fault detection and the thermal motor model both calculate from that entry, so one wrong value produces both symptoms.

On this page
Enter the motor nameplate full-load current, not the starter's frame rating, in the starter's motor data, and set the trip class to match the real start time. On this installation, two 3RW44-46-6BC-44 soft starters rated 315 A each drive 250 hp motors whose nameplate current is 305 A. That 10 A gap matters because the ground fault monitor and the thermal motor model both calculate from the same entered current, so one wrong value produces a ground fault warning at the bypass crossover and a thermal motor model overload on stop, even when the cables megger clean. The same current-setting discipline that applies when you set an overload relay from the nameplate applies here; see setting overload relays from motor nameplate full-load current.
Reading the two symptoms together #
The pattern in this case is consistent: the ground fault warning appears just before the contactors switch over, the motor then runs normally in bypass, the megger test on the disconnected cables passes, and a stop command produces a thermal motor model overload trip. Both starters behave the same way, which points to a shared configuration practice rather than two independent cable faults.
- Ground fault warning only at crossover, then normal running: the run-state monitor is evaluating a wrongly scaled or unbalanced current at the moment bypass closes.
- Megger test passes on disconnected cables: no insulation fault; the alarm is calculated, not measured to earth.
- Thermal model overload on stop: the model has been accumulating heat against a wrong current entry or a wrong trip class, and the trip displays at the stop state change.
- Identical behavior on two starters: common cause, almost certainly the motor data entry.
Why one entry produces two faults #
The ground fault function on this soft starter series is active only in the run state, after startup is complete. It does not use a dedicated residual current sensor; it derives the earth current from the three measured phase currents, where a sum or asymmetry that should be near zero is treated as earth current. If the entered rated motor current does not match the real load, or the current measurement is disturbed as the thyristors hand over to the bypass contacts, the calculated value can cross the threshold with no insulation fault present. A related computed-alarm case on drives is covered in why a drive trips ground fault with good megger readings.
The thermal motor model integrates current against the entered rated current and the selected trip class. If the current is entered too high or too low, or the class is too short for a high-inertia start, the model reaches its limit. Because it is evaluated continuously, the trip can appear at the stop command rather than when the heat was added. Trip class definitions themselves are explained in reading overload relay trip classes and curves.
Worked example: the current entry #
The starter is rated 315 A. The motor nameplate reads 305 A at the connected voltage. Suppose the commissioning engineer entered the starter's 315 A rating instead. The scaling error on the ground fault calculation is 315 divided by 305, about 1.03, a 3 percent skew: the monitor treats any computed earth current as 3 percent larger than a correctly scaled unit would. The thermal model running against the higher entry underloads the model by about 3 percent, delaying or masking trips. If instead the entry were the starter rating while the true load current sits near the nameplate value, both functions are systematically off by the same 10 A, which is exactly the kind of small, shared error that shows up only as marginal alarms at transitions. Enter 305 A, the nameplate value for this motor, in the rated motor current field, and leave the starter's frame rating out of the motor data entirely.
How to isolate the cause #
- Establish whether the machine is new under commissioning or an established running installation. New points to configuration or wiring; old points to degradation or a changed load.
- Open the motor data in the starter and compare each entry with the nameplate, above all the rated motor current (the nameplate value here) and the active parameter set for the motor. Correct any mismatch.
- Review the thermal motor model settings: trip class and the motor protection parameters. Match the class to the measured starting time and the load inertia; a high-inertia start needs a longer class than a default.
- Review the ground fault threshold and response. Keep the response on warning while you diagnose; do not disable the function outright without a protection concept behind that decision.
- Check the current measurement path: terminal torque on the line and load lugs, and that all three phase conductors connect symmetrically through the starter. Loose large lugs create a phase imbalance that reads exactly like earth current at the moment bypass closes and the current steps up.
- Confirm the earthing and shield connections follow the manufacturer's installation manual for this model.
- Read the starter's phase current display during a run and compare the three values. A spread beyond a few percent at crossover is the reading that matters.
- Repeat a start and record the display message, the point at which it appears and the load current.
Verifying the fix #
Start the motor with the ground fault response still on warning. Expected result: no warning at crossover. After bypass, compare the three displayed phase currents: balanced, with the total at or below the nameplate full-load current under load. Stop the motor several times, including after a loaded run: no thermal model overload trip. Check the model's utilization indication after a start: it falls back toward zero as the motor cools, and it does not climb from one start to the next. Once the runs are clean, restore the ground fault response to the intended protective action and repeat one start.
Pitfalls on this frame size #
- Entering the starter's 315 A frame rating instead of the motor's nameplate value skews both the ground fault scaling and the thermal model.
- Leaving a default trip class on a high-inertia load produces thermal trips with healthy cables.
- A passing megger test proves insulation only; it says nothing about how the starter computes current, so it cannot close a calculated alarm.
- Leaving the ground fault on warning hides the error rather than fixing it; treat warning as a diagnostic state only.
- If the starter also uses a current limit for the ramp, set that limit against the real starting current demand, as covered in setting a soft starter current limit without overheating the motor.
One safety note: before opening the starter cubicle or any motor terminal box to check terminals or disconnect cables, de-energize the feeder, lock it out and verify absence of voltage with a tested instrument, per NFPA 70E, 2024 edition; confirm the exact work requirements with your authority having jurisdiction and the equipment documentation.
Decision #
Enter the rated motor current from the nameplate, never the starter's frame rating, set the trip class from the measured start time, and verify balanced phase currents at the display. If both starters still show a ground fault at crossover after that, move to the measurement path: terminal torque and symmetric conductor routing. The megger-clean result already rules out the cables.
Questions asked
Why does the ground fault appear only just before the bypass contactors close?
Ground fault detection on this soft starter family is a run-state function: it starts evaluating when startup is complete and the unit moves to the bypass state. It is not active during the ramp. So a warning that shows at crossover is the monitor taking over, and it reacts to the current entry or an imbalance in the measurement, not necessarily to a real earth fault.
The cable megger test passed, so why does the starter still show a ground fault?
A megger reading proves the insulation resistance of the disconnected cable. The starter does not measure leakage with a residual current sensor; it derives the earth current from the three measured phase currents. A wrong rated motor current entry or an unbalanced current path can cross the threshold with perfectly healthy insulation.
Why does the starter trip on thermal motor model overload when I stop the motor?
The thermal model integrates measured current against the entered rated current and the selected trip class continuously, including during the run. If the rated current is set too low or the class is too short for the real start time, the model reaches its limit and displays the trip when the state changes at stop, even though the heat accumulated earlier.
Should I leave the ground fault response set to warning after fixing it?
No. Warning-only is a diagnostic step that displays the message without protective action, which is how it masked the configuration error. Once you have clean starts, a balanced current display and no thermal trip on stop, restore the response to the protective action your protection concept calls for, then repeat one start to confirm.