Current IntelPower LibraryShop main store

How-to

Testing 3RB2066 overload relay contacts without power

Motors and motor starters Published 6 min read By Current Intel engineering team

Short answer

Yes. The 3RB20/3RB21 electronic overload family has an internal power supply, so the contact check needs no auxiliary voltage: shift the trip slide from position 1 to position 0, read 95-96 open and 97-98 closed on a continuity meter, then confirm both change back on reset.

On this page
  1. Can you test a 3RB2066 without any auxiliary supply?
  2. Which contact is 95-96 and which is 97-98?
  3. How do you move the trip slide to simulate a trip?
  4. What readings prove the contacts work?
  5. What does a passing test look like with real readings?
  6. What does the no-power test leave unverified?
  7. How do you power the relay for an energized test?
  8. Questions asked

You can bench-test a 3RB2066 overload relay with nothing connected to it. The 3RB20/3RB21 electronic overload family has an internal power supply, so the auxiliary contacts change state with no control voltage present: shift the trip slide by hand from position 1 to position 0, read terminals 95-96 and 97-98 with a multimeter in continuity mode, and confirm both pairs change back on reset. This article gives the dead-relay procedure, the readings that pass, the readings that condemn the relay, and exactly what a no-power test cannot prove.

Can you test a 3RB2066 without any auxiliary supply? #

Yes: the 3RB20/3RB21 solid-state overload relays have an internal power supply, so no additional supply voltage is required, and this contact test runs on a relay that is completely de-energized with nothing wired to any terminal.

There is no auxiliary feed to connect and nothing to switch on before the check. Do not apply an external voltage to the auxiliary terminals to help the meter: a continuity or resistance range drives its own small test current through the probes, and an outside source on those terminals can damage the meter or the relay's contact circuit. The trip slide moves the contact assembly mechanically, so the test does not depend on the electronics at all — a relay with a dead measuring circuit still passes or fails this test purely on contact condition. How the internal supply draws its power matters only for an energized functional test, covered in the last section.

Which contact is 95-96 and which is 97-98? #

95-96 is the normally closed contact that opens when the relay trips, and 97-98 is the normally open contact that closes on trip — the assignment IEC 60947-4-1, edition 2018, fixes for the auxiliary contacts of overload relays.

IEC 60947-4-1 is the standard covering contactors and motor-starters, and the numbering exists so any starter behaves the same way on a trip: the NC contact breaks the coil circuit, the NO contact raises the trip signal. The same numbers are printed beside the terminals on the relay body, and the printed marking is the final reference for your unit. In the starter, 95-96 sits in series with the contactor coil so an overload drops the starter, while 97-98 feeds a trip lamp or PLC input; wiring overload relay contacts to the coil and the PLC shows that circuit in detail.

How do you move the trip slide to simulate a trip? #

Shift the slide sideways, from left to right, so it moves from position 1 to position 0; do not push it, because the mechanism is a lateral slide rather than a button, and the window reads 1 healthy and 0 tripped.

An arrow on the relay marks the healthy and trip positions, so you can confirm the state visually before probing anything. Once the slide sits at position 0 the relay is in its tripped state and the contacts have changed over exactly as they would after a real overload — the difference is that nothing heated and no current flowed. The reset button returns the relay to the healthy state for the second half of the test.

What readings prove the contacts work? #

With the slide at position 1, continuity across 95-96 and an open circuit across 97-98 are the correct healthy readings; with the slide at position 0 the two readings swap, and a reset swaps them back. Run the sequence on a dead relay, in this order:

  1. Isolate and lock out the starter's feeder and control circuit, open the enclosure, and test for absence of voltage at the relay terminals before touching any of them — the entire test is performed de-energized.
  2. Set the multimeter to continuity or low-resistance mode, short the probes together, and write down the lead resistance it shows; you subtract that value from every closed-contact reading.
  3. With the slide at position 1, probe 95-96: the meter shows continuity, a beep or a low ohm reading.
  4. Still at position 1, probe 97-98: the meter shows an open circuit, usually displayed as OL.
  5. Shift the slide from position 1 to position 0, left to right, without pushing it.
  6. Probe 95-96: now open. Probe 97-98: now continuity.
  7. Press the reset button until the window shows the healthy position, then re-probe both pairs: 95-96 closed again, 97-98 open again.

Any pair that fails to change state in either direction condemns the relay. A solid-state overload is a sealed unit, so a stuck or open contact means a replacement, not a repair.

What does a passing test look like with real readings? #

A pass is a stable, low reading on the closed side and OL on the open side in both states: in the worked example below, 0.35 Ω measured less 0.20 Ω of lead resistance leaves about 0.15 Ω across the closed contact. The numbers are illustrative readings from a handheld DMM — your meter and leads will read differently:

  • Setup: meter in low-resistance mode; the probes shorted together read 0.20 Ω, the lead resistance.
  • Slide at position 1: 95-96 reads 0.35 Ω, so the contact path is 0.35 Ω - 0.20 Ω = 0.15 Ω — closed. 97-98 reads OL — open.
  • Slide shifted to position 0: 95-96 reads OL — open. 97-98 reads 0.42 Ω, so the contact path is 0.42 Ω - 0.20 Ω = 0.22 Ω — closed.
  • After reset: both pairs return to the position-1 readings.

Decision for these numbers: the relay passes, because both pairs changed state with stable sub-ohm readings on the closed side. The criterion is the state change plus a reading that holds steady while the probes stay down; a closed-expected reading that flickers or wanders fails the contact even when the beeper sounds.

What does the no-power test leave unverified? #

The slide test proves the contact mechanics and none of the trip electronics: overload, phase-failure and phase-asymmetry detection, plus the current dial setting and trip class, pass no current through your probes and stay unproven.

The SIRIUS manual for the 3RU/3RB overload relays lists what makes these relays trip: overload, phase asymmetry, phase failure, ground fault on the 3RB21, and internal fault on the 3RB20. A relay with a dead measuring circuit can pass the slide test and then refuse to trip in service, so treat this bench check as a contact test before wiring, not a functional test before return to service. To prove the trip function, push a known current through the main circuit and time the trip — the procedure in thermal overload relay current injection test in a 25°C MCC does exactly that.

How do you power the relay for an energized test? #

You never wire a separate control supply: because the supply is internal, an energized functional test powers the relay by pushing current through its main-circuit terminals, the ones marked on the relay body, never through 95-96 or 97-98.

The auxiliary contact numbers carry no supply role, so do not infer a feed voltage or a feed terminal from them. For the bench contact test the answer is zero volts and zero wiring. For the injection test, connect the test set to the main-circuit terminals using the markings printed on the relay for your exact order number. If a procedure tells you to feed a control voltage into the auxiliary terminals of a 3RB20/3RB21 to make it work, that procedure belongs to a different device.

Questions asked

Does pressing the test button on a healthy 3RB2066 change the auxiliary contacts?

There is no auxiliary contact that monitors the test button's status, so a button press gives you nothing to measure across 95-96 or 97-98. The trip slide is the mechanical way to move both contacts on the bench, and the relay window is your reference for which state you are in while probing.

What if both 95-96 and 97-98 read closed while the slide is at position 1?

Check the slide and the window first: if the relay is already tripped, both readings are normal for that state and you should reset it and measure again. If the slide truly sits at position 1 and 97-98 still shows continuity, the signal contact is stuck closed and the relay fails the test — replace it rather than trying to service the sealed contact block.

What does it mean if 95-96 stays closed after the slide moves to position 0?

The normally closed contact is welded or stuck. In a starter that contact sits in series with the contactor coil, so a real overload would trip the electronics while the starter keeps running — the exact failure the relay exists to prevent. That unit fails the bench test; replace it and do not return it to a live starter.

Does the same no-supply bench test apply to the 3RB21?

Yes. The internal-power-supply statement covers the whole 3RB20/3RB21 solid-state family, so the 3RB21 contact test runs identically: shift the trip slide, probe 95-96 and 97-98 in continuity mode, and confirm both pairs change state and change back on reset.

Keep reading

  • How-to

    Wiring overload relay contacts to the coil and the PLC

    The overload relay's NC trip contact (95-96) belongs in series with the contactor coil so a trip drops the motor out even while the PLC still commands run; the NO auxiliary (97-98) is a separate status input to the PLC. A PLC input is not overload protection, because no general-purpose controller input is a listed motor overload device, so a panel wired the other way needs rewiring.

    Motors and motor starters

  • Troubleshooting

    Why a three-phase motor starter trips on a repeatable schedule

    A trip that repeats on the same schedule is an event you can capture: check the motor dead, then watch the meter and the relay flags at the moment of the stop and classify it as an overload trip, a phase-protection dropout, a latch drop or power at the motor with no run. In the confirmed case this pattern came from, the cause was a short damaged wire segment in the starter switch, and the motor was fine.

    Motors and motor starters

  • Selection guide

    Overload relay range selection for an 18.5 kW motor

    Select the relay by the motor's nameplate full-load current, not by kilowatts: pick the adjustable range that brackets that current away from both dial ends, then set the trip class from the measured acceleration time — class 10 for starts under 10 seconds, class 20 up to about 20. An 18.5 kW motor on a 400 V supply works out near 35 A; verify against the nameplate before you buy.

    Motors and motor starters