Explainer
Thermal overload relay current injection test in a 25°C MCC
Short answer
There is no published correction factor from a 25 °C motor-control centre to a 40 °C curve basis, and none may be invented. Verify an installed thermal overload by injecting current through it with a calibrated meter and judging each trip time against the manufacturer's upper and lower tolerance limits. Use a preheat toward the curve basis only where the manufacturer documents one; otherwise the result is recorded as inconclusive.
On this page
There is no standard field correction that converts an overload test taken in a 25 °C motor-control centre to a 40 °C curve basis, and no test procedure should pretend otherwise. The test that works removes the ambient question instead of correcting for it: inject current through the installed overload, measure that current with a calibrated meter, judge each trip time against the manufacturer's published upper and lower tolerance limits, and settle the cold-bucket starting condition one of two ways — a preheat the relay manufacturer documents, or a result logged as inconclusive. Where that basis comes from, what the relay's construction changes, and how the test and its decisions work are laid out below.
Where the curve basis comes from #
Overload heater documentation states the ambient at which the motor carries its rated load, and that basis is normally 40 °C; the published curves are drawn to protect a motor running warm from that starting point. A motor room held for human comfort puts the starter buckets near 25 °C — 15 °C below the curve basis. A bimetal element that starts cooler has bent less for the same current, so an uncompensated relay tested cold tends to trip late against the warm curve, with the gap widest at the low-current end of the overload region. Physics gives the direction but not a magnitude: the offset depends on element geometry, heater alloy and the compensation design, and none of those are printed on the curve sheet. That is why no standard correction exists, and why deriving one at the bench is a guess wearing a decimal point.
The stakes are the motor, not the paperwork: NFPA 70 (the National Electrical Code), 2023 edition, Article 430 treats motor overload protection as a function separate from the branch short-circuit and ground-fault protection, and the overload curve is what carries that duty. Confirm what your installation requires with the authority having jurisdiction and the relay's documentation. The acceptance band — the upper and lower limits drawn around that curve — is the manufacturer's tolerance, and how the curves and their trip classes are drawn is its own read: Reading overload relay trip classes and curves.
What the relay's construction changes #
Ambient-compensated bimetal relays carry a second bimetal strip that sees the bucket's heat but carries no motor current. It sits behind the trip bar and bends with ambient temperature at the same rate as the current-heated element, so the distance the element must travel to trip the mechanism stays constant and the trip point is designed not to move with ambient temperature. For a compensated relay, the cold bucket largely drops out of the test and the band result is final. Compensation covers ambient only: it does not erase heat already stored in the relay after hours of running, so test from a rested state and log that state.
Uncompensated bimetal relays and melting-alloy units have no such second element, so ambient temperature moves them directly. A melting-alloy relay also has no adjustment once its heater is selected; acceptance lives in the manufacturer's method, and a unit that misses the band is replaced. Identify the construction from the relay's own documentation before interpreting any result, and do not assume compensation in an older NEMA-style bucket relay just because modern IEC-style units usually have it. Single-phase sensitivity — the differential trip mechanism on IEC-style relays — is a separate feature and has nothing to do with ambient compensation.
The injection test, step by step #
De-energize the feeder, lock out, and verify absence of voltage before opening the starter bucket; NFPA 70E, 2024 edition, covers the safe-work practices for electrical work, and you confirm the applicable practices with the authority having jurisdiction and the equipment documentation. The injector is its own hazard once connected — a low-voltage, high-current source that is treated as live whenever it is on.
- Record the relay and heater identity, the dial setting or heater rating, and the nameplate full-load current the heater was matched to; Setting overload relays from motor nameplate full-load current is the reference for that match.
- Open the load side of the overload's current path and land the injector leads across it, one pole at a time unless the relay's documentation says otherwise.
- Use a relay-test current-injection set, or the arrangement MCC shops have used for decades: a variac driving a current transformer reversed so it turns voltage into current, with the output read on a calibrated clamp meter.
- Raise the current to the test point and read it in-circuit on the calibrated meter; the injector's dial is a setting, not a measurement.
- Time from current-on to the trip contact operating, and write the seconds down before judging anything.
- Run the no-trip check at 100 % of the setting as a separate log entry: hold the current and expect no trip, because a trip there is its own finding.
The worked example #
Every number in this example is an illustrative input, not a published rating: an example motor with a nameplate full-load current of 40 A (three-phase, 460 V), the heater matched to it, an ambient-compensated bimetal relay, and a bucket held at 25 °C. The acceptance band comes from the relay's own curve sheet; for the example, 12 s to 40 s at 600 % of setting and 45 s to 150 s at 300 %. Read your limits from your relay's sheet, never from this article.
First point: 600 % of 40 A is 6 × 40 A = 240 A injected, and the contact opens at 24 s — inside 12 s to 40 s, so the point passes. Second point: 300 % of 40 A is 3 × 40 A = 120 A injected, and the trip takes 170 s — past the 150 s upper limit, so the point fails late. For the compensated relay, ambient cannot explain a late trip, so the decision is fail: service or replace the relay per the manufacturer and retest.
Run the same numbers on an uncompensated relay in that cold bucket and the meaning changes: cold pushes trip times late, so a late result could be the room rather than the relay. Without a documented preheat, the honest log entry is inconclusive — not failed, and never failed-then-corrected. The no-trip check at 100 % of setting is held for its full interval and expected to end without a trip; a trip stops the test.
Handling the ambient question without inventing a factor #
The manufacturer documents a method. Follow it to the letter — current, interval, acceptance limits. The practice reported for heater-style overloads is a preheat that holds 100 % of full-load current for 10 minutes as a no-trip check: it brings the element toward operating temperature and proves the relay will not open on running current. Adopt it where the manufacturer or your approved engineering basis accepts it, and treat any trip during that interval as a finding, not as a timed-point result.
No documented method exists. Test anyway and log the measured ambient beside every result. The construction decides what the numbers mean: a compensated relay's band result is final; an uncompensated relay's late result in a cold bucket is inconclusive.
Acceptance demands the curve basis and none is available. The result stays inconclusive, and the relay gets either a documented-basis retest or a replacement. A measured trip time is never multiplied by a factor derived from the 15 °C gap between the room and the curve — that arithmetic invents a rating the manufacturer never published.
What the record shows #
- Relay and heater identity, and the dial setting or heater rating.
- The nameplate full-load current the heater was matched to.
- Measured bucket ambient and the relay's thermal state: rested, or recently loaded.
- Injection set and meter identification, with their calibration dates.
- Each injected current as measured in-circuit, not as set on the dial.
- Each trip time in seconds, and the band limits used, with the curve sheet they came from.
- The preheat basis if one was used, and the no-trip result.
The decision, case by case #
| Relay at test | Result in hand | Decision |
|---|---|---|
| Ambient-compensated bimetal | Every timed point inside the band; no-trip check clean | Pass — return to service |
| Ambient-compensated bimetal | Any timed point outside the band | Failed — recalibrate or replace per the manufacturer, then retest |
| Uncompensated bimetal or melting alloy | Timed points inside the band, tested cold | Pass — the cold bucket works against the relay, so an in-band result holds |
| Uncompensated bimetal or melting alloy | Any timed point outside the band, no documented preheat | Inconclusive — retest on a documented basis or replace; never correct the number |
| Any construction | Trips during the no-trip check at full-load current | Early-trip finding — verify the setting against the nameplate, then inspect or replace |
That table is the whole method: the band decides trip time, the no-trip check decides running current, the construction decides what a cold-bucket result means, and the manufacturer's documentation decides everything the curve sheet does not.
Questions asked
Does the 10-minute full-load preheat prove the relay is at the 40 °C curve basis?
No. Holding the relay at full-load current warms the element toward operating temperature and doubles as the no-trip check, but it is a reported field practice, not a documented guarantee of the curve's starting temperature. Use it where the manufacturer or your approved test basis accepts it, record the basis with the result, and measure the relay's temperature directly with a surface thermometer if the acceptance record must show the starting condition.
Can I injection-test a melting-alloy overload the same way?
Yes — isolate it, inject current through the heater circuit, measure with a calibrated meter, and compare each trip time with the published band. A melting-alloy unit has no ambient-compensation element, so bucket temperature moves it directly, and it offers no adjustment once its heater is chosen: a result outside the band is resolved by the manufacturer's method or by replacing the heater, never by a temperature correction.
How many points on the curve do I need to test?
Follow the relay manufacturer's test basis where one exists; the reported practice is one or more points per relay type. When you choose the points yourself, take two: one near 300 % and one near 600 % of the heater rating. A single in-band result does not prove the curve, because an element that has drifted or corroded can pass at one multiple and miss at another.
What does a trip during the full-load no-trip check mean?
Stop and record it as its own finding. A relay that opens at the motor's running current will nuisance-trip a healthy load: verify the heater or dial setting against the nameplate current first, then look at the element's condition — age, corrosion, contamination — and any real overload the motor carried just before the test. Do not continue to the timed points until the setting is proven correct or the relay is replaced.
Do solid-state overload relays need the same ambient handling?
Electronic overload relays sense motor current with internal circuits rather than a heated element, so MCC ambient does not shift them the way it shifts a bimetal or melting-alloy relay, and there is no heater to preheat. The acceptance logic still applies: inject current, measure it with a calibrated meter, and compare trip times with the manufacturer's band; the settings you verify are parameters, not heaters.