Current IntelPower LibraryShop main store

Explainer

MCC door-mounted overload reset: order it, don't assume it

Motors and motor starters Published 7 min read

Short answer

A door-mounted overload reset on a motor control centre is an order-time option, not an inherent feature of non-compartmentalized construction. The option exists only when the installed overload relay has a documented door-reset or remote-reset accessory. Name it in the MCC order per starter with each relay's full type designation; for a retrofit, verify the relay's accessories first, fit only the documented kit, and confirm the control circuit does not restart the motor on reset.

On this page
  1. What non-compartmentalized construction does and does not decide
  2. The relay defines the reset option, not the MCC frame
  3. Worked example: two motors, one MCC, two reset order lines
  4. Specifying the reset in the MCC order
  5. Retrofitting a door reset to an existing MCC
  6. Reset is not restart: trace the control circuit first
  7. The decision, case by case
  8. Questions asked

A door-mounted overload reset on a motor control centre is an order-time option, not a built-in feature of non-compartmentalized construction. The builder fits it only when the overload relay in that starter has a documented reset accessory: a door operator kit or a remote-reset terminal. If an MCC arrived with no reset buttons on its doors, nothing was left out of a standard build; the option was simply not ordered. Specify it per starter, naming each relay's full type designation, and treat any retrofit as an accessory installation verified against that relay's documentation.

What non-compartmentalized construction does and does not decide #

An MCC is an assembly that groups its incoming section and its motor starter units in one structure. Non-compartmentalized construction says the starters are not built as individual compartmented enclosures; it describes the internal arrangement of the assembly. It says nothing about which operator devices appear on the doors.

IEC 61439-2, in its 2018 edition, covers low-voltage power switchgear and controlgear assemblies, the family motor control centres belong to, and classifies internal separation into forms, Form 1 through Form 4 with sub-divisions. A form records how busbars, functional units and terminals are separated by barriers or partitions. No form requires or forbids a reset button on a door, so the idea that non-compartmentalized panels never get door resets is not a rule of the standard; builders mount reset operators on these constructions whenever the order includes them.

Separation forms and door operators are assembly-level choices. Confirm what your assembly's documentation states and what the local authority having jurisdiction requires before changing door equipment.

The relay defines the reset option, not the MCC frame #

Inside each starter, the overload relay trips on sustained overcurrent and its trip contact drops the contactor coil circuit; the wiring of that contact is the subject of wiring overload relay contacts to the coil and the PLC. Reset is a separate function: it restores the tripped mechanism or the electronic trip status. It is not a start command.

How a relay can be reset is a documented characteristic of its family. Thermal bimetal relays reset with a plunger or button and commonly offer a manual or automatic selector; electronic relays add a reset button and often a remote-reset terminal. The same documentation that defines the relay's trip class and curve, covered in reading overload relay trip classes and curves, also lists which reset accessories exist for that type: door-mount operators, extension shafts, remote-reset contacts.

Accessory catalogs are organized by relay type designation, so the reset option follows the relay, not the MCC frame. Record the full type designation printed on each relay's label for every starter. That designation, not the panel's construction type, answers whether a starter can take a door reset.

Worked example: two motors, one MCC, two reset order lines #

Take an illustrative MCC with two very different loads. Motor A: 10.8 kW, 400 V, three-phase, assumed power factor 0.85 and efficiency 0.90. Motor B: 0.17 kW, 400 V, three-phase, assumed power factor 0.65 and efficiency 0.65. All of these are declared example inputs.

For motor A, the three-phase full-load current estimate is I = P / (√3 × U × power factor × efficiency) = 10 800 W / (1.732 × 400 V × 0.85 × 0.90) = 10 800 W / 530 V ≈ 20.4 A. The estimate only selects the candidate relay range; the nameplate full-load current governs, and the dial is set from it as described in setting overload relays from motor nameplate full-load current.

For motor B: I = 170 W / (1.732 × 400 V × 0.65 × 0.65) = 170 W / 293 V ≈ 0.6 A.

One estimate lands near 20 A, the other below an ampere, so the two starters take different relay ranges and, in most product families, different relay series with different accessories. Shift the assumed power factor and efficiency and the estimate moves by about one ampere: at power factor 0.80 and efficiency 0.92, motor A estimates 21.2 A, which the relay's adjustable range absorbs. The order decision does not move at all. The door-reset option is ordered per starter, never per kilowatt, and one door accessory cannot serve both relays.

Check the estimates against the motor nameplates and the relay range scales before anything is ordered.

Specifying the reset in the MCC order #

Write the option into the specification, per unit number: the relay's full type designation, the reset location on the unit door, manual reset required, and whether a remote reset terminal must also be wired to a pilot station elsewhere. Unit doors on these line-ups carry several pilot devices, so specify the reset and the pilot devices together and the builder lays out each door once. Whether the operator lands on an individual unit door or on a common door aligned to the starter position is part of the same ordered configuration; the builder's program guide states which doors its construction supports.

Order time is when this works cleanest: the builder selects the matched accessory, mounts and aligns it before shipping, and the door operators appear on the approved drawings. Ask to see the reset option on those drawings before production starts. On a new MCC, the door reset is a specification line, not a wish.

Retrofitting a door reset to an existing MCC #

De-energize the starter's feeder and control circuit and verify absence of voltage at the relay terminals under the site's lockout procedure before anything is opened.

  1. Read the full type designation off each relay's label, on the front dial or side marking. Do not identify the relay by motor size.
  2. Pull that relay's accessory documentation from the relay manufacturer and look for a door-reset kit or extension shaft listed for the type.
  3. If a kit exists, fit it to its instructions: check the plunger alignment with the door closed, open and close the door to confirm it fouls nothing, and confirm the released position leaves the relay's reset untouched. Cut any door hole to the accessory's template.
  4. If no kit exists for that type, send the designation to the MCC supplier for an engineered alternative, or change the relay to one in the same starter family that carries the accessory. Do not improvise a rod, a longer plunger or an ordinary pushbutton: a reset held depressed defeats the manual reset and can damage the relay mechanism.

A permanently depressed reset operator is the failure mode to design out; it turns a manual reset into a forced one and hides the trip from the operator.

Reset is not restart: trace the control circuit first #

When the relay trips, its contact opens the coil path and the contactor drops out. Pressing reset re-closes the protection contact; it does not command a start. Whether the motor restarts depends on the circuit, not on the button.

With three-wire control, a momentary start button and a seal-in contact, the trip breaks the seal and the starter stays off until someone presses start again. A door reset here only re-arms the protection, so it can go on the door without reservation.

With two-wire control, a maintained command from a selector switch, float switch or pressure switch, the contactor re-energizes the instant the relay resets and the motor restarts at the door. If the process must not restart that way, the fix is in the circuit, a latched stop or a start permissive, not in the button.

The decision, case by case #

  • New MCC: order the door-mounted reset as an option, one line per starter, each naming the relay's full type designation and the reset location.
  • Existing MCC with a documented kit for the installed relay: fit the kit to its instructions with the starter isolated, then confirm the control-circuit behavior before the motor returns to service.
  • Existing MCC with no documented kit: an engineered alternative from the MCC supplier, or a relay change to a type that carries the accessory; never an improvised actuator.
  • In every case the reset re-arms protection only; the circuit decides whether the motor restarts.

Questions asked

Why does the reset button sometimes do nothing right after a trip?

A bimetal thermal element has to cool before its mechanism can re-latch, so a button pressed seconds after a trip may not move anything; that is normal recovery, not a broken button. Electronic relays may allow an immediate reset or hold a recovery time stated in the relay's documentation. Wait for the relay to recover, and diagnose the overload cause before putting the motor back in service.

Can I drill the door and mount an ordinary pushbutton over the relay's reset?

No. The reset is a small mechanical plunger with defined travel and alignment, and only the relay maker's documented door kit has the geometry to operate it from a closed door. An improvised button can hold the reset depressed, foul the door travel, or force a tripped relay back with the overload cause still present. Order the kit matched to the relay's full type designation.

What belongs on the order line for a door-mounted overload reset?

Name the starter or unit number, the overload relay's full type designation from its label, the required reset location on the unit door, and whether a remote reset terminal should also be wired to a pilot station. One MCC often carries several relay families, and each family uses its own reset accessory, so a single blanket line for the whole line-up will not cover every starter.

Does adding a door-mounted reset change the assembly's ratings?

The reset operator carries no power current, so it does not change the short-circuit rating or the overload protection settings. What matters is that the door cutout and the operator are installed as the builder's documented option, because an undocumented hole, a misaligned plunger or a held-closed reset can compromise the enclosure and the protection. Field modifications should follow the assembly documentation and local requirements.

Keep reading

  • Troubleshooting

    Motor starters trip when MCC doors are closed

    The trips are real protection, not nuisance: a thermal overload relay without ambient compensation responds to enclosure air temperature, so doors open plus a fan suppresses trips while motor heating continues. A 10-12 V spread on 480 V is 1.0% to 1.7% voltage unbalance, above the NEMA MG 1 limit of 1.0%, and a 60-70 A current spread is severe. Close the doors, pull the fan, and fix the upstream supply that survived the chiller and MCC replacement.

    Motors and motor starters

  • Explainer

    Motor starter vs contactor: using a starter as one

    A motor starter is a contactor with an overload relay added: the relay's normally closed contact opens the coil circuit on sustained overcurrent. A starter works wherever a contactor is called for, provided three checks pass — horsepower rating at the supply voltage, coil voltage, and the overload setting against the motor's nameplate full-load current. A NEMA Size 1 covers a 3 HP motor.

    Motors and motor starters

  • Selection guide

    Selecting overload and jam protection for a reversible motor

    Set a bimetallic or electronic overload relay from the motor's nameplate full-load current — never from wattage — and give the electronic-clutch trip to a separate current-sensing jam or shock relay set above the highest normal process current. Its adjustable reset delay must outlast the cycle timer's worst-case command drop-out, and auto reset needs a deliberate-restart decision because a live run command restarts the motor.

    Motors and motor starters