Selection guide
Overload relay range selection for an 18.5 kW motor
Short answer
Select the relay by the motor's nameplate full-load current, not by kilowatts: pick the adjustable range that brackets that current away from both dial ends, then set the trip class from the measured acceleration time — class 10 for starts under 10 seconds, class 20 up to about 20. An 18.5 kW motor on a 400 V supply works out near 35 A; verify against the nameplate before you buy.

On this page
- Kilowatts do not select the relay
- What the setting range must cover
- Trip class follows the measured start
- Worked example: an 18.5 kW motor on a 400 V supply
- Setting the dial: nameplate current first, the code ceiling second
- What moves the current off the estimate
- The selection at a glance
- Confirm it with the motor running
- Questions asked
An 18.5 kW motor does not select its own overload relay: kilowatts only get you to an estimate. Select the relay by the nameplate full-load current at your supply voltage — the adjustable setting range must bracket that current, away from both ends of the dial — and set the trip class from the measured acceleration time, not from the power rating. This article works the selection for an 18.5 kW, 400 V three-phase motor and shows what changes on a 480 V supply.
Kilowatts do not select the relay #
A thermal overload relay heats a bimetal element — or, in an electronic unit, a current-sensing circuit — with motor current and nothing else. The same 18.5 kW of shaft output draws a different line current on a 400 V supply than on a 480 V one, and the current also moves with efficiency, power factor and winding connection. Treat the kilowatt figure as a first estimate to check against the nameplate; the nameplate current is the value that selects the relay and sets the dial. For a packaged machine where only the equipment plate is legible, the method for calculating equipment nameplate full-load amps for three-phase machines walks through that conversion.
What the setting range must cover #
Every relay publishes an adjustable range stamped on its dial — for example 30 to 38 A. The nameplate full-load current must fall inside that range, and preferably in its middle third: at the low end, a small calibration drift or a warm panel trips a healthy motor; at the high end, the same drift lets the winding run hot. The trade rule is simple: the full-load current sits between the range limits, never at a limit. If the only relay you can obtain puts the nameplate at one end of the dial, take the adjacent range instead.
Trip class follows the measured start #
IEC 60947-4-1 grades overload relays into tripping classes — 10A, 10, 20 and 30 — defined by the maximum time the relay may carry 7.2 times its setting current before tripping: a class 10 unit must trip within 10 s, a class 20 unit within 20 s. Class 10 fits starts that clear inside 10 s, which covers most machines; class 20 rides through acceleration up to roughly 20 s. Pick the lowest class whose time clears your measured start, because a higher class also delays the trip on a stalled rotor. For how the published curves read trip time against multiples of setting current, see reading overload relay trip classes and curves.
Worked example: an 18.5 kW motor on a 400 V supply #
Inputs, each declared: shaft power 18.5 kW (the case at hand); supply 400 V line-to-line, three-phase, 50 Hz; efficiency 0.90 and power factor 0.85 as illustrative assumptions for a general-purpose induction motor — the nameplate's own figures replace them.
The rule: line current equals shaft power divided by the square root of 3, times line voltage, times efficiency, times power factor — I = P / (√3 × U × η × cos φ).
The arithmetic:
- √3 × 400 V = 692.8 V
- 692.8 V × 0.90 = 623.5 V
- 623.5 V × 0.85 = 530.0 V
- 18,500 W ÷ 530.0 V = 34.9 A
The estimate is about 35 A. Decision: read the nameplate, and if it confirms a current near this figure, select a class 10 relay whose range brackets it with margin — for example a relay adjustable 30 to 38 A, with the dial set to the nameplate current. If the measured start runs past 10 s, move to a class 20 relay in a range covering the same current. On a 480 V supply the same arithmetic gives √3 × 480 V = 831.4 V, and 18,500 W ÷ (831.4 V × 0.90 × 0.85) = 18,500 W ÷ 636.0 V = 29.1 A — a smaller range, which is exactly why the power rating alone cannot order the part.
Setting the dial: nameplate current first, the code ceiling second #
Set the dial to the nameplate full-load current; the details are in setting overload relays from motor nameplate full-load current. NFPA 70, the National Electrical Code, 2023 edition, section 430.32, allows a separate overload device to be set at most 125 % of nameplate full-load current for a motor marked with a temperature rise of 40 °C or less, and at most 115 % for all other motors. That is a ceiling, not a target: every point above nameplate current trades winding life for fewer trips. Confirm the section and the setting with your authority having jurisdiction.
What moves the current off the estimate #
Dual-voltage nameplates. Read the row for your connection before anything else. A motor marked for two voltages lists two currents; the wrong row puts the dial a factor off and the range misses the real load entirely.
Star-delta starting. Where the relay sits in the circuit decides the dial value. Mounted in the delta winding legs, it carries winding current — the line current divided by √3, about 0.58 of nameplate — so set the dial at 0.58 times the nameplate current. Mounted in the line supply, it carries full line current and the dial reads the nameplate directly. Confirm the position on the starter drawing, not from habit.
Soft starter with bypass contacts. After acceleration the relay senses line current, so the dial reads nameplate as in a direct-on-line starter. Verify the sensing arrangement against the starter documentation before you set it.
The selection at a glance #
| Check | Where the value comes from | What it decides | Symptom when it is wrong |
|---|---|---|---|
| Nameplate full-load current | Motor nameplate, at your supply voltage and connection | Setting range and dial value | Dial at a range end, or the current outside every range |
| Measured acceleration time | Clamp meter or starter current trend | Trip class — class 10 under 10 s, class 20 up to about 20 s | Trip during start, or slow trip on a stall |
| Supply voltage | Nameplate and measured supply | The current estimate from shaft power | Range one size off |
| Starting method | Starter drawing | Line current or winding current through the relay | Dial set to line current in a delta-leg relay |
| Contactor coupling | Starter build | Whether the relay mounts to the contactor | A relay that fits nothing, or a range that misses the motor |
Confirm it with the motor running #
Before opening the starter enclosure, de-energize the feeder, lock out and verify absence of voltage with a tested meter, as NFPA 70E, 2024 edition, requires for electrical work. Then close the panel and run the check:
- Measure the acceleration with a clamp meter or the starter's current trend. The current must fall back to running level before the class time elapses, with margin to spare.
- At full process load, the running current should sit at or just below the dial setting.
- Operate the relay's test function and confirm the contactor coil drops out and the trip indication shows.
A trip during a start with a healthy load points at the driven machine or a low supply first, not at the class. A trip at steady running current points at a mechanical overload or a dial set below the real load — fix the cause before touching the setting.
Questions asked
The nameplate current lands at the very end of the only relay range available. Do I install it anyway?
No. Manufacturers publish several overlapping ranges, so take the adjacent range that puts the current in the middle of its dial. If no range covers the current, re-check the voltage row and winding connection on the nameplate before ordering.
Does the ambient temperature inside the panel change a thermal relay's trip point?
Compensated thermal relays hold their trip point within a stated ambient span, published in the manufacturer's documentation. A relay mounted in an enclosure that runs hotter than that span trips early, so check the compensation range before you blame the setting. Electronic relays sense current rather than heater temperature and are less sensitive to panel temperature, but their documentation still states an operating range.
This motor is marked with a 1.15 service factor. Does that let me set the dial higher?
The service factor does not override the overload section. NFPA 70 section 430.32 still caps a separate overload device at 125 % of nameplate current for a motor marked 40 °C temperature rise and 115 % otherwise, and the exact markings change which ceiling applies. Treat them as limits, set from the nameplate current, and confirm the marking interpretation with the authority having jurisdiction.
If I put this motor on a VFD later, does the overload relay stay?
No. The drive's electronic motor protection replaces the relay: it is programmed with the motor nameplate full-load current and models the winding heating, so the thermal relay and its dial come out of the circuit. The disconnect and short-circuit protection ahead of the drive stay as they are.
