What the 125% trip current dial setting on an overload relay means

Motors and motor starters Published 7 min read

Short answer

Set the overload relay dial to the motor nameplate full-load current — 27.4 A in the worked example — and enter nothing extra. The trip-amps marking means the relay trips at 125% of the setting you enter (27.4 A × 1.25 = 34.25 A), so the multiplier already sits inside the plate. A 1.15 service factor is a loading allowance, not a reason to raise the setting, and the current-limit function is a separate threshold with its own delay.

On this page
  1. What the plate note actually says
  2. Enter the nameplate current once
  3. Where the code percentage lives
  4. Worked example: one nameplate, every step
  5. The current-limit fields are a different function
  6. When starts trip anyway
  7. The decision
  8. Questions asked

Overload relays announce their trip ratio on the rating plate in two phrasings: TRIP AMPS 125 % on many UL-listed units, and TRIPPING CURRENT 125% of DIAL SETTING on the base unit in the example below. Both are results, not instructions. The relay trips at the marked percentage of whatever current you enter, so the margin already sits inside the plate before you touch anything. That settles the configuration question: the dial, or the software field that replaces it, takes the motor nameplate full-load current and nothing else — no pre-multiplication, no service-factor bump, and no number typed into the current-limit fields. The worked example runs the full arithmetic on a 27.4 A nameplate so every step can be checked.

What the plate note actually says #

The note describes the trip point the relay will reach: it trips when the measured current reaches the marked share of the current you dialed in. Nothing on the plate asks you to multiply the motor's current before entering it. The multiplication happens exactly once, inside the relay, after your entry — which is why entering a pre-multiplied value is the classic mistake here.

It is a threshold statement, not a time statement. How long the relay waits once current passes the threshold comes from the trip class and its curve, a separate read that reading overload relay trip classes and curves works through in detail. The plate percentage answers where the curve sits; the class answers when it acts.

Enter the nameplate current once #

The input side never changes between relay styles: the dial on a thermal relay and the setting field on an electronic one take the motor's nameplate full-load current for the connection actually wired. If the plate lists a current for each voltage or connection, take the line matching the supply at the motor terminals. Electronic relays measure phase current through their own poles, so the entry is a pure setting — the relay compares what it measures against what you entered, and its own ratio does the rest. The steps, from nameplate to dial, are the same as for a plain thermal unit: setting an overload relay from nameplate full-load current shows them.

Service factor belongs to the motor, not to the relay. It is the manufacturer's stated allowance for continuous load above nameplate rating under the supply and ambient conditions the nameplate lists — a capability of the machine, not an instruction to any protective device. The code handles the protection side explicitly, which is the next point.

Where the code percentage lives #

NFPA 70, the National Electrical Code, 2023 edition, Section 430.32(A), caps a separate overload device at no more than 125% of the nameplate full-load current for a motor with a service factor of 1.15 or higher or a marked temperature rise of 40 °C or less, and at 115% for every other motor. Enter the nameplate current into a relay marked with the higher ratio and the trip point lands exactly on that ceiling: the plate note and the code section describe the same margin from opposite ends. Confirm the requirement with your local authority having jurisdiction and the relay documentation, because editions and local amendments move these numbers.

Only one sanctioned move raises the trip point above that ceiling. Section 430.34 permits the next higher setting when the motor cannot start within the standard one, capped at 140% of nameplate current for the higher-service-factor band and 130% for the rest — a deliberate, documented exception, not a license to pre-multiply a dial entry because a start misbehaves.

A motor in the lower band needs its dial entry scaled down so the trip point lands on the lower ceiling: enter 0.92 times the nameplate current — the ratio between the two ceilings — so a 10 A motor dials in at 9.2 A.

Worked example: one nameplate, every step #

Inputs: three-phase motor, 460 V, 60 Hz (example supply data), nameplate full-load current 27.4 A, service factor 1.15, dial range 25–100 A (example range), plate note as quoted in the introduction. Conductor sizing runs under its own code section and does not enter this calculation. The ambient is the one the nameplate assumes; a hotter installation is a ventilation problem, not a dial problem.

De-energize the feeder, lock it out, and verify absence of voltage before opening the starter to read or set the dial.

Enter 27.4 A on the dial: trip point = dial setting × marked ratio = 27.4 A × 1.25 = 34.25 A, exactly the Section 430.32 ceiling for this motor. That result is an estimate derived from the marked ratio; check it against the relay's published curve and the governing code before the motor runs.

Entering 34.25 A instead applies the plate ratio to a setting that already contains it: trip point = 34.25 × 1.25 ≈ 42.81 A. The 33.2 A figure sometimes proposed for this motor fails the same way — the plate ratio lifts it to 41.5 A, above the ceiling, with no code basis behind it. Any dial entry above the nameplate current produces that same violation; the sanctioned way up is the Section 430.34 exception, nothing else.

The current-limit fields are a different function #

In SIMOCODE ES, the configuration tool for the SIMOCODE pro base unit in this example, the overload field is Set Current Is1, and the current-limit page holds % of Is, Upper limit and Trip Level, shown disabled in this configuration. Those fields belong to a second protection: a current limit compares measured current against a threshold referenced to the setting current and applies its own delay and response, typically to supervise a stalled or jamming load. It is not the thermal overload model, it does not share the plate note, and it is not a place to store the service factor.

Entering the plate ratio in those fields does not make the two protections agree. It adds a second threshold at a current where the overload model already trips, plus whatever nuisance the extra logic contributes. Left disabled, the motor remains fully protected by the overload model; the fields exist for a defined supervision task, configured with their own threshold and delay, or not at all.

Item in this configuration What it is Correct handling
Set Current Is1 the overload reference current, the input the plate ratio multiplies the nameplate full-load current, 27.4 A
Service factor, 1.15 on this nameplate a loading capability of the motor no entry anywhere
% of Is, Upper limit, Trip Level a separate current-limit function with its own delay disabled unless a documented supervision task needs it
The plate's trip-amps note the trip point that results no entry — it is the output

When starts trip anyway #

A correctly set dial that still trips on start is pointing at the start, not at the entry. Long accelerating loads need the trip class matched to the start time: setting overload relays for high-inertia motor starts covers that selection. Trips that vary from one start to the next point at connection or starting-current trouble rather than the dial: troubleshooting intermittent instantaneous motor start trips walks that path. Raising the dial past the nameplate current trades the code ceiling for a nuisance you will chase later — fix the start, not the entry.

The decision #

  • Enter the nameplate full-load current on the dial, or in Set Current Is1, once. Nothing else goes into the overload setting.
  • Never multiply before entering. The plate ratio runs after your entry, so any value above the nameplate current pushes the trip point past the Section 430.32(A) ceiling — the worked example shows the 33.2 A version of that mistake landing at 41.5 A.
  • Service factor enters nothing. It selects the code ceiling only; the dial scaling for the lower band sits in the code section above.
  • Leave % of Is, Upper limit and Trip Level disabled unless the application documents a supervision task for them.
  • A start trip is a trip-class or starting-method problem — fix it there, never on the dial.
  • Open the starter only with the feeder locked out and verified de-energized.

Questions asked

The motor nameplate lists two currents for two voltages — which one goes on the dial?

Use the line that matches the connection actually wired at the motor terminals and the supply voltage present there. On a dual-voltage plate the low-voltage connection carries the higher current, so reading the wrong line puts the entry far off in one direction or the other. Set the dial to that line's full-load current, and treat the service factor printed beside it as belonging to the same line.

The nameplate shows no service factor — which ceiling applies?

The lower one. A motor with no marked service factor falls into the code's lower band unless its marked temperature rise qualifies it for the higher percentage, so the trip point belongs at or below 115% of the nameplate current. On a relay with the fixed higher ratio that means the 0.92 dial entry described above; on a relay that sets trip current directly, set the ceiling itself. The input still starts from the nameplate current.

How long does the relay wait once current passes the trip point?

The plate percentage sets only where the curve begins; the trip class sets the time. Under the IEC 60947-4-1 definition most relays follow, a class 10 unit must trip within 10 seconds at 7.2 times its setting current from cold, class 20 within 20 seconds, class 30 within 30 seconds. A long accelerating load needs the higher class, never a higher dial entry — the dial does not touch the time axis at all.

The nameplate current sits near the bottom of my relay's dial range — is that workable?

It functions, but it is poor practice. A setting deep in the lower part of the scale leaves little resolution for fine adjustment and makes later verification against the nameplate harder. Choose a relay whose dial range places the nameplate current in the upper half of the scale; manufacturers publish several overlapping ranges for exactly this reason. The trip-point arithmetic is identical on every range.

Keep reading

  • Troubleshooting

    Why raising a magnetic overload setting won't fix a hard start

    No. Raising the dashpot pickup toward the 125% ceiling a 1.15 service factor permits adds no starting torque; it only lets the motor sit at locked-rotor current longer while its running protection shrinks. Find which device opened — breaker instantaneous element or overload relay — and fix what makes the start hard; in the case behind this article, an over-filled fluid coupling was the whole problem.

    Motors and motor starters

  • Selection guide

    Setting overload relays for high-inertia motor starts

    Set the current dial at the motor's nameplate full-load current and buy starting time with the trip class, not with a higher setting: Class 10 holds starts up to about 7 s at 600 percent, Class 20 to about 14 s, Class 30 to about 21 s. Longer starts need reduced-current starting, not a bigger relay.

    Motors and motor starters

  • How-to

    Setting overload relays from motor nameplate full-load current

    Set the overload dial — or select heater elements — to the motor's nameplate full-load current for the connected voltage, with no multiplier. NFPA 70 NEC Article 430.32 limits (125% with service factor 1.15 or 40 °C rise, else 115%) are ceilings on the trip rating, not percentages to add to a dial already calibrated in motor amps.

    Motors and motor starters