Variable frequency drives Published 7 min read By Current Intel engineering team

Short answer

A V/f induction motor model that will not linearize is telling you the structure is wrong, not the gains: park it at a steady operating point, take the perturbation out of any saturated limiter, and linearize from the frequency command to measured shaft speed. Then tune an outer PI that trims the frequency command, proportional first and integral only once the loop tracks.

On this page
  1. What the plant for a V/f speed loop actually is
  2. Three reasons a linearization fails
  3. A worked estimate of the plant gain
  4. Verify feedback and the open-loop response
  5. Tuning the outer PI
  6. When V/f is the wrong structure
  7. Questions asked

If a V/f control model for a three-phase induction motor refuses to linearize, the problem is almost never the PID gains. A linearization is a local derivative taken at one steady operating point, between one defined input and one defined output. When the tool returns zero, garbage or an error, one of those three ingredients is missing: the operating point is still moving, a limiter in the path is clamped, or the input and output you selected are not the plant's real input and output. Fix the structure, verify the plant with a small open-loop step, and only then tune a PI controller whose output trims the frequency command. This article walks through each step and works the plant gain arithmetic for a real example motor.

What the plant for a V/f speed loop actually is #

For shaft-speed regulation built around a V/f core, the signal path runs: speed reference, speed error, PI controller, frequency command through its limits and ramp, V/f function, inverter, motor, measured shaft speed. The plant input for tuning is the frequency command. The voltage command is not an independent handle: the V/f function derives voltage from frequency, so a linearization that takes the internal voltage signal as input is modeling a different plant than the one your PI will actually drive.

The physics behind the path: stator frequency sets the synchronous speed of the rotating field as 120 times frequency divided by pole count, and the rotor develops torque through slip below that speed. Below the breakdown point and at full flux, torque is close to proportional to slip frequency, so shaft speed sits near synchronous speed minus a slip offset set by load torque, and raising the command frequency raises shaft speed almost one-for-one. That near-straight relation is the plant the outer PI works against.

One caveat belongs here. A plain V/f characteristic under-fluxes the motor at low frequency, where stator resistance takes a larger share of the small commanded voltage, and the motor comes up short on torque. That failure and its correction are covered in Why a VFD shows low output voltage and the motor has no torque; fix it before tuning, because a flux-starved plant is not the plant whose gain you will tune.

Three reasons a linearization fails #

The operating point is not steady #

A linearization is the derivative of the model at an equilibrium: states constant, inputs constant, controller output held. If the simulated motor is still accelerating, the load model is still changing, or the controller is still integrating toward its output, there is no equilibrium to differentiate, and the tool either fails outright or returns the derivative of a moving target. Drive the model to a steady condition first: constant load torque, speed settled, controller output parked, then request the linearization.

A limiter in the path is clamped #

Frequency minimum and maximum clamps, the voltage ceiling at the top of the V/f curve, current limit, a ramp that has not finished: any one of them holding its signal means a small perturbation at the linearization input produces no change anywhere downstream. The tool sees zero gain and reports a failure or a degenerate model. Identify which block is active at the operating point, move the point inside the limits, or accept that a clamped region has no linear model at all.

The input and output pair is wrong for the loop #

Selecting motor current as the linearization output when you intend to regulate speed gives you the current plant, not the speed plant, and gains derived from it will fight the loop you actually close. Including the controller in the path double-counts its action. And an inverter modeled with explicit switching is periodically time-varying, which ordinary steady-state linearization does not handle; use an averaged inverter representation for outer-loop work and keep the switching model for validation later.

A worked estimate of the plant gain #

Every input here is an example, chosen so the arithmetic can be checked. Motor: 4-pole induction machine on a 60 Hz supply, nameplate speed 1746 rpm, constant-torque load, operating near 60 Hz with full flux.

Synchronous speed at 60 Hz: 120 × 60 / 4 = 1800 rpm. Rated slip speed: 1800 − 1746 = 54 rpm.

Assume the load holds torque and the motor runs below breakdown slip, where torque is close to proportional to slip frequency, so slip speed stays near 54 rpm. Step the frequency command from 60 Hz to 62 Hz. New synchronous speed: 120 × 62 / 4 = 1860 rpm. New shaft speed: 1860 − 54 = 1806 rpm. Speed change: 1806 − 1746 = 60 rpm for a 2 Hz command change.

Local steady-state plant gain: 60 rpm ÷ 2 Hz = 30 rpm per hertz of frequency command, followed by the mechanical lag of inertia and load and whatever filtering sits in the feedback path.

This is an estimate, and it holds only inside the small-slip region at full flux. As slip approaches the breakdown point the torque-slip curve flattens, the gain falls toward zero, and beyond breakdown it flips sign, so a loop tuned at one speed can be sluggish or unstable at another. Check the shape against the motor's torque curve, and confirm any step test against the machine's limits before running it.

Verify feedback and the open-loop response #

Before tuning anything, prove the speed measurement chain with the loop open:

  • At standstill, the feedback reads a steady zero, not an offset or drift.
  • Sign convention: a forward increase in shaft speed moves the feedback the same way the reference does.
  • Scaling: compare the feedback against an independent speed measurement where practical, and resolve unit and gearing conversions before tuning.
  • Quality: check the trend for dropouts, noise and delay; a filtered or intermittent speed signal caps the loop bandwidth no gain set can recover.

On real hardware, de-energize the drive, lock out and verify absence of voltage with a meter rated for the available fault current before touching encoder or tach wiring in the panel; run any live step test in an approved commissioning mode within the motor and machine ratings.

With feedback verified, apply a small frequency step at the steady operating point and check the speed change against the estimate: roughly 30 rpm for a 2 Hz step on the example machine. If the direction is wrong, the magnitude is far off, or the current hits a limit, correct that before any tuning.

Tuning the outer PI #

Begin with proportional action only and integral disabled. Apply a small step at the operating point and increase the proportional gain until the closed-loop response shows a modest overshoot, then back off. Add integral action to remove the steady offset that slip droop leaves under load: without it, the shaft sits below the reference by whatever slip the load demands. Derivative action rarely helps here, because the plant gain is mild and the speed feedback is noisy, so derivative amplifies measurement noise more than it predicts plant motion.

Keep the frequency-command limits and ramp in place while tuning; they are part of the plant, and removing them to get a cleaner response tunes a loop that will not exist on the drive. Feedback delay and filtering set the ceiling on achievable bandwidth. If the loop hunts slowly between two speeds, lengthen the integral time first, then check whether the frequency command is bouncing between its limits, which is saturation rather than bad gains.

When V/f is the wrong structure #

Reported practice among engineers who close position or high-dynamic speed loops around drives is to set the drive up as a closed-loop vector speed controller with its own speed loop tuned as tightly as the mechanics allow. The reason matches the physics above: V/f cannot command torque directly, and its slip-based response is slow under impact loads, reversals or sustained low-speed operation. V/f with an outer PI is a regulation solution. It holds speed against steady and slowly varying load across the region where the plant gain stays positive and roughly flat.

The decision, by case: if the motor must hold a set speed under a steady load and the drive is V/f-only, verify the plant with a small step, then tune the outer PI at the operating point that matters. If the application needs fast torque response, zero-speed holding torque or position control, stop tuning the V/f loop and move to a drive that documents closed-loop vector control with an encoder input.

Questions asked

Can I close a speed loop on a V/f drive with no encoder?

Not properly. Without shaft-speed feedback the drive holds frequency, not speed, and slip lets the shaft slow as load rises; on the example motor that droop is the rated slip speed of 54 rpm. You can estimate slip from measured current and the motor's rated data, but the estimate is coarse and load-dependent. If the application needs real speed regulation, use a drive that supports closed-loop vector control with an encoder input, or accept the frequency-holding droop.

The model linearizes fine but the real drive behaves differently, so why?

A linearized model is a local approximation at one steady operating point. The real path adds the drive's own ramp, dead time from carrier and sampling, feedback filtering, and limiters the model never engaged. Validate the linear model against a small step on the real machine at the same operating point and adjust it before trusting any gains derived from it.

Why does my tuned speed loop still hunt slowly between two speeds?

Slow hunting in a plant that is close to a gain followed by a long lag usually means too much integral action: the controller keeps pushing after speed catches up, overshoots, and repeats. Lengthen the integral time first. If the frequency command bounces between its limits, the loop is saturating rather than mistuned, so reduce the proportional gain or the disturbance driving it there.

Keep reading

  • How-to

    Why a drive needs summed motor data for two motors in parallel

    One drive can run two motors in parallel, but only in V/f control with the motor current and power parameters set to the sums of both nameplates, the combined stator resistance entered, and a separate overload or PTC on each motor. The sum of the two motor currents must stay below the drive's output rating.

    Variable frequency drives

  • Troubleshooting

    Why a motor vibrates at low speed on a VFD

    Vibration that is strongest at a few hertz and disappears as the drive approaches 60 Hz is almost always the drive's low-end V/Hz curve or wrong motor data, not the rebuild. Derive the pole count from the nameplate speed, set the nameplate voltage, frequency and current, then raise low-frequency voltage boost in small steps until torque is steady; too much boost raises current and heat. If the motor shakes at every speed or drags by hand, stop and inspect the mechanical assembly.

    Variable frequency drives

  • Explainer

    Why voltage control cannot vary a single-phase motor's speed

    Reducing the voltage on a single-phase induction motor cuts its torque roughly with the square of the voltage, so half voltage leaves about a quarter of the torque while slip and current climb and the winding overheats. One reported 240 V, 2900 rpm single-capacitor motor reached about 700 rpm at 120 V with little usable torque. For real speed control, fit a three-phase motor and a VFD.

    Variable frequency drives