Troubleshooting
Why a motor vibrates at low speed on a VFD
Short answer
Vibration that is strongest at a few hertz and disappears as the drive approaches 60 Hz is almost always the drive's low-end V/Hz curve or wrong motor data, not the rebuild. Derive the pole count from the nameplate speed, set the nameplate voltage, frequency and current, then raise low-frequency voltage boost in small steps until torque is steady; too much boost raises current and heat. If the motor shakes at every speed or drags by hand, stop and inspect the mechanical assembly.

On this page
Shaking that is worst in the bottom few hertz and fades as the drive ramps toward line frequency is the signature of a starved V/Hz curve or wrong motor data in the drive, not of a bearing you seated wrong. A bearing, a rotor rub or a loose assembly shakes at every speed, including a straight across-the-line run. Fix it in the drive: derive the pole count from the nameplate speed, enter the nameplate voltage, frequency and full-load current, then raise the low-frequency voltage boost in the smallest steps the drive offers until torque holds steady at a few hertz. Take the final verdict from a protected run on the three-phase supply the machine will actually use. Here is the sequence, the arithmetic and the decision for each outcome.
What the speed pattern already proves #
A basic drive runs scalar volts-per-hertz control: output voltage falls in proportion to output frequency. At low frequency the stator's resistive drop, which shrinks with current but not with frequency, takes a large share of that small applied voltage. Air-gap flux collapses, torque arrives in pulses instead of smoothly, and the pulses shake the frame hard enough to rattle the machine. The disturbance lives exactly where the curve is wrong: the bottom of the range.
By the time the drive approaches rated frequency it is applying close to nameplate voltage, and the motor runs as it would across the line. Smooth running there says the windings, connections and rotating assembly can produce steady torque at full flux. A bearing fault does not read output frequency: roughness from a badly seated race or a rubbed rotor shows at every speed and, most tellingly, with the shaft turned by hand. A mounting resonance is speed-dependent too, but it only amplifies a torque ripple that already exists; kill the ripple and the resonance has nothing to feed on.
So the working diagnosis is electromagnetic: a motor that turns freely by hand and shakes only at the bottom of the range has a drive-side problem, and the fix lives in the drive's settings.
Enter the motor data before touching the curve #
The drive needs the nameplate as numbers: rated voltage, rated frequency, full-load current and rated speed. If the plate carries two voltage and frequency sets, the walkthrough on reading a dual voltage and frequency motor nameplate shows how to pick the pair that matches the connection you wired.
The pole count comes straight from the rated speed through the synchronous-speed relation: synchronous speed in RPM equals 120 times the frequency in Hz divided by the pole count, so poles = (120 x frequency) / rated speed.
Worked example, with example nameplate inputs of 230 V, 60 Hz and 1740 RPM: poles = (120 x 60) / 1740 = 7200 / 1740 = 4.14, which rounds to 4 poles. Check it forward: 120 x 60 / 4 = 1800 RPM synchronous speed, and slip = (1800 - 1740) / 1800 = 3.3%, a normal full-load slip, which confirms the reading. A plate near 3450 RPM rounds to 2 poles the same way.
Every value in the drive's motor-data screen comes from the plate, never from a generic table for a motor of that size; wrong entries carry far, as the walkthrough a spindle VFD that hums but won't turn on wrong motor data shows. The full-load current entry also feeds the drive's motor-protection model, so it protects the windings through exactly these low-speed tests.
Why the low end collapses, and how boost fixes it #
Work the same example at the bottom of the range. The nameplate ratio is 230 V / 60 Hz = 3.83 V/Hz, so straight proportion gives 3.83 x 6 = 23 V at 6 Hz. Now suppose a resistance check on this motor works out to about 1 ohm per phase and the motor draws about 10 A at that speed; these are example figures to show the arithmetic, so measure your own. The resistive drop is 10 A x 1 ohm = 10 V, leaving 23 - 10 = 13 V to build flux. Torque tracks flux squared, so what remains is (13/23) x (13/23) = 0.32, about a third of the torque the curve intends, and that remainder arrives unevenly, pulse by pulse. That uneven remainder is the shake.
The same drop shrinks in proportion as frequency rises: at 12 Hz the applied voltage is 46 V, the 10 V drop leaves (46 - 10) / 46 = 78%, and at rated frequency the drop is a few percent, invisible. That is why the shaking fades on the way up and is gone at full speed.
The low-frequency boost setting, which the manual may call voltage boost or torque enhancement, adds voltage back at the low end to make up the resistive loss. Set it from the minimum: run the motor unloaded at a fixed low frequency, raise one step, run again, and watch two things, whether torque holds from a standstill without bucking and whether the unloaded current stays where it was. Stop at the first steady result. Current that climbs with boost, a louder hum or warmth within a minute means overexcitation, so back off one step. The useful setting is the smallest one that works, never the largest. If the drive offers an autotune routine, run that instead; it measures the winding resistance with test signals and builds the low-end compensation from the measurement.
A check sequence that separates electrical from mechanical #
Work top to bottom and stop at the first branch that points mechanical:
- De-energize, lock and tag the input, wait the discharge interval the manual states (IEC 61800-5-1, the drive product-safety standard, is the reason labels and manuals state that time, because bus capacitors stay lethal after the input is off), and verify absence of voltage at the terminals. NFPA 70E, 2024 edition, defines the steps that establish an electrically safe work condition; confirm the details with your authority having jurisdiction and the equipment documentation.
- Bolt the motor to a rigid base and guard the coupling. Turn the shaft by hand: scraping, tight spots or rough bearings means open the assembly again, because no drive setting fixes that.
- Enter the nameplate data and the pole count derived above.
- Run unloaded, ramping from a few hertz upward, and read output current from the drive's own display at each step; an average-sensing clamp meter under-reads a pulse-width-modulated output, so trust the drive's numbers unless your meter is a true-RMS type rated for drive waveforms.
- Raise the boost one step at a time as above, reading the current after each step.
- Finish on the real supply: connect through branch protection sized for the motor per NFPA 70, the National Electrical Code, 2023 edition, Article 430, and run across the line. Steady, quiet running there closes the electrical question on the rebuild.
The single-phase test feed changes capacity, not smoothness #
Feeding the drive from a single-phase circuit does not itself shake the motor: the drive rectifies and filters that input and still synthesizes three phases at its output. What it can change is how much continuous output current the drive is rated to deliver, because the rectifier and bus work harder from two lines; many models state a lower continuous output rating for single-phase input in the manual's rating table. Compare that table's value with the motor's full-load current before trusting any tuning result: a drive running against its single-phase limit has little voltage headroom at the low end, and everything you tuned goes soft. The guide to sizing a VFD for a three-phase motor on single-phase input works the matching in full.
The decision, case by case #
- Shakes only in the bottom of the range, turns freely by hand, smooth at rated speed: the drive-side curve or data is wrong. Enter the pole count and nameplate values, add the minimum effective boost or run autotune; the rebuild is sound.
- Rough or tight by hand, or shaking at every speed including the across-the-line run: mechanical, meaning bearings, end-shield alignment, rotor rub or a soft mount. Stop tuning and open the assembly.
- Boost raises current and heat instead of calming the motor: one step too far. Back off; that is overexcitation, not more torque.
- Steady at a few hertz and steady across the line: the motor is done. Install it on its three-phase circuit and keep the drive for bench jobs.
Questions asked
Why do the smaller motors run smoothly on this same drive?
Each motor brings its own winding resistance and rated current, and one fixed curve rarely suits both: smaller machines carry more winding resistance relative to their ratings, so the low-speed voltage they need differs from a larger motor's. Smooth running on the small motors proves the drive outputs three healthy phases and its controls work. It says nothing about whether the curve matches the rebuilt motor, so tune against that motor's own nameplate.
What if the drive has no boost parameter at all?
Some very basic drives expose only base frequency and base voltage and fix the rest of the curve internally. Your levers then are the correct nameplate data, a different drive with adjustable low-speed voltage or autotune, or skipping the drive entirely. For a one-time check of a rebuilt motor, a protected run across the line on the real three-phase supply answers the assembly question better than more tuning on hardware that will not stay on the machine.
Which current reading should I trust while tuning?
The drive's own output-current display. An average-sensing clamp meter calibrated for sine waves reads a pulse-width-modulated output low and can look reassuring while the motor is overloaded. If you measure externally, use a true-RMS instrument rated for drive output waveforms and follow its manual for the frequency range it covers. Record current after every boost and frequency step so the trend, not one spot reading, guides the setting.
What does the drive's autotune routine actually do?
It applies test signals to the stationary motor, measures winding resistance and leakage inductance, and builds the low-frequency part of the voltage curve from those measurements instead of a fixed boost guess. Run it with the nameplate data entered first, the motor cold and prevented from turning, and the machine uncoupled if the procedure says so. Afterward, confirm steady low-speed torque and that unloaded current has not climbed.
Can sustained low-speed shaking damage the motor?
Keep test runs short. Violent vibration works the winding end-turns, the coupling and the mount, and at low speed the shaft fan barely moves air, so a motor drawing boosted current heats with little cooling. Run only long enough to read current and judge smoothness, bolt the motor down first, and treat climbing current or rising temperature as the signal to back the boost off and stop.