Current IntelPower LibraryShop main store

How-to

Why a drive needs summed motor data for two motors in parallel

Variable frequency drives Published 5 min read By Current Intel engineering team

Short answer

One drive can run two motors in parallel, but only in V/f control with the motor current and power parameters set to the sums of both nameplates, the combined stator resistance entered, and a separate overload or PTC on each motor. The sum of the two motor currents must stay below the drive's output rating.

On this page
  1. Why the summed data and V/f control are mandatory
  2. Setting up a MICROMASTER 430 for two motors
  3. Worked example: sizing a 15 kW drive for two 7.5 kW pumps
  4. What you give up with a parallel pair
  5. Questions asked

Yes, one drive can run two motors wired in parallel, and it is a common way to keep two pumps at the same speed. The conditions are firm: V/f control only, motor current and power entered as the sums of both nameplates, the combined stator resistance entered, the summed currents below the drive's output rating, and a separate overload on each motor. This article shows the parameter entry for a fixed parallel pair on a MICROMASTER 430; for switching motors off a running drive, see running two motors on one VFD with output contactors, which covers the different rules that case needs.

Why the summed data and V/f control are mandatory #

Vector control builds a motor model from one motor's data and estimates rotor speed from that model. With two motors in parallel the drive sees one combined impedance and cannot tell the motors apart, so sensorless vector control and encoder feedback are excluded. V/f control (P1300 = 0) needs no model, so it is the only permitted mode.

The same logic forces the summed entries. Set P0305 (rated motor current) to the total current of both motors and P0307 (rated motor power) to the total power, so the drive's limits and its V/f boost match the group it actually feeds. P0350 (stator resistance) must be the equivalent resistance of the motors in parallel, which is lower than either motor alone; the stator resistance parameter and its star-delta configuration page explains how the drive uses that value. Because the drive's internal I2t protection watches total current, it cannot protect the motors individually: NFPA 70, the National Electrical Code, 2023 edition, requires individual overload protection for each motor in a group installation, so fit a thermal overload relay per motor or a PTC thermistor per motor with its own evaluation. Confirm the requirement with your authority having jurisdiction and the drive documentation.

Setting up a MICROMASTER 430 for two motors #

Before opening the drive cabinet, de-energize the feeder, lock it out, and test for absence of voltage at the drive terminals. Then:

  1. Record each motor's rated current and rated power from its nameplate.
  2. Add the two currents and confirm the sum is below the drive's output current rating. If it is not, the drive is too small and no parameter setting fixes it.
  3. Set P1300 = 0 for linear V/f control. Do not use the textile V/f variants (P1300 = 5 or 6); they behave like the normal V/f modes but exist for other load types. The V/f versus vector control parameter comparison page shows what each P1300 setting does.
  4. Set P0305 to the summed current. P0307 takes kW when P0100 = 0 or 2 and hp when P0100 = 1, so enter the summed power in the unit your P0100 selects.
  5. Measure the stator resistance of the two motors connected in parallel and enter that value in P0350.
  6. Keep the total motor-cable length within the drive's permitted length for your cable type. For this drive family the documented maximum is 300 m of unscreened cable with an output choke fitted; without the choke the permitted length is shorter and comes from the drive's documentation for your frame size. Put no contactors, fuses or circuit breakers between the drive and the motors in a fixed pair.
  7. Fit one thermal overload relay or one PTC circuit per motor. A supported PTC arrangement uses series-connected sensors into one evaluation unit wired to a digital input set as an external fault (P0701 to P0708 = 29), but only while the total measuring-circuit resistance stays below the evaluation unit's response value. Never wire KTY84 sensors in series or parallel into a shared evaluation unit; the reading is wrong.
  8. Commission with both motors running: confirm V/f mode, check the summed P0305 and P0307, verify P0350, trip each motor's protection and confirm the drive stops.

Worked example: sizing a 15 kW drive for two 7.5 kW pumps #

Inputs: the reader's drive is a MICROMASTER 430, 15 kW (6SE430-2AD31-5CA0); the two pump motors are 7.5 kW each; each nameplate current must be read from the motor, so take 15.4 A per motor as an illustrative value for a 400 V four-pole machine of that size. The rule: the sum of the motor currents must be less than the drive's output current rating, and P0305 and P0307 take the sums.

  • Current check: 15.4 A + 15.4 A = 30.8 A. Read the drive's rated output current from its documentation; the drive is adequate only if its rating exceeds 30.8 A. If the rating is equal to or below that figure, choose the next drive size up.
  • Power entry: 7.5 kW + 7.5 kW = 15.0 kW, entered in P0307 (with P0100 = 0).
  • Resistance entry: two equal windings in parallel give half of one, so if one motor measures 0.60 ohm between terminals, P0350 = 0.30 ohm.

Decision: with the summed current below the drive rating, set P1300 = 0, P0305 = 30.8 A, P0307 = 15.0 kW, P0350 to the measured parallel value, one overload per motor, and run both pumps together with no switching on the output. Above the drive's current rating, the drive is undersized and must be replaced, not re-parameterized.

What you give up with a parallel pair #

Both motors receive the same frequency, so they start, stop and run together, and their speeds match only as closely as their slip allows. Do not connect or disconnect either motor while the drive runs: connecting causes an inrush that trips the drive, disconnecting can generate a damaging overvoltage. Because the drive's I2t model is blind to each motor, the per-motor overloads are not optional. Finally, keep the summed cable length within the documented limit for your cable and choke arrangement; an output choke also reduces heating in the protection devices between drive and motors where your installation has them.

Questions asked

Can I switch one motor off while the drive is running?

No. Connect or disconnect a motor only with the drive stopped and locked out. Connecting a motor to a live output causes an inrush that trips the drive on overcurrent, and disconnecting one can generate a damaging overvoltage on the output. If you need to drop one motor while the other keeps running, that is a different arrangement: see the article on one VFD with two motors and output contactors.

Why can't the drive's internal motor model protect two motors?

The drive measures total output current, not current to each motor. If one motor stalls, its extra current can be masked by the healthy motor drawing less, so the drive's I2t model sees nothing wrong. That is why each motor needs its own thermal overload relay or its own PTC thermistor evaluated separately.

Does the MM430 need an output choke for two motors?

Only if the summed cable length exceeds the drive's screened-cable limit. With an output choke the documented maximum for this drive family is 300 m of unscreened cable. Keep the total below the limit that applies to your cabling, choke and drive size.

Keep reading

  • Explainer

    Running a 450 kW DOL motor on a VFD: what to verify first

    A 3.3 kV, 450 kW motor will start and run on a correctly sized medium-voltage drive, but the Class F VPI insulation is not proven inverter-duty, so get the manufacturer's written withstand against the drive's output before connecting. On DOL, two motors draw 186 A running, 651 A with one starting, 1,116 A with both starting.

    Variable frequency drives

  • Explainer

    Running a standard 480 V motor on a VFD: what to check first

    Yes — a standard Class F 480 V motor can usually run from a matching 30 hp drive without an inverter-duty replacement. Keep the drive-to-motor lead at or under 100 ft or fit the output filter the drive maker's table names, confirm cooling at the lowest continuous speed, and reform the drive's DC bus capacitors if it sat unused for a year or more.

    Variable frequency drives

  • Selection guide

    Sizing a VFD for a 1 HP 220 V motor on single phase

    Size the drive by output current, not horsepower. This 1 HP, 220 V, three-phase motor draws 2.5 A at full load, so the drive needs at least 3.6 A of continuous output current; a 2 HP, 230 V single-phase-input frame rated about 7.5 A carries the single-phase rectifier's extra heat with room to spare. Stay on 230 V single-phase input rather than a 120 V voltage-doubler input.

    Variable frequency drives