VFD input contactor vs output contactor: which one the manual allows

Variable frequency drives Published 8 min read By Current Intel engineering team

Short answer

Put the magnetic contactor on the VFD input side, between the branch overcurrent device and the drive's R S T line terminals, and let the emergency-stop chain drop it out. Do not switch the drive-to-motor circuit unless the drive manual documents that arrangement and its sequence. The contactor is a disconnect, not overcurrent protection — the breaker or fuses ahead of it clear faults.

On this page
  1. Where the contactor goes
  2. Why the output side is the one the manual forbids
  3. The two stop paths
  4. Sizing the input contactor
  5. The contactor is not the breaker
  6. Commissioning checks
  7. Questions asked

Put the magnetic contactor on the VFD input side, between the branch overcurrent device and the drive's line terminals, and let the emergency-stop chain drop it out. Do not put a contactor between the drive and the motor unless the drive manual documents that arrangement and its sequence; manuals for this class of drive draw the contactor on the supply side of the line terminals and state the output prohibition outright. A contactor is a remotely operated disconnect. It is not overcurrent protection: the breaker or fuses ahead of it clear faults, and the drive's own control input commands starts and stops. Below are the placement rule, the two stop paths the contactor serves, the sizing arithmetic, and the checks that prove the wiring.

Where the contactor goes #

Read the wiring section of the manual for your exact model first. Where its hookup diagram shows a magnetic contactor, that contactor sits on the supply side of the drive's R, S and T line terminals, and the same section normally states that a magnetic contactor must not be placed on the drive output. The drawing answers the placement question: the contactor belongs between the supply and the drive, and nothing switches between the drive and the motor unless the manual puts it there. For how those R, S and T terminals take a single-phase supply, see wiring a VFD R S T input from a single-phase supply.

Three cases cover every machine you will wire:

  • The emergency-stop design removes electrical power, or you want a remotely operated disconnect: install the contactor in the supply, ahead of the drive's line terminals, and drop its coil from the stop chain.
  • A lockable manual disconnect already covers isolation and every stop can be a controlled stop through the drive: no contactor is needed — land the supply through its protective device straight on the line terminals.
  • The drive-to-motor circuit stays unswitched; the only documented exception is a bypass line-up, covered below.

Before you open the panel for any of this wiring: de-energize the circuit, lock it out, and verify absence of voltage at the drive terminals per NFPA 70E, 2024 edition.

Why the output side is the one the manual forbids #

A VFD builds the motor's voltage and frequency electronically and feeds the motor a pulse-width modulated waveform, not a sine wave. Opening a contactor in that circuit interrupts output current mid-pulse: the drive's output stage sees an open circuit and trips, the contact tips chop an inductive current their sine-wave rating tables never describe, and the opening gap takes a voltage transient. Closing back onto a spinning motor is worse: the drive sees voltage at a frequency it did not command and trips on overcurrent while the contacts make the inrush of re-accelerating the load. Both events come from a switch the drive cannot see coming, which is why manuals prohibit output switching outright.

The documented exception is a bypass line-up, where the manual sequences drive and bypass contactors so neither closes onto a rotating motor; why a manual disconnect on a VFD output ruins the bypass shows what happens when a switch added in the wrong place defeats that sequencing. Decision: no contactor on the output of a normal installation. If a machine genuinely needs the motor circuit switched, the manual for that drive must document the arrangement and its interlocks, and you wire exactly what it shows.

The two stop paths #

The drive's stop control input decelerates the motor under the drive's control and leaves the drive powered; that is the normal stop, wired as described in wiring start and stop pushbuttons when a VFD replaces a DOL starter. Dropping the input contactor removes electrical power immediately: the motor coasts, the drive loses its control supply, and IEC 60204-1, the standard for the electrical equipment of machines, calls that stop category 0 — stopping by immediate removal of power. Drive manufacturers publish application notes that wire the emergency stop through a supply contactor for exactly this duty.

Most machines take both signals. The emergency-stop device feeds the drive's dedicated stop input so a controlled deceleration begins, and it drops the contactor where the machine's risk assessment demands power removal; a sequence of controlled stop followed by supply removal at standstill is the category 1 pattern, and the drive manual names the standstill or safe-stop signals it provides. Use the contactor for emergency stop and isolation only, not for routine starts and stops: cycling the run command rather than the supply keeps the drive's precharge circuit out of repeated inrush and saves the contact tips. When the contactor re-closes, the drive must wait for a fresh start command — returning power may never run the machine by itself, which the same IEC 60204-1 provisions guard against and the drive's restart-on-power-up setting enforces.

Confirm the editions in force, local amendments, and the stop performance your machine needs with the authority having jurisdiction, the machine risk assessment, and the drive documentation.

Sizing the input contactor #

Select the contactor from the drive manual's rated input current, never from the motor's nameplate current. On a single-phase input the drive's line current runs above its output current — why VFD input current can run above output current explains the mechanism — so a frame picked on motor amps lands a size small.

Worked example, illustrative figures throughout; take the real ones from your manual and nameplates:

  • Supply: 240 V, single phase, 60 Hz.
  • The manual's rated input current for the model: 14 A.
  • Motor nameplate full-load current: 8.6 A, three phase.

Apparent power at rated input: 240 V × 14 A = 3360 VA. Carried instead over three lines at 240 V, that same power is 3360 VA ÷ (1.732 × 240 V) = 3360 VA ÷ 415.7 V = 8.1 A per line. The contactor sits on the side that carries about 1.7 times the per-conductor current of the motor circuit, so the manual's 14 A input figure governs the selection and the 8.6 A motor rating does not. The arithmetic ignores drive losses and harmonics on purpose: the manual's rated input current already includes them, which is what makes it the number to size on.

From the contactor manufacturer's table, choose a frame whose rated operational current at 240 V AC meets or exceeds the drive's rated input current in the utilization category that applies. IEC 60947-4-1, the contactor product standard, defines those categories; AC-1 covers non-inductive or slightly inductive loads at power factor above 0.95. In the example, a frame rated 20 A AC-1 qualifies and a 9 A frame does not. A drive input is a rectifier feeding a capacitor bank, not a resistive load, so confirm from the contactor maker's data that the frame suits that duty rather than assuming the AC-1 figure transfers unchanged. For how far the two sides of a drive can diverge, see why line-side kVA differs from motor-side kVA.

Decision: the contactor's rated operational current at the supply voltage, in the documented category, must meet or exceed the drive manual's rated input current. Treat the result as a selection check against the manual and the contactor datasheet, not as a rating in itself.

The contactor is not the breaker #

A contactor carries no fault-current interrupting rating and cannot do overcurrent protection's job. The branch breaker or fuse set sits ahead of it, selected from the drive manual's protective-device table for the model — where the manual calls for a circuit breaker rather than fuses, install the breaker type and rating it names — and coordinated with the supply conductors under the governing code. Using a motor circuit breaker as the infeed protector is a common pattern; using a motor circuit breaker on a servo drive infeed walks through one.

Keep the devices' roles separate in your head as well as in the panel: the breaker clears short circuits and protects the conductors, the contactor only switches, and the emergency-stop contactor is an automatic disconnect layered on top of the machine's manual one. NFPA 79, 2021 edition, requires an industrial machine's supply circuit to have a disconnecting means that opens all ungrounded conductors and can be locked in the open position; the E-stop contactor supplements that device, it does not replace it.

Commissioning checks #

Prove the two stop paths separately before the machine runs production:

  • The contactor sits in the supply, ahead of the drive's line terminals, and nothing switches the drive-to-motor circuit.
  • The drive's stop input decelerates the motor while the drive stays powered.
  • The emergency-stop chain drops the contactor and removes supply; the motor coasts, and power removal alone does not stop a rotating load instantly — the machine must reach the safe state its risk assessment defines.
  • Re-closing the contactor leaves the drive stopped until a fresh start command.
  • The protective device ahead of the contactor matches the manual's table for the model.
  • If the drive shows a fault after an emergency stop, read its fault history against the manual's fault table for the model before changing anything; a supply-loss or undervoltage entry is the expected result of removing input power.
  • Record the contactor rating and utilization category, the protective device, and the observed stop behavior in the machine documentation.

If the contactor chatters or fails to pull in, check coil voltage and the control contacts first; if the drive trips on a stop, the fault history and the manual's fault table decide the cause, not guesses about parameters.

Questions asked

Can I open a contactor between the VFD and the motor only while the drive is stopped?

Only if the manual for your exact drive documents output switching and the sequence to use. Opening at standstill avoids the switching transient, but a contactor that closes onto a coasting motor still produces a drive overcurrent trip, and an uninterlocked contactor can close at speed. With no documented approval, leave the drive-to-motor circuit unswitched and do your isolation at the input side or a lockable disconnect.

What size contactor does a 2.2 kW drive on single-phase input need?

Size it from the drive manual's rated input current for the model, not the motor's nameplate current; on a single-phase input that line current is roughly 1.7 times the equivalent three-phase line current, because one conductor pair carries the whole load. Pick a contactor whose published AC-1 rated operational current at your supply voltage meets or exceeds the manual's figure, and confirm from the contactor maker's data that the frame suits a rectifier-capacitor input.

Is a drive fault after the emergency-stop contactor opens a problem?

A supply-loss or undervoltage entry in the fault history is the expected consequence of removing input power from an energized drive; the manual's fault table for your model confirms the code. Entries that do not match it point to wiring or parameter problems and deserve the table's corrective action. Because repeated input interruptions stress the precharge circuit, reserve the contactor for emergency stop and isolation, and put frequent routine stops on the drive's stop input.

Will a three-pole contactor work on a single-phase supply to the drive?

Yes. Land the supply's two energized conductors on two poles and leave the third pole unused; a spare pole is not an instruction to parallel poles or switch other circuits. Parallel two poles for higher current only where the manufacturer's table explicitly rates paralleled poles, because the poles do not share current evenly. Size the contactor on the drive's rated input current either way.

Keep reading

  • Troubleshooting

    Why a VFD trips a motor phase loss fault and what to measure

    Measure all three motor phase currents under load before you reset a VFD motor phase loss fault. Imbalance between the readings, not a continuity check with the circuit dead, is what finds the loose joint, open conductor or failed winding behind the trip; the worked example shows the arithmetic.

    Variable frequency drives

  • How-to

    Stopping one VFD when either motor overload trips

    Wire 24 V DC from the drive through each MPCB trip contact to its own digital input, set both inputs as external fault, and make the fault stop a coast. One tripped overload then latches a drive fault, names the motor, and takes torque off the healthy motor at once. Keep the series-contact stop as a fallback and leave Safe Torque Off to the safety concept.

    Variable frequency drives

  • How-to

    Feeding a rotary phase converter idler from a VFD

    Yes. A reported test ran a 4.0 kW, 240-380 V drive into a roughly 4 hp idler and started a 2 hp mill across the synthesized bus. Treat the idler as one more motor on the drive: size it on total current, strip every start and run capacitor, fit a sine-wave filter sized for the whole bus, and check each switched start against the drive's overload curve.

    Motors and motor starters