What 11 leads and a 19.5/9.5 FLA pair tell you
Short answer
A 19.5/9.5 A nameplate pair is the full-load pair for the two voltages, not a starting and running pair: each voltage times its own current lands within 3% of the other, near 2.1 kVA. Keep the motor off 220 V until every lead is traced to its winding sections, start winding, capacitor and switch; then connect the main sections in series and set the overload from the high-voltage entry.

On this page
An 11-lead motor with a nameplate pair of 19.5/9.5 A answers its first question before you touch a wire: those are two full-load ratings, one per voltage connection, not a starting current and a running current. The plate itself carries the proof — each voltage times its own current gives the same apparent power, about 2.1 kVA, and only a dual-voltage pair agrees that closely. So the machine is a single-phase dual-voltage motor whose main winding is split into two sections, connected in parallel as found for the low voltage. What the plate cannot hand you is the connection diagram, and that is the one thing needed before 220 V. The work below traces all 11 leads to the winding sections, the start winding, the capacitor and the switch, then settles the decisions for the high-voltage conversion and the compressor.
What the nameplate pair means #
FLA on a motor plate means full-load amps: the current the machine draws at 100% of rated load, at rated voltage and frequency. A dual-voltage single-phase motor carries two entries because its stator winding is built as two matched sections — joined in parallel the sections take the low voltage, joined in series they take the high voltage, and the current entry falls to about half at the same shaft output. That series-or-parallel split is the entire mechanism behind a dual-voltage rating.
A starting surge is never printed as an FLA entry. Locked-rotor data appears as a code letter when a plate lists it at all, not as a second current value, so the reading "the big number is starting, the small one is running" has nothing on the plate behind it — and the arithmetic in the next section argues against it directly.
The as-found run fits the dual-voltage reading too. Unloaded on the low-voltage connection the machine drew about 10 A, roughly half the low entry, and that is a normal no-load figure on a small single-phase motor: magnetizing current holds the field up whether or not the shaft is loaded, so no-load current does not fall in proportion to shaft load. The reading proves the winding and start circuit are intact as connected. It proves nothing about rated horsepower — apparent power becomes shaft horsepower only through efficiency and power factor, and on this plate those are unreadable.
Checking the 19.5/9.5 A pair: 110 V against 220 V #
Inputs, all from the motor's own nameplate: the two voltage entries, 110 V and 220 V, and the two current entries, 19.5 A and 9.5 A.
The rule, in words: the same winding delivering the same shaft output at either connection must draw the same apparent power, so each voltage times its own current should land on the same value. A running-and-starting pair printed on one line would not agree, because starting current is set by the locked-rotor condition, not by the winding connection.
Arithmetic:
- 110 V × 19.5 A = 2,145 VA
- 220 V × 9.5 A = 2,090 VA
- Difference: 2,145 − 2,090 = 55 VA, which is 55 ÷ 2,145 = 2.6% of the larger product
- Ratio of the two current entries: 2.05, within plate rounding of the factor of 2 that a series connection delivers
Result: the pair is a dual-voltage full-load pair. At full load the machine presents about 2.1 kVA of apparent power at either connection; shaft horsepower stays unknown because the plate's efficiency and power factor cannot be read.
Decision: take the smaller entry as the high-voltage rating and expect a correct high-voltage run to settle near it at full load. A run near twice the high-voltage entry means the winding is still in parallel — open the circuit rather than repeat the test.
What 11 leads can hold on a single-phase motor #
Eleven wires do not set the phase count, and they need no three-phase explanation. A dual-voltage single-phase machine can bring out ten to twelve leads on its own: four for the two main winding sections, two for the auxiliary start winding, two for the centrifugal switch or starting relay, and two more each when the machine carries a run capacitor or a thermal protector wired into the bundle. A second speed winding would add further leads. Ten or eleven fits a capacitor-start machine with a thermal protector comfortably.
The printed numbers carry their own warning. The group taped as 3-12 on a motor with 11 wires shows the numbering is not a count of what is present: one numbered lead is missing, buried or misread. Keep the factory numbers exactly as printed and note the discrepancy — renumbering destroys the only key to the original diagram.
If the plate's phase entry says three, stop and follow identifying wires on an unmarked three-phase motor instead, where the tell is similar resistance between every pair among the winding leads. Otherwise the capacitor settles it: start and run capacitors belong to single-phase machines, so follow the capacitor's two pigtails to whatever they join and write that into the map.
Tracing the leads to sections, start winding and switch #
Before the connection box opens, lock out and tag the supply, verify absence of voltage at every lead, and discharge each capacitor through a suitable resistor and verify it reads zero — a start capacitor holds its charge long after the motor stops. The taped groups are a record of the low-voltage connection that ran, not a high-voltage diagram.
| Group as found | What to establish |
|---|---|
| 9-6-8 | Confirm each printed number, then record which winding or device each of the three reaches. |
| 5-7-10 | Document the three-way junction before separating it — a junction ties sections or the start circuit together. |
| 3-12 | Verify that 12 is a true marking and not a damaged or misread digit, and note that only 11 wires exist. |
| 2-4-white | Trace the white conductor until its function is proven: line pigtail, switch lead or thermal lead. |
| 11-black | Do the same for the black conductor; assume nothing from its color. |
- Photograph the plate, the taped groups and every junction as found, then label each lead with your own numbers without removing factory sleeves.
- Undo the friction tape and separate all leads so each can be measured on its own.
- Identify and tag capacitor and switch paths first so they cannot contaminate winding readings: on an ohmmeter a capacitor never settles on a steady value, while a closed centrifugal switch reads near zero at rest.
- Measure resistance between every pair of leads and write the full matrix down. Winding sections appear as stable pairs — the two main sections read nearly equal, and the auxiliary winding reads higher because its wire is finer.
- Build the map from the matrix: which pairs are the two main sections, which pair is the auxiliary winding, which leads pass through the switch, and whether the white and black conductors are line pigtails or thermal-protector leads.
- Check every winding to the frame with an insulation resistance tester before the first energized test. A motor that sat unused for years fails on insulation more often than on winding resistance, which is why a stored vintage motor needs megger and winding tests before reuse.
- Remember that resistance identifies the sections but not their polarity. The manufacturer's diagram settles polarity; without it, a brief energized check on a fused circuit separates an aiding pair from a bucking one — a bucking pair hums and vibrates without turning — but that check is rougher on the motor than reading the diagram.
Making the high-voltage connection #
On the traced map, the high-voltage connection puts the two main sections in series: one section's finish joins the other's start, and the line lands on the two free ends. The low-voltage connection ties the two starts together and the two ends together and feeds the pair in parallel. The sections carry the same current either way — that is why the plate shows half the current at double the voltage.
The start circuit is where conversions go wrong. The auxiliary winding and its capacitor must land where they see the voltage they were designed for, and on many dual-voltage single-phase motors that is across one section at the high-voltage connection rather than across the full line. Whether this machine does that is exactly what the manufacturer's diagram settles, so get the diagram: give the manufacturer or its distributor the model marking, frame, serial and the voltage-current pair exactly as printed. The readable part of the marking on this plate began 5KC184; a diagram for a different motor that shares those characters is a search lead, not authority to energize.
Never prove the conversion by energizing the as-found connection at 220 V. Double voltage on the parallel connection drives the sections to twice their designed flux, current climbs well past the rating, and the insulation takes the damage in seconds. Energize only on a connection you have traced and checked to ground. The discipline is the same one reconnecting medium-voltage dual-voltage motor windings in series and parallel walks through: the sections change, not the supply.
Once the connection is confirmed, set the overload from the high-voltage nameplate entry, the way setting overload relays from motor nameplate full-load current describes. The branch-circuit sizing from that same entry is worked in the questions at the end.
Decisions for this motor #
- As found, on the low-voltage connection: the unloaded draw of about 10 A is a healthy no-load reading, so the machine can keep running solo. Before trusting it under load, watch the current fall after acceleration — that is the start circuit releasing — and keep repeated stalled starts off the table, because a stalled motor has seconds, not minutes.
- Conversion to the high-voltage connection: not from the tape layout. Trace to a map, obtain the diagram, test insulation to ground, connect the sections in series, set the overload, and make the first run unloaded before anything couples to the shaft.
- The compressor: a compressor is a high starting-torque load, and a motor that spins clean by itself can still stall or cook its start winding on one. Couple it only after the connection is proven, make the first loaded starts with the unloader open so the pump does little work, and judge the result by whether the running current sits near the high-voltage entry and the frame stays cool. If it hums, vibrates or never releases the start circuit, stop and recheck the connection.
Questions asked
How can I tell an unmarked motor like this is single-phase and not three-phase?
Look first for a capacitor wired into the leads; a start or run capacitor marks a single-phase machine, because a three-phase motor needs no phase-shifting capacitor. Check the phase entry if the plate survived. By resistance, a single-phase dual-voltage machine shows two nearly equal main sections plus a higher-resistance auxiliary winding, while a three-phase machine shows similar resistance between every pair among its winding leads. Trace before energizing; lead count alone proves nothing.
What overcurrent protection does the high-voltage connection need?
From NFPA 70, the National Electrical Code, 2023 edition, Article 430: size branch-circuit conductors at 125% of the 9.5 A nameplate entry, which is 11.9 A and within the ampacity of 14 AWG copper; an inverse-time circuit breaker may be no larger than 250% of that entry, or 23.8 A, so a 25 A breaker fits; a time-delay fuse may be no larger than 175%, or 16.6 A, so a 20 A fuse fits. Confirm the final sizes with the local authority having jurisdiction and the equipment documentation.
Where do I get a wiring diagram for a motor with no connection cover?
Ask the motor manufacturer or its distributor, giving the model marking, frame size, serial number and the voltage-current pair exactly as printed, even where characters look wrong; suppliers match connection sheets by frame and winding data. A diagram from a different motor that shares part of the marking is not authority to energize. If the plate is unreadable and no diagram turns up, weigh a replacement motor over guessing a connection.