Explainer
What IEC 60034-12 actually limits on motor starting current
Short answer
IEC 60034-12 sets a maximum locked-rotor apparent power, not a starting-current ratio. A motor declaring a starting-to-rated current ratio of 7.3 can comply while failing a purchase requirement of less than 6.5. Run both acceptance checks: the table limit qualifies the design, the customer's ceiling decides the order.

On this page
- What does IEC 60034-12 actually limit?
- Why do the datasheet ratio and the customer limit disagree?
- How much starting current does the design N limit allow?
- Can a motor pass the standard and still fail your specification?
- Which current definitions must match before you compare the two numbers?
- What if your supply really needs the lower current?
- Which check decides the order?
- Questions asked
A datasheet ratio of 7.3 can satisfy IEC 60034-12 and still fail a purchase specification that demands less than 6.5, because the standard never sets a starting-to-rated current ratio at all. It caps locked-rotor apparent power for each starting design and power band instead. That gap is not the supplier contradicting the customer; it is two different acceptance checks, and both have to run before an order. The table limit qualifies the machine's design. The customer's current-ratio ceiling decides whether the motor can be bought, and on the papers in front of you this machine fails that second check as written.
What does IEC 60034-12 actually limit? #
IEC 60034-12 sets a maximum locked-rotor apparent power for each starting design and power band of a single-speed, three-phase cage induction motor, and for design N and design H machines between 63 and 630 kW that ceiling is 10 kVA per kW of rated output.
The current edition, IEC 60034-12:2024, specifies the starting-performance parameters of single-speed three-phase cage induction motors at 50 Hz or 60 Hz across eight designs. The tables behind the design N and H entries set one apparent-power ceiling across the band above 63 kW and up to 630 kW, and the supplier's declaration should name the edition, design and table entry it is judged against. The standard exists so torque, locked-rotor current and apparent power get declared consistently, which is what lets a direct-on-line or star-delta starter be sized and the supply impact be judged before purchase.
It is a declaration framework, not an installation rule: the equipment documentation confirms what applies on your machine, and where an inspector reads a requirement into the job, the local authority having jurisdiction settles it. The figure has a physical meaning too, because a locked rotor sits at slip 1 and takes the full supply at standstill; why an induction motor draws heavy current at starting walks through the reason that current runs so high (article:why-an-induction-motor-draws-heavy-current-at-starting).
Why do the datasheet ratio and the customer limit disagree? #
They disagree because they measure different things: the datasheet's 7.3 is a starting-to-rated current ratio, while the standard's check compares locked-rotor apparent power with rated output power, so a motor at 7.3 can be compliant and still miss a purchase limit of less than 6.5.
Neither statement is wrong. The supplier answered the question the standard asks; the customer asked a question the standard never asks. A declaration of conformity does not waive a stricter purchase requirement, and a stricter purchase requirement does not make the machine non-compliant. Read the specification's wording as well as its number: a strict less-than ceiling rejects a declared value equal to it, so marginal cases turn on that comparison rule.
Keep the two records separate while you work:
| Acceptance check | Quantity compared | Result for the offered machine |
|---|---|---|
| Purchase specification | declared starting-to-rated current ratio against the customer's ceiling | fails: 7.3 against a ceiling of less than 6.5 |
| IEC 60034-12 | locked-rotor apparent power divided by rated output, per the declared design and power band | passes once the ratio converts inside the table limit, as the worked example shows |
| Installation performance | voltage dip, acceleration time and protection coordination on the real supply | its own study, covered by neither figure |
How much starting current does the design N limit allow? #
For a 100 kW, 400 V motor with 0.90 efficiency and 0.90 power factor, the design N and H apparent-power ceiling of 10 kVA/kW converts to a starting-to-rated current ratio of 10 × 0.90 × 0.90 = 8.1, so both 6.5 and 7.3 sit inside it.
The worked example uses illustrative inputs stated in full: three-phase, 400 V line-to-line, 50 Hz, 100 kW rated mechanical output, efficiency 0.90 and power factor 0.90 as decimals. Symbols: Pn is rated output in kW, VLL the line-to-line voltage in volts, In the rated line current, IL the locked-rotor line current, and K the table's kVA-per-kW figure.
Rated line current:
In = Pn × 1000 / (√3 × VLL × η × cosφ) = 100 × 1000 / (1.732 × 400 V × 0.90 × 0.90) = 100000 W / 561.2 ≈ 178.2 A
Apparent-power ceiling from the table entry:
Smax = 10 × 100 kW = 1000 kVA
Locked-rotor line current at that ceiling:
IL = Smax × 1000 / (√3 × VLL) = 1000000 VA / (1.732 × 400 V) ≈ 1443.4 A
Current-ratio ceiling:
IL / In = 1443.4 A / 178.2 A ≈ 8.1
The shortcut skips the currents entirely: ratio ceiling = K × η × cosφ = 10 × 0.90 × 0.90 = 8.1. Run the conversion the other way and the offered machine's declared ratio corresponds to about 9.0 kVA per kW, inside the table limit while sitting above the customer's ceiling. Treat all of this as an estimate built on the example inputs: the machine's own declared efficiency, power factor and apparent power govern, and the table entry must match the edition and design the supplier cites.
Can a motor pass the standard and still fail your specification? #
Yes, and on this order the specification wins: standards compliance qualifies the machine's design, while the customer's current-ratio ceiling is a separate contractual gate that no declaration of conformity can waive, so the offered machine fails that gate exactly as the papers stand.
Both parties have told the truth, which is why the argument feels stuck. The fix is procedural, not technical. Either the customer keeps the ceiling and you source a machine whose declared ratio sits below it under the same conditions, meaning direct-on-line at rated voltage in the connection you will wire, or the customer reviews the numbers and releases a written change to the requirement. Do not let an interim message carry that change; the acceptance record should end the argument, not extend it.
Which current definitions must match before you compare the two numbers? #
Compare only like with like: the numerator must be the RMS locked-rotor line current declared for a direct-on-line start at rated voltage and the stated connection, the denominator the rated line current for the same rating, and a peak value against an RMS value invalidates the whole comparison.
Half of the disputes in this shape dissolve once both sides quote the same quantity. The first half-cycle peak that trips an instantaneous element is a different animal from the RMS locked-rotor value in the ratio, and why motor start peaks don't compare to instantaneous breaker settings keeps the two apart (article:why-motor-start-peaks-don-t-compare-to-instantaneous-breaker-settings). Connection matters just as much: the same machine draws different line current in wye than in delta, so a ratio quoted for one connection says nothing about the other until you convert, as why a motor draws different line current in wye and delta shows (article:why-a-motor-draws-different-line-current-in-wye-and-delta).
Checking the link bars means opening the terminal box, so de-energize, lock off and verify absence of voltage first. And if the machine will actually start through a soft starter or a drive, remember the declared ratio still describes the direct-on-line case; the current the supply sees becomes a different number that the starter's own data carries.
What if your supply really needs the lower current? #
Then reduce the current the supply sees with a soft starter or a drive, verify the reduced-voltage torque still accelerates the load, and get the change in writing, because the starter changes line current but never changes the motor's declared direct-on-line ratio.
Start with the reason behind the ceiling. Usually it is voltage dip on a weak supply or a generator, occasionally protection coordination; the driver tells you which figure actually has to fall. Induction-machine torque falls roughly with the square of the voltage at the motor terminals, so a reduced-current start trades acceleration force for supply friendliness, and the motor's accelerating torque needs checking against the driven load across the whole run-up, not only at standstill.
A start that stalls or drags on overheats the rotor and walks the protection into a trip, so the starter's current limit needs the motor's thermal capability in view; setting a soft starter current limit without overheating the motor covers that balance (article:setting-a-soft-starter-current-limit-without-overheating-the-motor). The protection side of long, hot starts deserves the same pairing of acceleration time with the trip settings, which a plant guide to locked-rotor motor protection works through step by step (https://industrialmonitordirect.com/blogs/knowledgebase/ngl-plant-motor-protection-against-locked-rotor-failures). If the numbers close with a starter in the line, the specification needs a line for it: acceptance stated against the starting method actually used, with the written change attached before the order goes in.
Which check decides the order? #
The customer's ceiling decides this order: the declared ratio fails it, so the selection is rejected as written unless the customer documents a change, while the machine itself remains a compliant example of its declared design that other buyers can accept.
Work the four cases in this order:
- Ratio inside the customer ceiling: order the motor, and file the declared design, edition and table entry so the standard check is on record.
- Ratio above the ceiling, kVA-per-kW conversion inside the table limit, which is this machine's case: reject against the specification, or take a written waiver after the dip and protection figures have been reviewed.
- Conversion above the table limit: the machine does not meet its declared design, so send the datasheet back for corrected data or the correct designation.
- Supply cannot take the current: quote a starter or a drive with the acceleration and thermal checks done, and attach the customer's written change to the requirement.
Close the file with five items: the declared ratio, the declared design and edition, the table entry and band, the converted kVA-per-kW figure, and the customer's acceptance decision in writing. The supplier described the standard correctly and the customer set a real requirement; the order follows the specification, and nothing in the standard overrides it.
Questions asked
Which edition of IEC 60034-12 is the current one?
IEC 60034-12:2024 is the current edition, and it specifies starting-performance parameters for eight designs of single-speed three-phase cage induction motors at 50 Hz or 60 Hz. Tables and limits have moved between editions, so confirm the table number, design and power band against the edition cited in the supplier's declaration, and read the standard from an authorized source rather than a copy of unknown origin.
Does the locked-rotor apparent power limit change with supply voltage?
No. The standard states its ceiling as apparent power divided by rated output power, which is voltage-independent. The same design N machine declares different locked-rotor amperes at 400 V and at 690 V while staying inside the same table entry, which is why every conversion to a current ratio needs the real voltage, efficiency and power factor of the machine being judged.
What separates design N from design H?
Design N is the general-purpose designation for machines with normal starting torque, and design H covers machines built to deliver high starting torque. Both share the apparent-power table in the power band used in the example, but their torque requirements differ, so the design follows the driven load first and the current-ratio argument second.
Why do datasheets quote a starting current ratio at all?
Because the ratio is the figure a starter and protection engineer applies directly: breaker settings, soft starter sizing and voltage-dip estimates all take locked-rotor amperes as their input. It is a convenient engineering number rather than the standard's acceptance quantity, so treat it as commercial data to be checked against the specification, not as proof of conformity.
What should I ask the supplier for before re-running the acceptance checks?
Ask for the declared design and the cited edition, the applicable table entry and power band, the declared locked-rotor apparent power or its kVA-per-kW figure, and the RMS locked-rotor line current for a direct-on-line start at rated voltage in the connection you will actually wire. Those four items let you run the standard check and the specification check yourself.
