Current IntelPower LibraryShop main store

Explainer

What load shedding on a drive really requires from a trip

Variable frequency drives Published 6 min read By Current Intel engineering team

Short answer

Load shedding is a measured drop in incoming power within a required time, not any trip. Use a controlled deceleration stop when the process must manage motion and stored energy; use freewheel or Safe Torque Off only when an uncontrolled coast is acceptable, and always block automatic restart.

On this page
  1. What "trip the motor" has to mean
  2. The stop methods compared
  3. Removing torque does not remove kinetic energy
  4. The command-path checks on the installed drive
  5. Worked example: shedding a 75 kW pump within 10 s
  6. Restart interlocks and proving the sequence
  7. Questions asked

Load shedding on a drive is a measured drop in incoming electrical power within a required time, and that definition decides which stop you use. A normal deceleration stop, a coast stop, Safe Torque Off (STO) and opening a contactor all end in "motor stopped," but they differ in how fast the demand falls, where the rotating energy goes and what restarts the motor afterwards. Pick controlled deceleration when the process must manage motion and braking energy; pick freewheel or STO only when an uncontrolled coast is acceptable; and treat contactor opening and fault resets as non-methods.

What "trip the motor" has to mean #

A shedding request is an operational command, not a fault. Write the requirement in measurable terms before touching any parameter: how many kilowatts the feeder demand must fall, within how many seconds, with what the driven process is allowed to do meanwhile. Acceptance is the power trend on the feeder meter or a validated drive power reading, not a stopped status bit. If the machine's safety requirements call for a safety function, design that separately; operational shedding should use the drive's normal control functions.

The stop methods compared #

Method What it does electrically Where it fits Where it fails
Deceleration (ramp) stop Drive keeps control, reduces frequency, motor torque opposes rotation; braking energy can return to the DC link Process needs managed motion, e.g. pumps, conveyors with hold-back Fast ramps can trip the drive on DC-link overvoltage if braking energy has nowhere to go
Freewheel (coast) stop Drive drops output; motor coasts on friction and load torque High-friction or low-inertia loads where an uncontrolled coast is harmless High-inertia or gravity-driven loads coast for a long time or keep moving
Safe Torque Off (STO) Drive's safety function prevents torque generation; motor freewheels When a hardware-level torque removal is wanted and the coast is acceptable Not electrical isolation; supply and stored energy remain; diagnostics and validation required
Open a motor-side contactor Interrupts the drive-to-motor circuit while the drive may be energized Only with a manufacturer-approved switching sequence Stresses equipment, wears contacts, re-close needs synchronization
Fault reset Clears an eligible fault Never a stop With a run request active it restores operation

Removing torque does not remove kinetic energy #

STO and coast stops end torque, not motion. A motor and its driven equipment keep rotating until friction, process resistance or a separate brake absorbs the stored kinetic energy; coast-down time depends on inertia, speed, load torque and external forces. A load pushed by gravity or by another machine can keep moving indefinitely after the drive stops producing torque. Measure or estimate the coast-down time before choosing freewheel, and confirm it against the process's allowable motion.

A deceleration stop keeps the drive in control, but it moves the problem to the DC link. When motor torque opposes rotation, mechanical energy flows back into the link, and if the drive has no braking resistor, no regenerative front end and no other drive sharing the link, the link voltage rises until the drive trips on overvoltage, which is exactly the uncontrolled coast you were trying to avoid. Read the drive's documentation for the installed braking means, and inspect that equipment physically, before shortening a ramp.

The command-path checks on the installed drive #

Before wiring anything, record for each drive: its exact reference, firmware identification, motor data, the active control source (terminals, fieldbus or other), the configured stop type, and existing safety wiring. Then:

  • Trace the shedding request through the same control architecture the run command uses; a stop on a different control channel may be ignored.
  • Read the configured response to a stop request: ramp, coast, or another configured behavior, and confirm it matches your choice above.
  • If STO is used, check its connections against the drive's safety manual and establish whether it already belongs to a safety circuit before adding an operational function to it.
  • Inspect motor-side and supply-side contactors and their interlocks; neither is an interchangeable stop command.
  • Identify every restart path: maintained run commands, restored communications, cleared STO inputs and fault recovery.
  • Keep shedding logic separate from fault acknowledgement, and keep a torque-removed status distinct from a shaft-stopped status.

Worked example: shedding a 75 kW pump within 10 s #

Inputs. A 75 kW centrifugal pump on a drive, feeder demand to fall by its full 75 kW within 10 s, no braking resistor installed, measured coast-down time of about 25 s. These are the example's own figures; substitute your measured values.

Rule. A deceleration stop holds demand roughly proportional to speed cubed for a centrifugal pump, so the demand falls with the ramp; a coast stop removes electrical demand immediately but leaves the shaft turning for the coast-down time.

Arithmetic. Required demand drop: 75 kW within 10 s. A 10 s ramp removes 75 kW inside the window while keeping control of the water column, but with no braking resistor the returned energy may trip the drive: at rated speed the pump returns a fraction of 75 kW through the ramp, and even 20 kW returned into a link with no sink is enough to raise the voltage toward trip. A coast stop drops the electrical demand to zero in under a second but leaves the shaft turning about 25 s.

Result. The coast stop meets the power requirement easily; the 10 s ramp meets it only if the braking energy is handled.

Decision. For this pump the process tolerates the 25 s coast, so configure the shedding command as a coast stop and interlock the restart. If the process needed controlled motion, fit and wire a braking resistor sized from the drive documentation first, then use the ramp. If the required shedding time were shorter than one control scan plus the contactor and drive response, open the supply-side contactor instead, with the manufacturer's approved sequence.

Restart interlocks and proving the sequence #

Hold the shed state until the supervising controller explicitly releases it. Then test functionally with the shedding request active: command the shed, confirm the feeder power falls within the required time on the meter, confirm the motor does not restart when communications blip or a fault clears, and record the result. Any wiring or parameter work inside the drive enclosure starts with lockout, opening the incoming supply and testing for absence of voltage, per your site's procedure under NFPA 70E, 2024 edition; STO is never a substitute for that isolation. For coast-stop versus deceleration behavior on a specific small drive, see the coast stop and deceleration time explanation; for a braking resistor deceleration setup on a GS20 drive, the article on GS20 braking resistor parameters covers the settings.

Questions asked

Can I open the output contactor to shed the load?

Not as the primary method. Switching an energized drive output is only allowed where the drive manufacturer documents an approved sequence for it, and a contactor that opens under load adds wear and re-close synchronization problems. Send a stop command through the drive's control path instead, and let the drive remove torque itself.

Does a fault reset work as a trip?

No. A fault reset clears an eligible fault; it is not a stop command. If a run request is still active, resetting the fault restores operation, which is the opposite of shedding. Keep fault acknowledgement out of the shedding logic entirely.

Is Safe Torque Off the same as electrical isolation?

No. STO removes the drive's ability to produce motor torque through its safety function, but the incoming supply and stored DC-link energy remain present. Never treat STO as isolation for electrical work; lockout and a test for absence of voltage are still required before opening the drive.

Why does my drive trip on overvoltage when I shorten the deceleration ramp?

A short ramp forces the motor to brake hard, and the rotating energy flows back into the drive's DC link faster than the drive and its braking equipment can absorb it. The link voltage rises until the drive trips. Lengthen the ramp or verify the installed braking resistor or other energy-handling means before shortening it again.

What restart interlock should the shedding sequence have?

Check every restart path: a maintained run command, restored communications, cleared STO inputs and fault recovery can each restart the drive on their own. Test the sequence functionally with the shedding request active to prove the motor stays stopped.

Keep reading

  • Troubleshooting

    Setting a GS20 drive for braking resistor deceleration stops

    With a braking resistor installed on B1 and B2, set P06.01 (overvoltage stall prevention) to 0 so the resistor carries the deceleration energy and the drive holds its programmed ramp. Then confirm the resistor leads land on B1 and B2 alone and that its resistance and duty match the model's selection data.

    Variable frequency drives

  • Troubleshooting

    Why a VFD DC bus overvoltage fault appears at random

    One ~670 V DC sample sitting between steady ~570 V readings in a 400 V drive's fault log is the fingerprint of a regenerative spike lasting a few milliseconds. An overhauling load through a high-ratio gearbox pumps energy back faster than V/Hz control and the brake chopper can absorb it. Move the drive to sensorless vector control, run auto-tune, lengthen the decel ramp and raise the regen power limit.

    Variable frequency drives

  • Troubleshooting

    Why a VFD overvoltage fault shows with no motor connected

    With the motor disconnected, no energy returns to the drive, so an overvoltage fault can only mean the DC link is being charged past its trip level from the line side. Measure all three line-to-line voltages: sustained high input, a capacitor-switching transient, or a failed sensing board are the remaining causes, in that order of testing.

    Variable frequency drives