Explainer
What megger trend lines actually predict about motor failure
Short answer
A megger trend line predicts ground-path failures only: moisture, carbon tracking and contamination slowly lowering winding-to-frame resistance. Trend critical DC and wet AC motors annually to twice yearly under matched temperature, humidity and test conditions, using IEEE 43-2013 limits as the floor. A passing reading predicts nothing about phase-to-phase faults, bearings or sudden failures, so test the rest of the AC fleet only after a trip, blown fuse or retermination.

On this page
- What can a falling megger trend actually warn you about?
- What can a megger test never predict?
- Which test conditions must you hold steady before comparing readings?
- What does IEEE 43-2013 say the reading should be?
- How often should scheduled megger testing run?
- What do you do when the trend line crosses your limit?
- Is a scheduled megger program worth the labor at your plant?
- Questions asked
A megger trend line predicts one thing well: a winding that is slowly growing a conductive path to ground. Test the same motor the same way, at similar temperature and humidity, and a steady fall in insulation resistance flags carbon tracking, moisture and contamination weeks or months before a trip. It predicts nothing about phase-to-phase winding faults, bearings or sudden mechanical failures, so schedule the test only where ground paths are the real risk: DC machines at every brush check, wet and contaminated critical AC motors annually to twice yearly. Everything else gets tested after an event.
What can a falling megger trend actually warn you about? #
A logged decline in insulation resistance catches exactly one failure family: conductive leakage paths from the winding or commutator to frame, built by carbon brush dust, moisture ingress, oil-borne contamination and gradual thermal aging of the ground wall. Those mechanisms develop over months, which is the window a trend covers.
That is why DC machines are the classic case. Carbon brushes wear continuously, the dust is sticky and conductive, and it tracks across insulation surfaces toward frame. Oil mixing with the dust cements it in place. Plant experience with forced-ventilated mill motors shows the limits of housekeeping: even with filters and regular cleaning at brush checks, carbon and airborne scale still worked into the windings and pulled the readings down year over year. A trend line built from each motor's own log made that decline visible while the machine was still in service, so the rebuild could be planned into a shutdown instead of ordered by an unplanned stop.
Moisture does the same job faster. A motor that sits in a damp corner or a washdown area loses insulation resistance until it dries out, and a log shows whether the drying is keeping up or the contamination underneath is getting worse. Thermal aging of the ground wall is slower still, but it is the mechanism the long trend catches on machines a decade old.
What can a megger test never predict? #
A passing ground-insulation reading says nothing about phase-to-phase or turn-to-turn winding faults, bearings, vibration or rotor problems, and those are the modes behind most sudden motor deaths. A motor can read clean to frame today and fail tomorrow for reasons the test never measures.
The reason is physical. An insulation tester applies voltage between the winding and the frame, so it sees one wall of insulation only. A fault that starts between adjacent turns or phases inside the slot has no path to frame until it burns through, and by then the trend line is irrelevant. If you have seen a motor read well to ground yet trip its breaker on start, the start-related fault mechanisms in why a motor meggers good but trips the breaker on start explain the gap. For how phase-to-phase readings differ and what they can and cannot show, the guide on megger test results and why phase-to-phase values differ covers that test configuration in depth.
So set expectations correctly at your plant: the megger is one data point beside vibration, bearing temperature and trip history, not a certificate of motor health. Plants that rely on it as the whole story are consistently surprised by sudden failures, which is the most common objection to funding the program.
Which test conditions must you hold steady before comparing readings? #
Only readings taken under matched conditions form a trend: same test voltage, same points winding-to-frame, similar winding temperature and humidity, and the same applied time. Winding temperature alone roughly halves resistance for every 10 °C rise, and a damp morning reading can sit an order of magnitude under the same motor measured dry in the afternoon.
The discipline that makes trends work is boring and absolute. Record the winding or ambient temperature, the humidity, the tester and its voltage, the elapsed time, and the exact test points for every reading, on every motor, in that motor's own log. Never compare a reading from the armature commutator to frame on a DC machine against a later stator reading, and never compare a switchgear-side reading with a terminal-box reading as if they were the same test. The guide on motor megger trending with controlled test data walks through which variables to pin down and how to log them. Before you open the terminal box, de-energize, lock out and verify absence of voltage, and discharge the winding after each test, because the tester stores hazardous energy in the winding capacitance.
What does IEEE 43-2013 say the reading should be? #
IEEE 43-2013 sets minimum acceptable insulation resistance for AC and DC rotating machine windings: for most windings built after about 1970, the minimum is the machine's rated voltage in kV plus 1 MΩ, corrected to a 40 °C base, and the polarization index should be at least 2.0 for Class B, F and H insulation. Confirm the exact clause against the standard and the machine's documentation before you adopt the number.
Worked example for a 460 V AC induction motor, tested winding-to-frame with a 500 V DC tester for 60 seconds, winding at 25 °C, reading 100 MΩ:
- Temperature correction to the 40 °C base, using the approximation that resistance halves per 10 °C rise: divide by 2^((40 − 25) ÷ 10) = 2^1.5 ≈ 2.83, giving 100 MΩ ÷ 2.83 ≈ 35.4 MΩ.
- Minimum from IEEE 43: 0.46 kV + 1 MΩ = 1.46 MΩ.
- Decision: 35.4 MΩ clears 1.46 MΩ by two orders of magnitude. The motor passes, and the corrected value is the one that goes in the log.
The corrected figure is an estimate, so check it against IEEE 43-2013, the tester's documentation and the motor manufacturer's data. For the test voltage itself, the choice depends on the winding's rating and construction; the guidance in megger test voltage for servo and induction motors covers how that selection is made. Note that the informal shop rule of 1 MΩ for every 1000 V of rated voltage sits below the IEEE 43 floor for low-voltage machines; use it only as a rough field check, never as the acceptance criterion.
A single passing value is not the point of the program. Three annual corrected readings of 1000 MΩ, then 300 MΩ, then 80 MΩ all clear 1.46 MΩ, but that slope is the actionable signal: it says a conductive path is growing, and it gives you time to plan cleaning, drying or a rebuild on your schedule.
How often should scheduled megger testing run? #
Schedule the test annually to twice yearly, and only on motors where a ground path is the dominant risk: DC machines at every brush check, critical AC motors of any size, and anything in wet, dusty or washdown service. The general AC fleet is tested event-driven, not on a calendar.
Documented plant programs follow that split. One steel-mill program tested 500–2500 hp, 600 V DC mill motors twice yearly alongside critical AC TEFC and TENV machines of any size; another plant tested the important motors on older machines once a year. Both kept per-motor logs and both acted on the trend, not on any single number. For the rest of the fleet, the triggers are events: any motor or cable change, a cable retermination, an overload trip, a blown fuse or a suspected electrical fault. When the event involves the cable, test it too, against the acceptance levels for 600 V power cable insulation resistance tests rather than the rotating-machine values above. Baseline a new reading after seal or bearing replacement as well, since that work opens the machine and can admit contamination.
What do you do when the trend line crosses your limit? #
Clean first, decide second: blow the machine out with dry air, wash or dry the winding as your motor shop directs, then repeat the identical test under the same conditions. If the corrected value recovers and holds, contamination was the cause and the motor stays in service; if the corrected trend keeps falling across two consecutive tests, plan replacement or rebuild at the next shutdown.
Judge the machine against its own history, not against a universal cutoff. One mill program knowingly ran large DC machines at corrected readings as low as 50 kΩ after cleaning while a replacement was being readied, monitored and scheduled — a site decision built on that fleet's history, not a number to copy onto a random-wound AC motor. Where a trip value comes from, state it in your own maintenance standard per motor class and keep it consistent.
For planned-maintenance evaluations on larger machines, add the polarization index: the ratio of the 10-minute to the 1-minute reading. An index of 2.0 or better supports the insulation, and a low index on a machine whose one-minute value just barely clears the minimum is a rebuild order waiting for a shutdown window.
Is a scheduled megger program worth the labor at your plant? #
Commit the labor where it pays: every DC machine with carbon brushes gets a winding-to-frame reading at each brush inspection, critical and wet-contaminated AC motors get a logged test once or twice a year under matched conditions, and everything else gets tested after a trip, a blown fuse, a retermination or a motor swap. That split is the decision.
The economics support it. A trend that flags contamination months out turns an emergency motor change into a planned rebuild, and on a DC machine an unplanned failure can cascade into drive and line replacement if no spare exists. The same test spread across a thousand healthy general-purpose AC motors returns almost nothing, because those motors fail by mechanisms the megger cannot see. Run the program on the assets where ground paths actually kill the machine, log every reading against that motor's own history, and treat the result as one voice among vibration, bearing temperature and trip history — the test that catches the slow leak to ground, with no pretense of catching the rest.
Questions asked
How long do I apply the megger voltage before reading?
IEEE 43-2013 bases its acceptance values on a 60-second application of the test voltage, and the polarization index uses the ratio of the 10-minute reading to the 1-minute reading. Hold the same duration on every test you intend to trend, because insulation resistance on a healthy winding keeps climbing while the voltage stays applied.
Can I megger a motor while it is still connected to the drive?
No. Disconnect the motor leads from the drive or follow the drive manual's testing procedure, because the tester's DC output can damage drive electronics and the reading would not represent the winding alone. Isolate the motor, test it to frame, and test the feeder cable separately if the cable is also in question.
Does the polarization index help on small random-wound motors?
It helps least where the winding already reads very high. A small random-wound motor measuring in the gigohm range has little room to rise between one and ten minutes, so the index adds little there. The index is most informative on larger machines whose insulation resistance is low enough to show a clear upward climb during the test.
How many readings make a usable trend line?
Treat three comparable results on the same motor as the minimum before acting on a slope, and log the cleaning, repair, bearing and seal work dates beside each value. A reading that only departs from history after a wash-out or a rewetted shutdown is not the same signal as a steady decline on an untouched machine.