Explainer
Megger test voltage for servo and induction motors
Short answer
Megger a servomotor power winding at 500 V DC only after the feedback, encoder and brake circuits are disconnected; drive electronics do not survive winding-test voltage. A used induction winding rated above 100 V takes 1.5 times rated voltage with a 1000 V DC floor, stepped up from 500 V on a clean, dry winding. The acceptance resistance comes from the motor documentation, not a universal table.

On this page
- What megger voltage do you use on a servo motor winding?
- What megger voltage do you use on a used induction motor?
- Why disconnect the encoder and brake circuits before you megger a servo?
- How do you prepare a used winding so the reading means anything?
- How do you raise the test voltage on a marginal winding?
- What insulation resistance reading counts as good?
- Why does a motor megger good and still trip the breaker on start?
- What do you do when a winding reads low?
- Questions asked
Megger a servomotor power winding at 500 V DC with the feedback, encoder and brake circuits electrically disconnected, and megger a used induction winding rated above 100 V at 1.5 times its rated voltage with a 1000 V DC floor, stepped up from 500 V on a clean, dry winding. The acceptance resistance is the one number that does not come from a rule: it comes from the motor's own documentation, read against a fixed test time and a recorded winding temperature. Everything below is how those numbers get applied without wrecking the electronics that share the motor's connectors.
What megger voltage do you use on a servo motor winding? #
Test a servomotor power winding at 500 V DC, and only after the feedback, encoder and brake circuits are electrically disconnected, because the tester applies its full voltage to everything between its leads and those electronics do not survive a winding-grade test.
The measurement itself is ordinary: join the power leads, clamp one tester lead on them and the other on the bare frame metal with the paint scraped from under the clip, and read. What separates the servo job from a duty-motor job is what shares the connectors — resolver or encoder, brake rectifier, temperature sensors — and those circuits come off before the leads go on, as the next section covers.
Record the full motor identification from the nameplate first, because the acceptance limit in the documentation attaches to that identification, not to the family name on the housing. Whichever family the axis carries — the selection guide comparing 1FT7 and 1FK7 servomotors walks through that choice — the procedure is the same: isolated power winding, known voltage, recorded temperature.
What megger voltage do you use on a used induction motor? #
For a used asynchronous induction winding rated above 100 V, the common maintenance practice is 1.5 times the rated voltage with a 1000 V DC floor, applied to a winding that has been cleaned and dried, and reached in successive steps from 500 V.
The multiplier-and-floor rule is maintenance practice for service-aged windings, not a factory acceptance test, and it assumes a clean, dry winding — a damp or dirty one gets whatever number the moisture dictates, not the insulation's. Worked example, 400 V winding: 1.5 × 400 V = 600 V, which sits under the floor, so the floor governs and the test runs at 1000 V DC. A 690 V winding works out to 1035 V DC by the same multiplication, just clear of the floor, so there the multiplier governs. Treat those results as an estimate of practice and check them against the machine's documentation before the leads go on.
When the motor's own instruction names a test voltage, that voltage and its stated duration replace the rule outright. For the standard's own frame on ordinary induction machines, the article on which test voltage applies when meggering an IEC induction motor covers the selection from the IEC side.
Why disconnect the encoder and brake circuits before you megger a servo? #
Disconnect the feedback, encoder, brake and temperature-sensor circuits before the leads go on, because a powered-down drive still holds the motor side of its output semiconductors in circuit, and winding-test voltage that a stator shrugs off destroys those electronics.
Isolating the drive supply is not isolating the winding. The tester applies its voltage to everything electrically between its leads — cable, connectors, the drive's output stage — and semiconductors do not care that the cabinet is switched off when they are still soldered into the path. A shared connector housing proves nothing about the rating of each pin in it, so the accessory connectors come off per the machine's wiring diagram and the power terminals get positively identified before the clamps close.
Decide the cable question deliberately and write down which way you went, because a reading taken with the cable in describes cable-plus-winding, not the winding. Where the boundary sits decides what a number convicts; the article on insulation resistance testing from switchgear versus motor terminals covers the same boundary question for machine circuits. If the first reading comes in low with the cable still connected, the move is to split the boundary, not to lower the voltage.
How do you prepare a used winding so the reading means anything? #
Clean the winding and dry it before you read, because moisture and conductive dust on the end turns and terminal surfaces form leakage paths that pull the number down with nothing actually wrong inside the ground wall.
One safety note, and it comes before all of this: de-energize the circuit, lock it out and verify the absence of voltage at the terminals before the terminal box opens, then treat the tester's own output as live until its discharge cycle has finished. NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, covers the safe work practices this sequence follows; your authority having jurisdiction and the equipment documentation govern the details.
With that done, clean accessible surfaces by a method the motor instruction allows and dry by a controlled method, because unsuitable solvents and uncontrolled heat ruin good insulation along with the contamination. Record the winding temperature before the leads go on so the reading has a reference. Storage cases are their own discipline, and a machine that sat for months gets the fuller workup in the article on testing a stored vintage motor before it goes on a VFD.
How do you raise the test voltage on a marginal winding? #
Climb in successive steps from 500 V toward the target and stop if a step reads low, because a clean bill of health at a lower voltage never authorizes the next voltage up on a marginal winding.
If the motor's instruction names a test voltage outright, apply that voltage for its stated duration and skip the ladder — the stepped climb is the practice for used windings under the multiplier-and-floor rule when the documentation is silent. Raise, hold, read, and climb only when the step reads comfortably.
The ladder is not a rescue: more voltage does not make a weak ground wall stronger, it punches through the weakness the lower step only exposed, and a winding that will not hold one step has told you what it is. It is not a withstand test either — the resistance check diagnoses condition, while a dielectric withstand test proves a specified stress against a specified pass rule, and improvising the second from a megger destroys insulation that was serviceable.
What insulation resistance reading counts as good? #
The acceptance value comes from the motor's own documentation, compared against a reading taken at a fixed elapsed time — 60 s is the common service convention — on a winding whose temperature you recorded at the moment of test.
The instrument reports R = V/I, the applied DC voltage over the current it measures, and in the first seconds that current includes charging and absorption components, so a reading at one elapsed time is not interchangeable with a reading at another. Hold the voltage for the stated time and write the resistance and the winding temperature down together.
Temperature moves the number hard: insulation resistance roughly halves for every 10 °C rise, so a hot reading and a cold one are not the same animal. IEEE Std 43-2013, the recommended practice for testing insulation resistance of rotating machinery, is the reference the acceptance limits in motor documentation are built against, and the trend against last year's test at matched voltage, time and temperature matters even when the latest value passes. A reading past the end of the scale means the resistance exceeds what the meter resolves, not that insulation is infinite.
The decision: at or above the documented limit on a clean, dry winding at a recorded temperature passes; below it, the winding fails acceptance until cleaning, drying or repair brings the retest back over.
Why does a motor megger good and still trip the breaker on start? #
A winding can pass the ground-wall test and still short turn-to-turn, so a motor that reads well to frame but trips its breaker on start has a fault the megger was never built to see.
The ground-wall test stresses insulation between the winding as a whole and the frame. It never stresses insulation between adjacent conductors, so a handful of shorted turns can sit happily above the acceptance limit to frame and still collapse the winding's impedance when the contactor closes — which the breaker sees as a fault current, not as a pass. That is the division of labor: the megger clears the path to ground, the start current tells you about the copper inside the slots.
The article on a motor that meggers good but trips the breaker on start works that case end to end, including the supply and load checks a winding test cannot reach.
What do you do when a winding reads low? #
Clean it, dry it and split the circuit before condemning the winding, because most low first readings recover once moisture and contamination leave, and a combined motor-plus-cable measurement proves only that one of the two is wet or failed.
Split the circuit first: retest with the cable disconnected and only the winding between the leads, and if the cable needs a number of its own, test it to its own procedure and its own limit. Clean and dry by the allowed methods, hold the drying until the resistance stabilizes instead of grabbing the first recovering value, then retest at the same voltage, the same duration and a recorded temperature so the two readings actually line up.
If the retest still sits under the acceptance limit, the winding has failed and the choice is rewind or replace — the megger has done its job, which is ending the argument with a number. If it recovers, write down the recovered value and what was done to get it, because that record is what makes next year's comparison worth anything.
Questions asked
Can I megger the motor through its attached cable?
You can, and a combined test that reads well proves both the cable and the winding above the limit in one pass. A low combined reading, though, does not say which part failed, so split at the terminal box and test the winding and the cable separately before you order a rewind or a new cable.
What voltage applies to a winding rated below 100 V?
The multiplier-and-floor practice is quoted for windings rated above 100 V. Windings rated lower, and the low-voltage circuits around them, take whatever test voltage the motor documentation specifies, because applying a 1000 V floor across insulation and electronics never sized for it causes the damage the test was meant to prevent.
How long do you hold the test voltage before reading?
Hold it for whatever time the motor instruction states. Where none is given, the 60 s reading is the common service convention, and it only compares cleanly against readings taken at the same elapsed time, the same voltage and a recorded winding temperature.
Does the motor need discharging after the test?
Yes. The winding and any attached cable hold a capacitive charge at the test voltage after the leads come off, and that stored charge is a genuine shock hazard. Let the tester's discharge cycle run to completion and verify the terminals before anyone touches them, the same absence-of-voltage check you performed before the test.
What do you test the encoder and brake circuits with?
Not with the winding tester. Feedback, encoder and brake electronics carry insulation never meant for winding-test stress, so their checks are the low-voltage continuity and resistance measurements the motor and drive documentation describe. If a brake coil's own insulation needs a number, its documentation supplies both the voltage and the limit for it.