What NEMA MG-1 start clauses mean for motor start inhibits
Short answer
MG-1 parts (a) and (b) are capability statements: two starts in succession from ambient, and one start from rated load operating temperature. They do not set a starts-per-hour rate or a restart delay. Program a start inhibit only from the motor and starter manufacturer's stated duty.

On this page
NEMA MG-1 gives motor starting capability, not a restart timer. Part (a) allows two starts in succession, coasting to rest between starts, with the motor initially at ambient temperature. Part (b) allows one start with the motor initially at a temperature not exceeding its rated load operating temperature. Those two statements are the whole answer the standard provides: no starts-per-hour rate, no cooling delay, no recovery time after the second start. The starts-per-hour figure or restart-inhibit timer you program into a protection relay must come from the motor manufacturer's stated duty for your application, possibly adjusted for the starting method, not from MG-1 alone.
What parts (a) and (b) actually say #
Both clauses are conditions the motor is designed to meet, stated in the same spirit as the temperature-rise limits in MG-1 Part 31 for inverter-fed motors: they define what the machine tolerates, not how often you may use it.
- Part (a), the cold-start capability: the motor starts once from ambient temperature, coasts fully to rest, then starts again. "In succession" means the two starts form one stated sequence. It does not license a second start while the rotor is still turning, and it does not state how long you must wait after the second start.
- Part (b), the warm-start capability: the motor may make one start from a temperature not exceeding its rated load operating temperature. Rated load operating temperature is far above ambient, so a motor that has been running and then tripped or stopped is normally still within that limit, and one restart is within the stated capability. The clause does not grant unlimited warm restarts and does not name the wait before the next one.
Why starting is the hard case #
The limit exists because a start is the worst thermal and mechanical event the machine sees. At standstill the rotor bars see line-frequency induced current at high magnitude, heating the bars and the short-circuit ring quickly while there is no circulating air to cool them. Once the motor is running, the rotor frequency drops to a small fraction of line frequency and its heating and cooling conditions change completely. This is why larger motors are usually rotor-limited for consecutive starts, while smaller machines are more often limited by the stator winding's ability to shed heat. The relevant engineering background is set out in IEC 60034-12, which limits the locked-rotor apparent power a motor may draw; a related article explains what IEC 60034-12 actually limits on motor starting current.
A start-stop-stop-start sequence therefore stresses the machine differently from a long continuous run, and a timer based only on elapsed time since the last start is a control approximation, never proof that the rotor has cooled.
Cold starts, warm starts and starts per hour are three different statements #
Keep the three apart, because relay settings are built from them one at a time.
| Statement | What it specifies | What it does not specify |
|---|---|---|
| Cold-start capability | Number of starts from ambient, coasting to rest between them | Running time between sequences, recovery after the last start |
| Warm-start capability | One start from up to rated load operating temperature | Any second warm start, or the wait before one |
| Starts per hour | Starts allowed over an interval, with the associated run and rest sequence | Anything, unless the manufacturer supplies the complete sequence |
Two starts from ambient with a short inter-start rest do not tell you how many starts the next hour allows, and one warm start does not establish when the next warm start is permissible.
Worked example: the autotransformer starter wording #
A starter manufacturer states two conditions. First: two starts from ambient, each not exceeding 30 seconds, with a 30-second rest between them. Second: one start of 30 seconds only if the controller was pre-loaded with the autotransformer off the circuit for at least one hour.
Decode the first condition as a bounded sequence, not a rate:
- Start 1: no more than 30 seconds of acceleration or run.
- Coast to rest, then 30 seconds at rest.
- Start 2: no more than 30 seconds.
- Recovery after start 2: not stated.
The arithmetic of the sequence is therefore 30 s start + 30 s rest + 30 s start = 90 seconds of defined activity, and nothing more. A third start, a shortened inter-start rest, or a post-sequence delay read into the wording would all be assumptions beyond the stated duty. On a 5 kV, 300 hp machine on an autotransformer starter, an acceleration attempt that nears the 30-second limit is itself a warning: that motor is spending most of its permitted thermal budget per start, and repeated or extended attempts will overheat the rotor bars even though the line current at the autotransformer tap looks modest.
The second condition is ambiguous as written: "pre-loaded with the autotransformer off the circuit" does not make clear whether the one hour applies to the motor, the controller or the transformer, or to which preceding operating condition. Ask the starter or motor manufacturer to define it before encoding the phrase as a generic restart delay. A related article covers how an autotransformer starter fails during a voltage sag, which is the other failure mode this starting method brings.
Translating the duty into a start inhibit #
Most modern motor protection relays provide a start-inhibit or restart-supervision function: a setting that blocks a start command until an elapsed timer expires or a start counter clears. The generic behavior to configure, described without reference to any one parameter name, is:
- Obtain the motor manufacturer's cold- and warm-start capability, maximum start duration, permissible run and rest sequence, and recovery requirement, together with the starter's stated sequence and the clarified one-hour condition.
- Decide which event starts the inhibit timer: the completed start, the stop, or the start command.
- Decide whether the timer continues while the motor is stopped, and what releases the inhibit.
- Program the earliest of the manufacturer's limits, so the inhibit never permits a start the duty statement does not.
- Record the reasoning against the motor's documentation so the next engineer does not re-derive it.
If the approved duty turns out to be one start per hour, a simple timer started at each start and timing through the stop satisfies it. If the duty is one cold sequence plus one warm start, the logic must count starts, not just time, and release after the correct combination. Do not copy a starts-per-hour figure from another motor: a different machine's permitted starts, run intervals and cooling conditions establish nothing about this one.
One safety note: setting or reading relay configuration on a live 5 kV starter is energized work. De-energize, lock out and verify absence of voltage per NFPA 70E, 2024 edition, before opening the panel, and confirm the applicable requirements with your local authority having jurisdiction and the equipment documentation.
The decision for each case #
- Motor at ambient, stopped, rotor at rest: part (a) supports two starts with coasting to rest between them, each within the starter's stated duration limit, here 30 seconds, and 30 seconds of rest between them. After the second, do not start again until the manufacturer's recovery data says so.
- Motor just stopped after running: part (b) supports one start, because the machine is at or below its rated load operating temperature. Beyond that one start, the wait comes from the manufacturer's duty, not from the standard.
- No manufacturer duty statement in hand: leave the existing inhibit in place and obtain the data. A guessed timer can either permit a damaging start or block a machine longer than its approved duty requires, and both outcomes cost more than the phone call.
Questions asked
Can I restart a motor that just stopped while it is still warm?
Part (b) of the MG-1 start clauses allows one start when the motor is initially at a temperature not exceeding its rated load operating temperature. A motor that has been running and then stopped is normally below that temperature, so one restart is within the standard's stated capability. The number of further warm starts and the recovery time between them must come from the motor manufacturer's stated duty, not from the standard.
Does two starts in succession mean I can start it twice per hour?
No. Part (a) defines one bounded sequence: two starts from ambient, coasting fully to rest between them. It says nothing about running time between sequences, recovery after the second start, or a rate per hour. A starts-per-hour figure requires the manufacturer's complete duty statement for that motor and application.
Why does the rotor limit consecutive starts on larger motors?
At standstill the rotor sees line frequency induced into its bars, and the high starting current heats the rotor bars and short-circuit ring severely while no forced airflow cools them. Once the motor is running, the rotor frequency drops well below line frequency and its heating and cooling conditions change, so repeated starts from rest stress the rotor far more than continuous running does.
How long after two starts from ambient can I start again?
The standard does not state a recovery time after the second start, and the starter wording in this example gives a 30-second rest between the two starts but no interval after the pair. Program a recovery time only from the motor manufacturer's stated duty. Until that data is in hand, keep the existing inhibit in place rather than replacing it with a guessed delay.