Motors and motor starters Published 9 min read By Current Intel engineering team

Short answer

A soft starter breaks a load away only when the square of the voltage ratio times the motor's locked-rotor torque exceeds the load's breakaway torque. With k as initial voltage over line voltage, standstill torque is roughly k² of locked-rotor torque while standstill current scales only with k. Compute the minimum initial voltage from the two torques, set one panel step above it, and fix a stalled start with voltage, not ramp time.

On this page
  1. Why does a motor hum without turning on the initial start voltage?
  2. How fast does motor torque fall when the start voltage drops?
  3. What initial start voltage breaks the load away?
  4. Where do you read locked-rotor torque and breakaway torque?
  5. Does a longer start ramp time fix a stalled start?
  6. What happens when the initial start voltage is set too high?
  7. How does the current limit change the breakaway margin?
  8. How do you verify the initial start voltage on the floor?
  9. Questions asked

A motor that hums, twitches and refuses to turn on a soft starter is not asking for a longer ramp; it is telling you the initial start voltage produces less torque than the load needs at standstill. Induction-motor torque falls with the square of applied voltage while current falls only in proportion to it, so the minimum initial voltage comes from one comparison: the square of the voltage ratio times the motor's locked-rotor torque against the load's breakaway torque. Work that comparison from the two datasheet torques, set the panel step above the result, and a stalled start becomes an immediate breakaway. This article derives the square law, works it through an illustrative 45 kW motor, and separates the jobs of start voltage and ramp time.

Why does a motor hum without turning on the initial start voltage? #

The motor sits still because the initial voltage leaves the shaft less torque than the load needs to break away: the starter applies k times line voltage, the motor delivers k² times its locked-rotor torque — half the voltage, a quarter of the torque — so the load wins the first instant.

A humming, motionless rotor is a locked-rotor condition. The stator is energized, slip is at maximum, and the line feeds roughly k times the locked-rotor current, but that current does no mechanical work: it lands as heat in the stator, the rotor bars and the starter's thyristors, which is why a stalled attempt must be measured in seconds, not in ramp durations. Rule out the mechanical twins before touching the setting — a jammed conveyor, a seized bearing or a load frozen by cold product holds the shaft exactly as still. Turn the shaft by hand under lockout; if it moves freely, the electrical explanation stands.

How fast does motor torque fall when the start voltage drops? #

Torque falls with the square of the applied voltage while current falls only in proportion to it: at 40% voltage the shaft develops about 16% of locked-rotor torque and the starter still draws about 40% of locked-rotor current, which is why low settings stall silently and hot.

Write k for the fraction of line voltage the starter conducts at any instant — 0.6 means 60% — T_LRT for the motor's locked-rotor torque at full voltage and I_LRT for its locked-rotor current. Standstill torque is k² × T_LRT; standstill current is about k × I_LRT. A soft starter shapes the voltage wave by delaying each half-cycle's conduction, so the exact torque at a given conduction angle varies a little between models; the applied-voltage square law is the design basis every reduced-voltage starting manual works from. The table below assumes the linear-current approximation and ignores saturation: it is the standard reduced-voltage relation, not a vendor curve.

Initial voltage, k Standstill torque, share of locked-rotor Standstill current, share of locked-rotor
0.30 9% 30%
0.40 16% 40%
0.50 25% 50%
0.60 36% 60%
0.70 49% 70%

What initial start voltage breaks the load away? #

Set the initial voltage so k² times the motor's locked-rotor torque clears the load's breakaway torque with margin: the minimum is the square root of breakaway torque over locked-rotor torque, and the setting should sit one or two panel steps above it.

In symbols, k_min = √(T_b / T_LRT), with T_b the load's breakaway torque, both torques in newton-metres from the datasheets. The inputs and the result below are illustrative: an estimate to be checked against the motor datasheet and the starter manual before it becomes a setting.

  • Inputs, illustrative: a 45 kW, 4-pole motor on a 400 V, 50 Hz line, 1480 rpm full-load speed, 80 A full-load current, datasheet locked-rotor torque 160% of full-load torque; machine data puts load breakaway at 45% of full-load torque.
  • Full-load torque, from the power-speed relation T = 9550 × P ÷ rpm: 9550 × 45 kW ÷ 1480 rpm = 290 N·m.
  • Locked-rotor torque: 1.60 × 290 N·m ≈ 465 N·m.
  • Load breakaway: 0.45 × 290 N·m ≈ 131 N·m.
  • Minimum ratio: √(131 ÷ 465) = √0.282 ≈ 0.53.
  • Set 60%: 240 V on the 400 V line gives standstill torque 0.36 × 465 N·m ≈ 167 N·m, a surplus of 36 N·m — about 28% above breakaway — at a standstill current of about 0.6 × (7.0 × 80 A) ≈ 336 A.

Check the 7.0 current multiple against the nameplate code letter rather than assuming it, and treat the 28% surplus as the point of the exercise: datasheet tolerance, a stiff cold bearing and feeder sag all shave terminal torque, and the surplus is what survives them. On simple starters the initial voltage is a rotary selector marked in percent of line voltage; on digital units it is a percent-of-line entry in the basic start parameters — the manual names it for your model, and no parameter map carries across brands.

Where do you read locked-rotor torque and breakaway torque? #

The motor's locked-rotor torque comes from the manufacturer datasheet or, for NEMA designs, from the minimum values tabulated in ANSI/NEMA MG 1-2016 (Revised 2018); the load's breakaway torque comes from the machine builder's data or a measured trial at the lowest stable start voltage.

MG 1 sets minimum locked-rotor torques per horsepower and speed in Table 12-2 for Design A and B motors, and raises the values for high-torque duty in sections 12.38.2 and 12.38.3 for Design C and D; IEC machines carry equivalent minimums under IEC 60034-1. The nameplate design letter selects the table; the code letter gives locked-rotor current only, never torque. For the load side, ask the machine builder for breakaway in newton-metres or as a share of the motor's rated torque. When the data is missing, bracket it on the floor: the lowest step that turns the shaft immediately puts an upper bound just above the requirement, the step below it shows the requirement is not yet met, and keep each stalled trial to a few seconds so repeated locked-rotor heating stays small.

Does a longer start ramp time fix a stalled start? #

No — ramp time changes how fast voltage climbs once the start begins, but standstill torque is set by the initial voltage alone: if the motor has not broken away by then, a longer ramp only stretches the time it sits stalled at high current, heating windings and thyristors.

The ramp's only job is to pace voltage from the initial step to full voltage; acceleration time is decided by the torque surplus along the speed axis, not by the ramp clock. Ramp much longer than the acceleration and the motor crawls in a reduced-voltage, high-slip state that adds rotor heat; ramp shorter than it and full voltage arrives while the rotor is still slow, spiking the current and handing back the inrush the starter was installed to cut.

One cost does not depend on ramp shape at all: during acceleration the rotor circuit dissipates heat equal to the kinetic energy finally stored in the shaft, so a high-inertia fan costs far more heat per start than a pump whichever ramp you choose. That is the same heating trade-off behind Setting a soft starter current limit without overheating the motor. A stalled start needs more voltage at the first step, not more seconds on the clock.

What happens when the initial start voltage is set too high? #

Too high an initial voltage throws away the soft start: current rises roughly with k and torque with k², so the load takes a torque step that snaps belts, shifts product and hammers pipework while the supply sees most of the inrush it was there to avoid.

The audible signature is a thump and an instant snap to speed with the bypass closing almost at once; the mechanical signatures are coupling shock, conveyor product shift and pump water hammer, because the starter exists to limit torque as much as current. Soft starter literature describes pre-settable start voltages anywhere from 10% to 70% of line voltage and instructs setting them to achieve at least breakaway — a wide band, so the calculation, not the default dial position, picks the point. The discipline is the lowest step that breaks away immediately and keeps the margin the torques call for.

How does the current limit change the breakaway margin? #

A current limit clamps the voltage the starter delivers, and clamped voltage means squared torque loss: a limit that pulls the terminal voltage down to k cuts the standstill torque to k² of locked-rotor torque, so a start that breaks away at full voltage can still stall under the limit.

Set the initial voltage for breakaway first, then confirm the limit leaves at least that voltage available at standstill. When the limit clamps conduction below the breakaway point, the rotor sits stalled at high current exactly as before — the fault path, read from the current side, is the one in why a large motor stalls when the soft starter hits current limit. Raising the limit to rescue a low initial voltage merely re-creates direct-on-line current; the two settings are one decision, not two.

How do you verify the initial start voltage on the floor? #

Log one start with a clamp meter: current should step to a plateau near k times locked-rotor current, fall as the motor accelerates and drop to running current when the bypass closes; a flat high plateau means the shaft never broke away or the ramp outlasts the acceleration.

Making the meter connections means opening the starter enclosure or the motor terminal box, so de-energize, lock out and verify absence of voltage before touching a conductor; where the logged start must run with the panel open, NFPA 70E, 2024 edition, governs the risk assessment and protective equipment, and your local authority having jurisdiction and the starter documentation have the final word.

The judgement points, in order:

  1. Read the nameplate and datasheet: full-load current, full-load speed, design letter, locked-rotor torque and locked-rotor current.
  2. Compute the minimum ratio from breakaway and locked-rotor torque; set the initial voltage one to two steps above it and the ramp to a mid-range value.
  3. Connect the clamp meter to one motor lead under the completed lockout, then restore power.
  4. Start and listen: breakaway must be immediate. A hum longer than a second or two means raise the initial voltage one step and retry, keeping every stalled attempt to a few seconds.
  5. Watch the end of the ramp: a current spike means full voltage arrived before full speed; lengthen the ramp modestly or lift the initial step so acceleration finishes inside it.
  6. After consecutive starts, check motor frame and starter temperature against the motor manufacturer's starts-per-hour guidance before the next attempt.

Questions asked

Does the voltage-squared torque rule hold while the ramp is climbing?

It applies instant to instant: the torque at any moment follows the square of whatever voltage the starter is conducting at that moment. It stays a standstill calculation. Once the rotor is turning, the torque available at a given voltage also depends on slip and speed, so the k-squared comparison sets the initial step and cannot predict torque part-way through acceleration.

How does a 5% supply sag during the start change the breakaway margin?

Torque follows terminal voltage squared, so a 5% sag leaves 0.95 squared, about 90% of the intended torque, roughly a 10% cut. The example's 36 N·m surplus would survive it, but a thinner margin could vanish. If the feeder run is long, estimate the sag from the start current and the feeder impedance before shrinking the setting.

Do NEMA Design C or D motors need a different initial voltage?

They change it in your favour. Design C and D motors carry higher minimum locked-rotor torque than the Design A and B values, which lowers the k you need for the same breakaway torque, so the same load starts on a lower voltage step with more margin. Read the nameplate design letter first, then the matching table or section.

Can the starter's boost or kickstart feature replace the calculation?

No. A boost pulse applies a higher voltage for a fraction of a second to snap through stiction, and it obeys the same square law: it works only if its voltage clears the breakaway point, and it draws the matching higher current while it runs. Treat the boost level as the initial voltage in the calculation and set the sustained step to the value you verified.

What if the load needs more torque than the motor's locked-rotor torque?

Then no setting on the starter can start it, because full line voltage only ever delivers the locked-rotor torque. Unload the machine first — valves, vanes, a clutch or a centrifugal coupling — or move to a motor design with higher locked-rotor torque or a drive that builds torque with frequency. Reduced voltage only cuts torque; it never multiplies it.

Keep reading

  • Explainer

    Why a 415 V delta motor cannot run on 240 V

    A plate that reads 415 V delta, with no second voltage-connection pair, describes single-voltage windings that need 415 V across each coil. On a 240 V supply the motor reaches about one third of rated torque in delta and about one ninth in star, so it will not serve as a full-rated rotary phase converter idler. Replace it with a motor whose plate reads 240 V delta or feed it through a step-up transformer.

    Motors and motor starters

  • Troubleshooting

    Why an oversized soft starter may not suit a smaller motor

    An 18.5 kW soft starter can sometimes stay on a 9.5 kW motor, but only after three checks: the starter's documented minimum motor current, the adjustable overload setting span, and the short-circuit coordination. Swap the breaker alone and one of those usually fails.

    Motors and motor starters

  • Explainer

    Why star-delta starting on motors under 5 hp buys you nothing

    You can use a star-delta starter at any motor rating, but no standard requires it, and under 5 hp it buys you nothing: a 5 hp, 460 V motor draws 7.6 A full load, so its DOL inrush is small against a plant feeder. Choose DOL unless the utility or a weak supply forces reduced-voltage starting.

    Motors and motor starters